FALCON single-channel partial discharge monitor for medium voltage equipment
FALCON is a single-channel continuous partial discharge monitor for medium voltage switchgear, cables, transformers and motors. It works with inductive HFCT sensors or capacitive TEV antennas, processes data automatically and builds T-F maps.
- Number of channels
- 1
- Wideband path
- 16 kHz to 30 MHz
- Resolution
- 12 bit
- Sampling rate
- 125 MS/s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
FALCON is used for continuous monitoring of the insulation of medium voltage equipment, including switchgear for low and medium voltage, cables, transformers, motors and other rotating machines. A rise in partial discharge activity shows the insulation deteriorating before breakdown. The unit is single-channel, and its main task is to detect the presence of an insulation defect; the exact location is found by further analysis.
The unit accepts high-frequency partial discharge signals from the connected sensor: an inductive HFCT clamped around the three cable screens or around a common screen, or a capacitive TEV antenna fixed with magnets to metal parts of the cabinet. The wideband path of 16 kHz to 30 MHz, with a 125 MS/s sampling rate and 12-bit resolution, records the amplitude, phase and shape of each pulse. For every pulse the unit calculates its time and frequency content and builds a T-F map, which separates the different discharge sources. The full scale is 5 V peak, the input impedance 50 Ω, and the connector is BNC.
The synchronisation channel operates in the 5–500 Hz range with 10 Ω input impedance and 1 MS/s sampling at 12 bit, with BNC connectors. The unit sets full scale and trigger level automatically, rejects noise, recognises a growing trend of discharges and raises alarms. Maintenance is needed only when an alarm is raised.
A FALCON set consists of a sensor, a synchronisation kit and a web application. Built-in computing resources and memory keep measurements for up to two years, and data and trends can be viewed from any point on the network through a web browser with little traffic. Communication runs over two 10/100/1000 Mb/s LAN ports using OPC UA (IEC 62541), IEC 61850, Modbus and DNP3, so the unit can be integrated into an existing monitoring system.
Installation is quick: the unit is fixed with two magnets to metal parts of the cabinet or to a DIN rail, and it configures itself automatically once power is applied. It runs on 12 / 24 V DC at 1 A, with an operating temperature of -20 °C to +55 °C.
Technical specifications
| Number of channels | 1 |
|---|---|
| Wideband path | 16 kHz to 30 MHz |
| Resolution | 12 bit |
| Sampling rate | 125 MS/s |
| Full scale | 5 V peak |
| Input impedance | 50 Ω |
| Connector | BNC |
| Sync frequency range | 5–500 Hz |
| Sync input impedance | 10 Ω |
| Sync sampling | 1 MS/s, 12 bit |
| Communication | 2 LAN ports, 10/100/1000 Mb/s |
| Protocols | OPC UA (IEC 62541), IEC 61850, Modbus, DNP3 |
| Power supply | 12 / 24 V DC, 1 A |
| Operating temperature | -20 °C to +55 °C |
| Sensors | HFCT, TEV antenna |
Request a price and lead time
FALCON single-channel partial discharge monitor for medium voltage equipment. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which sensors are connected to FALCON?
An inductive HFCT sensor clamped around the cable screens, or a capacitive TEV antenna fixed with magnets to metal parts of the cabinet.
Does FALCON locate the exact position of a defect?
The unit is single-channel and shows whether an insulation defect is present, while the exact location is found by further analysis.
How does FALCON connect to SCADA?
Through two 10/100/1000 Mb/s LAN ports using OPC UA (IEC 62541), IEC 61850, Modbus and DNP3.
Similar equipment from other manufacturers