DoblePRIME IDD bushing monitor for up to 12 bushings, tap current 1–200 mA
The doblePRIME IDD is an intelligent diagnostic device for online monitoring of high-voltage bushings and current transformers. It analyses leakage current and phase for up to 12 bushings, detects insulation defects and issues warnings based on both offline and online data.
- Number of channels
- 3, 6 or 12
- Monitored bushings
- up to four sets of three bushings
- Measurement method
- raw leakage current waveform and relative phase
- Tap current range
- 1–200 mA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The IDD is used for continuous monitoring of bushings on power transformers and of current transformers under operating voltage. It detects signs of deterioration in a bushing and issues warnings. Measurements are made for each bushing individually and for the group together. One unit covers up to 12 bushings, meaning up to four sets of three.
The measurement method records the raw waveform of leakage current from the bushing tap, together with the relative phase. From these data the unit calculates power factor and capacitance, and it logs results at a set interval or on demand. It keeps both raw oscillograms and derived values for deeper analysis. The embedded expert system learns the normal behaviour of each bushing and compares calculated online data with offline test results, so it tells rapid deterioration apart from slow deterioration of the insulation.
There are three variants. The DPID 100 has 12 channels, the DPID 102 has 6 channels, and the DPID 101 has 6 channels with three reference-voltage inputs from instrument transformers. The reference voltage can come through a digital or an analogue input, and the transformation ratio can be measured. Signals connect to screw terminals.
Tap current covers 1 to 200 mA, with amplitude accuracy of ±1% of reading and phase accuracy of 0.01 degrees. Resolution is 0.1% of the input signal peak. Isolation between bushings and between a bushing and the host exceeds 2500 V. The host processor is an ARM Cortex at 180 MHz, with 32 MB of RAM and 16 MB of flash.
On installation the measuring tap cap is replaced by a bushing adapter, and the tap earth stays connected through the device. Surge protection uses suppressors and spark gaps with several earthing paths, and an armoured cable with a terminal box is offered for harsh conditions. The housing is anodised aluminium measuring 200 x 330 x 82 mm and weighs 2 kg. It runs from 24 V DC @ 1 A and works between -20 and +50 °C. It can operate stand-alone, networked to a SCADA system, or as part of a doblePRIME platform.
Technical specifications
| Number of channels | 3, 6 or 12 |
|---|---|
| Monitored bushings | up to four sets of three bushings |
| Measurement method | raw leakage current waveform and relative phase |
| Tap current range | 1–200 mA |
| Amplitude accuracy | ±1% of reading |
| Phase accuracy | 0.01° |
| Resolution | 0.1% of input signal peak |
| Bushing-to-bushing isolation | >2500 V |
| Bushing-to-host isolation | >2500 V |
| Reference voltage | digital or analogue input (optional) |
| Connections | screw terminals |
| Processor | ARM Cortex 180 MHz |
| Memory | 32 MB RAM, 16 MB flash |
| Power supply | 24 V DC @ 1 A |
| Operating temperature | -20 °C to +50 °C |
| Storage temperature | -20 °C to +70 °C |
| Humidity | 0–95% without condensation |
| Dimensions (H x W x D) | 200 x 330 x 82 mm |
| Weight | 2 kg |
Part numbers
Show all part numbers (3)
DPID 100, DPID 101, DPID 102
Request a price and lead time
DoblePRIME IDD bushing monitor for up to 12 bushings, tap current 1–200 mA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many bushings can one unit monitor?
Up to 12 bushings, meaning up to four sets of three. Variants are available with 12 channels (DPID 100) and with 6 channels (DPID 101 and DPID 102).
Which parameters does the monitor calculate for each bushing?
From the leakage current waveform and phase, the unit calculates the power factor and capacitance of each bushing.
Is an external reference voltage needed?
It is optional. The DPID 101 has three reference-voltage inputs from instrument transformers, and the signal can be fed through a digital or analogue input.
Similar equipment from other manufacturers