IDM+ multi-function power system monitor: fault recorder, PMU, PQ class A
The IDM+ is a digital fault and disturbance recorder for substations and power stations that combines DFR, DDR, SER, PMU, travelling wave fault location and power quality monitoring to IEC 61000-4-30 class A in one unit. It samples 512 readings per cycle, with 20-bit resolution on current channels.
- Functions
- DFR, DDR, SER, PMU, TWS, PQ class A
- Analogue channels
- 9, 18 or 36
- Digital channels
- 32, 64 or 128
- Resolution
- 20 bit (current), 16 bit (voltage, DC)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The IDM+ is supplied in three configurations that differ in channel count. The IDM+ 9 provides 9 analogue and 32 digital channels in a 3U case, the IDM+ 18 provides 18 analogue and 64 digital channels in a 6U case, and the IDM+ 36 provides 36 analogue and 128 digital channels in a 6U case, arranged in two blocks of 18 and 64. All cases mount in a 19-inch rack, measure 487 mm wide and 362.2 mm deep, and weigh 15 kg for the 3U model and 23 kg for the 6U model.
Digital fault recording (DFR) is the base function. Options add dynamic disturbance recording with slow scan (DDR), sequence of events recording (SER), synchrophasor measurement (PMU) to IEEE C37.118, certified class A power quality monitoring (PQ) to IEC 61000-4-30 Ed 2.0, IEC 61000-4-7 and IEC 61000-4-15, and travelling wave (TWS) line fault location accurate to ±60 m. One unit therefore replaces several separate recorders and simplifies integration into an automated substation through IEC 61850 (MMS).
The measuring chain samples at 512 readings per cycle, with 20-bit resolution on current channels and 16-bit resolution on voltage and DC channels, and an error of 0.1 % of full scale. The sample rate is selectable between 30.7, 15.3, 7.6, 3.8 or 1.9 kHz for a 60 Hz network, or 25.6, 12.8, 6.4, 3.2 or 1.6 kHz for a 50 Hz network. When locked to the built-in GPS module, the clock accuracy is 100 ns.
Designed for substations and power stations, the recorder captures what happened after a disturbance so engineers can see the cause and the measures needed to stop it recurring. Its construction is fully solid state. Data is stored on a CompactFlash card of at least 4 GB, with 8 GB or 16 GB as an option. It runs from 88–300 V AC or DC, with a 35–65 V DC option, and draws 40 VA. The operating range is −5 to +50 °C and storage is −30 to +70 °C. The iQ+ client-server software running at the master station collects and analyses the records.
Technical specifications
| Functions | DFR, DDR, SER, PMU, TWS, PQ class A |
|---|---|
| Analogue channels | 9, 18 or 36 |
| Digital channels | 32, 64 or 128 |
| Resolution | 20 bit (current), 16 bit (voltage, DC) |
| Accuracy | 0.1 % of full scale |
| Sampling | 512 readings per cycle |
| Sampling rate, 50 Hz | 25.6, 12.8, 6.4, 3.2, 1.6 kHz |
| Sampling rate, 60 Hz | 30.7, 15.3, 7.6, 3.8, 1.9 kHz |
| TWS fault location accuracy | ±60 m |
| Clock accuracy | 100 ns with built-in GPS |
| Data storage | CompactFlash 4 GB, option 8 or 16 GB |
| Protocol | IEC 61850 (MMS) |
| Power supply | 88–300 V AC or DC, option 35–65 V DC |
| Power consumption | 40 VA |
| Operating temperature | −5…+50 °C |
| Storage temperature | −30…+70 °C |
| Enclosure | 19 inch, 3U or 6U, 487 x 362.2 mm |
| Weight | 15 kg (3U), 23 kg (6U) |
| Standards | IEEE C37.118, IEC 61000-4-30 class A, IEC 61000-4-7, IEC 61000-4-15 |
Part numbers
Show all part numbers (3)
IDM+ 9, IDM+ 18, IDM+ 36
Request a price and lead time
IDM+ multi-function power system monitor: fault recorder, PMU, PQ class A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the difference between the IDM+ 9, IDM+ 18 and IDM+ 36?
The channel count and case size. The IDM+ 9 has 9 analogue and 32 digital channels in a 3U case, the IDM+ 18 has 18 and 64 in a 6U case, and the IDM+ 36 has 36 and 128 in a 6U case.
How accurately does the unit locate a fault on a line?
With the travelling wave (TWS) option, the fault is located to within ±60 m.
Is the IDM+ suitable for 50 Hz networks?
Yes, for 50 Hz the available sample rates are 25.6, 12.8, 6.4, 3.2 and 1.6 kHz.