International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

PDTracII 4208 continuous online partial discharge monitoring up to 35 kV

The PDTracII 4208 continuously measures partial discharge in the insulation of motors, generators, dry-type transformers and air-insulated switchgear up to 35 kV. It has three fixed 80 pF capacitive sensors, one per phase, and a monitor with a built-in network interface.

Equipment voltage class
up to 35 kV
Sensors
EMC 80 pF (6.9–35 kV), one per phase
Frequency band
0.1–350 MHz
Pulse amplitude
2–34000 mV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Partial discharges are small sparks within insulation that give early warning of an approaching failure. The system measures them automatically while the machine runs and builds a trend, which helps spot early insulation abrasion, loosening of stator slot wedges, thermal ageing and manufacturing defects. The results support condition-based maintenance and management of the service life of a fleet of machines.

Each phase gets an epoxy-mica EMC 80 pF coupling capacitor rated for 6.9–35 kV. Where 80 pF unbalanced sensors are already installed, the monitor can be connected to the existing terminal panel without stopping the equipment. As an option it can be set up for low frequency capacitive sensors of 1–2 nF. Noise separation relies on filtering and pulse shape analysis, which removes electrical interference and stops false signals when the equipment is connected by shielded cable longer than 30 m.

The monitor covers 0.1–350 MHz with pulse amplitudes from 2 to 34000 mV across 10 sensitivity steps, using 24 phase windows per cycle. Each magnitude window (+Qm and −Qm) in each phase takes 5 s to acquire, and synchronisation runs from 20 to 120 Hz. It produces phase-resolved PRPD patterns, pulse height analysis and the summary figures Qm and NQN. Qm is used for trending and for comparison with similar machines, using the maker's statistical tables.

The system can run standalone, with the archive read periodically over USB, or on a network via Ethernet (TCP/IP) and Modbus, and integration with SCADA is possible through Modbus TCP/IP. It has a relay alarm output for remote signalling and up to 8 analogue inputs for trending temperature, voltage, current and power. An optional humidity and ambient temperature sensor can be fitted. The operating range is 0…55 °C with humidity up to 95 % non-condensing, the monitor measures 56 x 45 x 23 cm, and modular hardware makes on-site repair and upgrades simpler.

Versions with enclosures and certifications for explosive atmospheres are available, marked Class 1, Division 2, Groups A, B, C, D; II 3 G Ex nA nC IIC T5 Gc; BR-ExnA nC IIC T5. The system conforms to IEEE 1434:2016, IEC 60034-27-2:2012 and IEC 62478.

Technical specifications

Equipment voltage classup to 35 kV
SensorsEMC 80 pF (6.9–35 kV), one per phase
Frequency band0.1–350 MHz
Pulse amplitude2–34000 mV
Sensitivity steps10
Phase windows24 per cycle
Acquisition time5 s per window (+Qm and −Qm) in each phase
Synchronisation frequency20–120 Hz
Analogue inputsup to 8
CommunicationUSB, Ethernet (TCP/IP), Modbus
Operating temperature0…55 °C
Relative humidityup to 95 % non-condensing
Monitor dimensions56 x 45 x 23 cm
Ex markingClass 1, Division 2, Groups A, B, C, D; II 3 G Ex nA nC IIC T5 Gc; BR-ExnA nC IIC T5
StandardsIEEE 1434:2016, IEC 60034-27-2:2012, IEC 62478

Request a price and lead time

PDTracII 4208 continuous online partial discharge monitoring up to 35 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can the PDTracII 4208 be connected to sensors that are already installed?

Yes, the monitor connects to existing 80 pF unbalanced sensors through the terminal panel without stopping the machine, and optionally to 1–2 nF sensors.

How does the system tell partial discharges from interference?

By filtering and pulse shape analysis, which removes interference, including when the equipment is connected by a cable longer than 30 m.

Can the monitor be used in a hazardous area?

Yes, versions are marked Class 1, Division 2 and II 3 G Ex nA nC IIC T5 Gc.