PDA-IV Portable Partial Discharge Monitor for Hydro Generators

A portable instrument for periodic online measurement of partial discharges in the stator windings of hydro generators fitted with epoxy-mica capacitor sensors. A measurement on a machine in operation takes under 30 minutes and does not interfere with its running.

Purpose
periodic online partial discharge monitoring of hydro generators
Sensor inputs
12
Frequency range
40 to 350 MHz (80 pF), 2 to 350 MHz (1 to 2 nF)
Pulse amplitude
2 to 34000 mV

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Insulation faults are among the main causes of unplanned outages in generators, motors, metal-clad switchgear and dry-type transformers. Partial discharges are an early sign of stator winding damage, so periodic measurement on a machine in service reduces the risk of sudden failure. The PDA-IV collects data under normal electrical, mechanical and thermal loads and detects abrasion of insulation, loosening of slot wedges, thermal ageing and manufacturing defects. The results are used to plan repairs of high-voltage rotating machines and to compare condition against the supplier's severity tables.

The instrument separates partial discharges from network corona, sparking on busbars and other interference by the shape of each pulse and its arrival time, and digital filtering of every pulse prevents false readings. The measurement band runs from 40 to 350 MHz with 80 pF epoxy-mica capacitors, and from 2 to 350 MHz with 1 to 2 nF capacitors. Pulse amplitudes range from 2 to 34000 mV, in 10 sensitivity steps, with 100 phase windows per cycle and an acquisition time of 1 s or 5 s per amplitude window. The instrument builds phase-resolved discharge patterns and pulse amplitude distributions.

The operator connects a low-voltage coaxial cable from the PDA-IV to the sensor termination box, and connects the instrument to a control computer by USB or Ethernet. Measurement is started in the PDLitePro program, which collects data automatically while the generator is running, and the PDView program issues automatic warnings and diagnostics. Up to 12 sensors can be connected: 80 pF epoxy-mica capacitors rated from 6.9 to 35 kV, stator slot couplers, bus couplers and capacitive dividers.

Optionally the instrument can run off-line tests on individual bars, coils and stator windings using portable sensors rated 16 kV and 25 kV, and it can run from a 12 V battery pack. The method follows IEEE Std. 1434-2014 and IEC60034-27-2:2012. Operating temperature is -15 to 45 °C, with relative humidity up to 95 % non-condensing. Mechanical tests follow IEC 60068-2-6, IEC 60068-2-27 and MIL-STD 810G Method 514, and the unit conforms to CE and UL. It is supplied in a transport case measuring 41 × 31 × 21 cm and weighing 10 kg.

Technical specifications

Purposeperiodic online partial discharge monitoring of hydro generators
Sensor inputs12
Frequency range40 to 350 MHz (80 pF), 2 to 350 MHz (1 to 2 nF)
Pulse amplitude2 to 34000 mV
Sensitivity steps10
Phase windows100 per cycle
Acquisition time1 s or 5 s per amplitude window
Compatible sensors80 pF epoxy-mica capacitors (6.9 to 35 kV), stator slot couplers, bus couplers, capacitive dividers
Measurement durationunder 30 min per machine
PC interfaceUSB, Ethernet
Powermains, optional 12 V battery
Off-line testing (option)portable sensors rated 16 kV and 25 kV
Operating temperature-15 to 45 °C
Humidityup to 95 % non-condensing
Case41 × 31 × 21 cm, 10 kg
StandardsIEEE Std. 1434-2014, IEC60034-27-2:2012, IEC 60068-2-6, IEC 60068-2-27, MIL-STD 810G Method 514, CE, UL

Part numbers

Show all part numbers (1)

PDA-IV

Request a price and lead time

PDA-IV Portable Partial Discharge Monitor for Hydro Generators. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the generator have to be shut down for measurement?

No. Data is collected on a machine in operation without affecting its running, and a measurement takes less than 30 minutes.

Which sensors are needed on the machine?

Epoxy-mica capacitors of 80 pF rated from 6.9 to 35 kV, stator slot couplers, bus couplers or capacitive dividers, up to 12 inputs.

How does the instrument separate partial discharges from interference?

By the shape of each pulse and its arrival time, with digital filtering of every pulse, which removes network corona and sparking on busbars.

Similar equipment from other manufacturers