INFORMA PMD-A Power Quality Analyser with Fault Recording
The INFORMA PMD-A combines power quality monitoring to IEC 61000-4-30 Class A with digital fault recording in one unit. It offers 9 to 36 configurable AC or DC analogue channels, a 25.6 kHz sampling rate at 50 Hz and a 19-inch rack-mounted enclosure.
- Compliance
- IEC 61000-4-30 Class A, IEC 61000-4-7, IEC 61000-4-15, IEEE 1159, IEEE 519
- Analogue channels
- 9 (3U); 9/18/27/36 (6U)
- Sampling rate
- 25.6 kHz at 50 Hz; 30.72 kHz at 60 Hz
- Bandwidth
- 25 to 4600 Hz ± 0.5 dB
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The unit suits distribution substations where voltage quality has to be watched and fault events recorded at the same time. Its Class A performance to IEC 61000-4-30 has been approved by an independent third party. EN 50160 reports and IEC 61000-3-6 and 61000-3-7 reports are built in, and customised reports can be added. The manufacturer cites a 90% reduction in analysis time, since the whole power system overview sits on a single screen alongside a device and communication health check.
Channel count depends on the chassis. The 3U version carries 9 configurable analogue channels, while the 6U version offers 9, 18, 27 or 36. Sampling runs at 25.6 kHz at 50 Hz and 30.72 kHz at 60 Hz, with a bandwidth of 25 to 4600 Hz at ±0.5 dB. Voltage inputs are rated 63.5, 120, 240 and 440 VAC, with 300 V CAT III and 150 V CAT IV categories and a continuous overload of 1000 VAC. Current inputs are available in 1, 2, 5 and 10 A ranges, with 20-bit resolution.
A transient recording module captures surges up to 6 kV over a bandwidth of 2.5 kHz to 5 MHz, sampling at up to 20 MHz. The unit has 32 digital inputs, isolated in groups of eight and accepting 24/48 to 250 VDC, plus four form A/B relay outputs for alarms. Time synchronisation comes from GPS to within ±300 ns, from IRIG-B to within ±2 ms, or from a 1 PPS signal. Where protection and metering current transformers are both available, two sets can be connected so that load current and fault current are both measured accurately.
Communication runs over two 100 Mb Ethernet ports with RJ45 connectors, three RS232 ports and one RS485 port, with optional fibre optic Ethernet and an internal PSTN modem. Protocols include TCP/IP, Modbus, IEC 60870-5, IEC 61850, GSM and GPRS. Records are stored on 4 GB Compact Flash as standard, with 8 GB or 16 GB available as options. Power input is 90 to 264 VAC or 88 to 300 VDC, and the unit also comes in 36 to 72 VDC and 18 to 36 VDC versions. It operates from -5°C to 50°C within an IP 41 enclosure, and a calibration check is due once every 5 years.
Technical specifications
| Compliance | IEC 61000-4-30 Class A, IEC 61000-4-7, IEC 61000-4-15, IEEE 1159, IEEE 519 |
|---|---|
| Analogue channels | 9 (3U); 9/18/27/36 (6U) |
| Sampling rate | 25.6 kHz at 50 Hz; 30.72 kHz at 60 Hz |
| Bandwidth | 25 to 4600 Hz ± 0.5 dB |
| Voltage ranges AC | 63.5, 120, 240, 440 VAC |
| Measurement category | 300 V CAT III, 150 V CAT IV |
| Current ranges | 1, 2, 5, 10 A |
| Current overload | 200 A for 1 s; 40 A continuous |
| Transient recording | Up to 6 kV, 2.5 kHz to 5 MHz, up to 20 MHz |
| Digital inputs | 32, in groups of 8, 24/48 ... 250 VDC |
| Relay outputs | 4 form A/B |
| Time synchronisation | GPS ± 300 ns; IRIG-B ± 2 ms; 1 PPS |
| Interfaces | 2 × Ethernet 100 Mb RJ45; 3 × RS232; RS485 |
| Protocols | TCP/IP, Modbus, IEC 60870-5, IEC 61850, GSM, GPRS |
| Record storage | Compact Flash 4 GB (8 GB/16 GB optional) |
| Power supply | 90 - 264 VAC (88-300 VDC); 36 - 72 VDC; 18 - 36 VDC |
| Typical load | 25 VA (3U); 50 VA (6U) |
| Operating temperature | -5°C ... 50°C |
| Enclosure rating | IP 41 |
| Dimensions, 3U | 132.5 × 487 × 362.2 mm |
Request a price and lead time
INFORMA PMD-A Power Quality Analyser with Fault Recording. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the INFORMA PMD-A produce EN 50160 reports?
Yes. EN 50160 reports are built in, alongside IEC 61000-3-6 and 61000-3-7 reports and user-defined reports.
How many analogue channels can I get?
The 3U unit has 9 channels, while the 6U unit offers 9, 18, 27 or 36 channels, AC or DC.
Which protocols does the unit support for system integration?
TCP/IP, Modbus, IEC 60870-5 and IEC 61850, plus GSM and GPRS.