Hydran M2-X online monitor of gas and moisture in transformer oil

The Hydran M2-X online monitor tracks gases and moisture in transformer oil to detect developing faults early. Its measuring range is 25–2000 ppm H₂ equivalent, and moisture is measured over 0–100% RH.

Sensor
fuel cell behind a gas-permeable membrane (combined gas H₂, CO, C₂H₂, C₂H₄, or hydrogen only)
Range
25–2000 ppm (H₂ equivalent)
Accuracy
±10% of reading ±25 ppm
Moisture
0–100% RH, ±2% RH

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The sensor is built on a fuel cell behind a gas-permeable membrane. It measures the combined gas (H₂, CO, C₂H₂, C₂H₄) or hydrogen alone. Accuracy is ±10% of reading ±25 ppm, and for moisture ±2% RH. Communication is over Modbus and DNP 3.0, with optional IEC 61850. Operating temperature −40…+55 °C, packaged weight 9 kg. The previous generation, Hydran M2, works as a single-component DGA monitor.

Technical specifications

Sensorfuel cell behind a gas-permeable membrane (combined gas H₂, CO, C₂H₂, C₂H₄, or hydrogen only)
Range25–2000 ppm (H₂ equivalent)
Accuracy±10% of reading ±25 ppm
Moisture0–100% RH, ±2% RH
CommunicationModbus, DNP 3.0; optional IEC 61850
Operating temperature−40…+55 °C
Weight9 kg (packaged)

Request a price and lead time

Hydran M2-X online monitor of gas and moisture in transformer oil. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)9027 10 10 00
HS, 6 digits9027 10
CN (EU)9027 10 10
HTSUS (USA)9027 10 20 00
China customs tariff9027 10 00 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What is the measuring range and accuracy of the gas measurement?

The range is 25–2000 ppm H₂ equivalent, with accuracy of ±10% of reading ±25 ppm.

Which protocols does the monitor use to transmit data?

Modbus and DNP 3.0, with IEC 61850 as an option.

What temperature range does the device work in?

The operating temperature is −40…+55 °C, and the packaged weight is 9 kg.