DRA-3 Insulation Diagnostics Analyser with Up to 10 kV Test Source

The DRA-3 is used for offline diagnosis of winding insulation in generators and motors, and suits transformers too. It measures charging and discharging currents of stator or rotor insulation, from which cleanliness, ageing, resin decomposition and degree of polymerisation are assessed.

Type
polarisation and depolarisation current analyser (PDC)
Application
generators, motors, transformers
Mode
offline insulation diagnostics
Power supply
90 to 240 V AC

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The instrument works with the stator and rotor windings of medium and high voltage electrical machines, and with the insulation of power transformers. Diagnosis is carried out on de-energised equipment, so measurements are usually combined with planned repairs, machine inspections or acceptance tests. The PDC method assesses insulation condition from the change of current over time during charging and the subsequent discharge, rather than from a single resistance value.

A built-in floating DC source delivers up to 10 kV at fixed levels of 0.5, 1, 2.5, 5 and 10 kV. Current is measured through a 100 kΩ shunt over a range from 1 mA down to 0.1 nA, with a resolution of 1 pA. The instrument runs from an AC supply of 90 to 240 V.

All three phases and earth are connected at once. The phases are then measured one after another without operator intervention, with a connected computer directing the steps and storing the results. Several configurations are available: all three phases together against earth, each phase separately, and between phases.

After the data is saved, the evaluation program automatically calculates the polarisation index, insulation resistance, absorption coefficient and other parameters, and produces a full report. It can compare up to four different measurements, which helps track the insulation of one machine between overhauls. The instrument performs insulation resistance profiling (IRP) and automatic temperature correction according to IEEE 43.

The kit includes the DRA3 instrument, a transport case, a mains cable, four high-voltage leads, three red and one black crocodile clips, a 5 m USB cable, an operating manual and a software disc. The instrument measures 50 × 38 × 20.3 cm and weighs 11.34 kg, and the transport case measures 71 × 69 × 41 cm and weighs 31.3 kg. Order code HVDRA corresponds to the analyser with charging and discharging current measurement at voltages up to 10 kV.

Technical specifications

Typepolarisation and depolarisation current analyser (PDC)
Applicationgenerators, motors, transformers
Modeoffline insulation diagnostics
Power supply90 to 240 V AC
High voltage outputup to 10 kV, fixed 0.5, 1, 2.5, 5 and 10 kV
Measuring shunt100 kΩ
Current range1 mA to 0.1 nA
Resolution1 pA
Measurement configurationsthree phases to earth, each phase separately, between phases
Calculated parameterspolarisation index, insulation resistance, absorption coefficient
Measurement comparisonup to 4
StandardIEEE 43 (IRP, temperature correction)
Instrument dimensions50 × 38 × 20.3 cm
Instrument weight11.34 kg
Case dimensions71 × 69 × 41 cm
Case weight31.3 kg

Part numbers

Show all part numbers (2)

DRA3, HVDRA

Request a price and lead time

DRA-3 Insulation Diagnostics Analyser with Up to 10 kV Test Source. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Do the leads have to be reconnected for each phase?

No. The three phases and earth are connected once, and the instrument then measures the phases in sequence under computer control.

Which test voltage levels can be set?

The source delivers up to 10 kV DC at fixed levels of 0.5, 1, 2.5, 5 and 10 kV.

Does the software correct insulation resistance for temperature?

Yes. The software performs insulation resistance profiling (IRP) and automatic temperature correction according to IEEE 43.