507 ITM intelligent transformer monitor with fibre optic inputs, 38–138 kV
The 507 ITM monitors oil-filled transformers rated 38–138 kV that are installed in chambers and underground rooms. It reads winding hot-spot temperature straight from fibre optic probes, works out the same value using IEEE and IEC models, and switches the cooling fans and pumps.
- Transformer voltage class
- 38–138 kV
- Input modules
- up to 4, types configurable
- Fibre optic inputs
- up to 16 (MOD 638, up to 8 channels, up to 2 modules)
- Fibre optic probe accuracy
- ±1 °C
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 507 ITM comes in a NEMA 4X enclosure, either fibreglass or stainless steel, and can be mounted in an enclosure or on a panel. The heater is optional, with a choice of none, 120 V AC or 240 V AC. Power draw is below 15 W from DC and below 30 W from AC, and the insulation withstands 2500 V AC for 60 seconds to earth.
The main difference from the 506 VTM is the set of fibre optic inputs, which read hot-spot winding temperature directly. The MOD 638 module carries up to 8 channels, and up to 2 modules can be fitted, giving 16 fibre optic channels in total. Probe accuracy is ±1 °C. In parallel, the monitor calculates winding temperature with IEEE and IEC models from the transformer maker's data and compares measured and calculated values in real time, raising an alarm if they diverge.
TransLife shows the rate at which asset life is being used, the life consumed and the life remaining. Critical Forecast estimates the time until a critical temperature is reached under current conditions, and Temperature Profiler keeps a record of temperature history. Automatic switching of cooling groups evens out running hours across fans and pumps, and a pre-cooling function is included.
The unit accepts up to 4 input modules of configurable types, including RTDs, current transformers, pressure, oil level, voltage, flow, and dry and powered contacts. Outputs are 4 programmable relays, one system status relay, one heater control relay, and Form C contacts rated 10 A at 120/240 V AC and 10 A at 30 V DC. Communication runs over RS485 or RS232 using DNP 3.0 level 3 slave, Modbus RTU or ASCII, and wireless links with secure Wi-Fi are available. Third-party vault sensors such as water level, fire detectors and entry sensors can be connected, along with the maker's 900/910 pressure relays and 930 pressure monitors.
Technical specifications
| Transformer voltage class | 38–138 kV |
|---|---|
| Input modules | up to 4, types configurable |
| Fibre optic inputs | up to 16 (MOD 638, up to 8 channels, up to 2 modules) |
| Fibre optic probe accuracy | ±1 °C |
| Output relays | 4 programmable, 1 system status, 1 heater control |
| Output type | Form C, 10 A at 120/240 V AC, 10 A at 30 V DC |
| Protocols | DNP 3.0 level 3 slave, Modbus RTU, ASCII |
| Interfaces | RS485, RS232, secure Wi-Fi |
| Display | 2 x 16 character backlit LCD |
| Power consumption DC | <15 W |
| Power consumption AC | <30 W |
| Dielectric strength | 2500 V AC, 60 seconds to earth |
| Enclosure | fibreglass or stainless steel NEMA 4X |
| Heater | none, 120 V AC or 240 V AC |
| Mounting | enclosure or panel mount |
Part numbers
Show all part numbers (10)
ITM507-00364074, ITM507-00243424, ITM507-00259508, ITM507-00239942, ITM507-00252019, ITM507-00274986, ITM507-00424187, ITM507-00392450, ITM507-00422852, ITM507-00355545
Request a price and lead time
507 ITM intelligent transformer monitor with fibre optic inputs, 38–138 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many fibre optic probes can be connected to the 507 ITM?
Up to 16. The MOD 638 module has up to 8 channels, and up to 2 such modules can be fitted.
Which protocols does the monitor use to send data to SCADA?
DNP 3.0 level 3 slave, Modbus RTU and ASCII over RS485 or RS232, with wireless communication possible through secure Wi-Fi.
Does the monitor control the cooling system?
Yes, it switches fan and pump groups automatically, evens out their running hours and has a pre-cooling function.
Similar equipment from other manufacturers