IDM+PMU 9/18/36 Phasor Measurement Unit for Substations
The IDM+PMU 9/18/36 calculates and streams synchronised phasors of currents and voltages for up to ten three-phase circuits. The units are modular, hardened for substation conditions, and configured through a standard web browser without separate software.
- Type
- Phasor measurement unit (PMU)
- Analogue channels
- 9, 18 or 36
- Digital channels
- 32 or 64, input 48–250 VDC (24–250 VDC optional)
- Circuits monitored
- Up to ten three-phase
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
IDM+PMU units are used in distributed phasor measurement systems at generation, transmission and distribution sites. Synchronised phasors and the state of digital inputs feed wide-area measurement, protection and automation systems, and the digital states can also go to state estimators to establish the network configuration. The manufacturer recommends a PMU where a multifunction device cannot be justified on cost.
The family has three versions. The IDM+PMU 9 has 9 analogue and 32 digital channels and monitors one complete circuit, with three phase voltages and three phase currents, or two circuits sharing a voltage source. The IDM+PMU 18 has 18 analogue and 32 digital channels and monitors three or five circuits. The IDM+PMU 36 has 36 analogue and 64 digital channels and monitors six or ten circuits.
Sampling runs at 512 samples per cycle, with 20-bit resolution for current inputs and 16-bit for voltage inputs. 1% TVE is maintained across 10% to 120% of nominal, a wider band than C37.118 requires. Nominal current is 1 A or 5 A, with full-scale values of 10 or 20 times nominal. Nominal voltage is 63.5 V (140 V full scale), 120 V (270 V), 240 V (480 V) or 440 V (800 V). Digital inputs accept 48 to 250 VDC, with 24 to 250 VDC optional. Clock accuracy is 1 µs when locked. Phasors are transmitted under C37.118 at frame rates up to 50 or 60 Hz, as single-phase phasors or sequence components, and active, reactive and apparent power can be added to the stream.
The series fully complies with IEEE C37.118.1-2014 and industry information security requirements. The IDM+PMU 9 and 18 have two RJ45 Ethernet ports, one at the front for local connection and one at the rear, optionally fibre, for streaming phasors. The IDM+PMU 36 has four ports. The front panel carries nine LED indicators for power, healthy status, communication, clock sync, alarm and three general states. Power input is 88 to 250 VAC or 88 to 300 VDC, optionally 35 to 65 VDC, drawing 40 VA for the IDM+PMU 9 and 80 VA for the IDM+PMU 18 and 36. The units mount in a 19-inch rack, at 3U (132.5 mm) for the IDM+PMU 9 and 6U (265.8 mm) for the others, with a width of 487 mm and a depth of 362.2 mm. Operating temperature is -5 to +50°C, and storage is -30 to +70°C.
Technical specifications
| Type | Phasor measurement unit (PMU) |
|---|---|
| Analogue channels | 9, 18 or 36 |
| Digital channels | 32 or 64, input 48–250 VDC (24–250 VDC optional) |
| Circuits monitored | Up to ten three-phase |
| Sampling rate | 512 samples per cycle |
| Resolution | 20 bits for current, 16 bits for voltage |
| Accuracy | 1% TVE from 10% to 120% of nominal |
| Nominal current | 1 A or 5 A |
| Nominal voltage | 63.5 V, 120 V, 240 V or 440 V |
| Clock accuracy | 1 µs when locked |
| C37.118 frame rate | Up to 50 or 60 Hz |
| Ethernet ports | 2 (IDM+PMU 9/18) or 4 (IDM+PMU 36), RJ45, optional fibre |
| Power supply | 88–250 VAC, 88–300 VDC, optional 35–65 VDC |
| Power consumption | 40 VA (IDM+PMU 9), 80 VA (IDM+PMU 18 and 36) |
| Operating temperature | −5 to +50°C |
| Storage temperature | −30 to +70°C |
| Dimensions | 19-inch rack, 3U or 6U; width 487 mm, depth 362.2 mm |
| Standard | IEEE C37.118.1-2014 |
Part numbers
Show all part numbers (3)
IDM+PMU 9, IDM+PMU 18, IDM+PMU 36
Request a price and lead time
IDM+PMU 9/18/36 Phasor Measurement Unit for Substations. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many circuits does each version monitor?
The IDM+PMU 9 monitors one or two circuits, the IDM+PMU 18 three or five, and the IDM+PMU 36 six or ten.
What accuracy does the unit deliver?
An error of less than 1% TVE from 10% to 120% of nominal, with a sampling rate of 512 samples per cycle and a clock accuracy of 1 µs.
How is the unit configured?
Through a standard web browser, with no separate software required.