International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

507 ITM intelligent transformer monitor with fibre optic inputs, 38–138 kV

The 507 ITM monitors oil-filled transformers rated 38–138 kV that are installed in chambers and underground rooms. It reads winding hot-spot temperature straight from fibre optic probes, works out the same value using IEEE and IEC models, and switches the cooling fans and pumps.

Transformer voltage class
38–138 kV
Input modules
up to 4, types configurable
Fibre optic inputs
up to 16 (MOD 638, up to 8 channels, up to 2 modules)
Fibre optic probe accuracy
±1 °C

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The 507 ITM comes in a NEMA 4X enclosure, either fibreglass or stainless steel, and can be mounted in an enclosure or on a panel. The heater is optional, with a choice of none, 120 V AC or 240 V AC. Power draw is below 15 W from DC and below 30 W from AC, and the insulation withstands 2500 V AC for 60 seconds to earth.

The main difference from the 506 VTM is the set of fibre optic inputs, which read hot-spot winding temperature directly. The MOD 638 module carries up to 8 channels, and up to 2 modules can be fitted, giving 16 fibre optic channels in total. Probe accuracy is ±1 °C. In parallel, the monitor calculates winding temperature with IEEE and IEC models from the transformer maker's data and compares measured and calculated values in real time, raising an alarm if they diverge.

TransLife shows the rate at which asset life is being used, the life consumed and the life remaining. Critical Forecast estimates the time until a critical temperature is reached under current conditions, and Temperature Profiler keeps a record of temperature history. Automatic switching of cooling groups evens out running hours across fans and pumps, and a pre-cooling function is included.

The unit accepts up to 4 input modules of configurable types, including RTDs, current transformers, pressure, oil level, voltage, flow, and dry and powered contacts. Outputs are 4 programmable relays, one system status relay, one heater control relay, and Form C contacts rated 10 A at 120/240 V AC and 10 A at 30 V DC. Communication runs over RS485 or RS232 using DNP 3.0 level 3 slave, Modbus RTU or ASCII, and wireless links with secure Wi-Fi are available. Third-party vault sensors such as water level, fire detectors and entry sensors can be connected, along with the maker's 900/910 pressure relays and 930 pressure monitors.

Technical specifications

Transformer voltage class38–138 kV
Input modulesup to 4, types configurable
Fibre optic inputsup to 16 (MOD 638, up to 8 channels, up to 2 modules)
Fibre optic probe accuracy±1 °C
Output relays4 programmable, 1 system status, 1 heater control
Output typeForm C, 10 A at 120/240 V AC, 10 A at 30 V DC
ProtocolsDNP 3.0 level 3 slave, Modbus RTU, ASCII
InterfacesRS485, RS232, secure Wi-Fi
Display2 x 16 character backlit LCD
Power consumption DC<15 W
Power consumption AC<30 W
Dielectric strength2500 V AC, 60 seconds to earth
Enclosurefibreglass or stainless steel NEMA 4X
Heaternone, 120 V AC or 240 V AC
Mountingenclosure or panel mount

Part numbers

Show all part numbers (10)

ITM507-00364074, ITM507-00243424, ITM507-00259508, ITM507-00239942, ITM507-00252019, ITM507-00274986, ITM507-00424187, ITM507-00392450, ITM507-00422852, ITM507-00355545

Request a price and lead time

507 ITM intelligent transformer monitor with fibre optic inputs, 38–138 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How many fibre optic probes can be connected to the 507 ITM?

Up to 16. The MOD 638 module has up to 8 channels, and up to 2 such modules can be fitted.

Which protocols does the monitor use to send data to SCADA?

DNP 3.0 level 3 slave, Modbus RTU and ASCII over RS485 or RS232, with wireless communication possible through secure Wi-Fi.

Does the monitor control the cooling system?

Yes, it switches fan and pump groups automatically, evens out their running hours and has a pre-cooling function.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides