DeltaMaxx Analyser for tg δ, Capacitance and Partial Discharge, up to 50 kV

DeltaMaxx measures the dielectric loss factor, capacitance and partial discharge in the windings of generators and motors, at test voltages up to 50 kV. A digital algorithm replaces the classic AC bridge, and signal processing takes place right at the test object.

Models
DeltaMaxx 15, DeltaMaxx 20, DeltaMaxx 30, DeltaMaxx 50
Test voltage
15 kV, 20 kV, 30 kV, 50 kV
Test frequency
10–100 Hz
Maximum current
10 A standard, also 50 mA and 2 A (depends on shunts)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The instrument is used for offline insulation diagnostics on generator and motor windings, dry-type transformers, capacitors, paper-impregnated cables, individual coils and bars, phase-segregated busbars and medium voltage circuit breakers. Three configurations are available: a tg δ and capacitance meter with a built-in reference capacitor, a partial discharge detector with a built-in coupling capacitor, or both functions in one unit. The DeltaMaxx 15, 20, 30 and 50 models differ in test voltage.

For loss factor measurement, the unit records the high voltage applied to the object together with the current flowing through the reference capacitor and the object, read as the voltage drop across shunt resistors. A 16-bit converter digitises these signals, and the algorithm works out the phase difference, calculates the loss angle and removes several sources of error. The instrument tunes itself to a supply frequency between 10 and 100 Hz, and higher harmonics, including the third and fifth, are rejected in software. Differential amplifiers allow work on both earthed and unearthed objects.

Partial discharge pulses are taken off through the built-in coupling capacitor, and the coupling impedance, pre-amplifier, signal processing and digitising all sit inside the measuring unit, so no external shunts or long signal cables are needed. The instrument plots a phase-resolved discharge pattern and calculates apparent charge Qapp to IEC 60270 and the Qm value to IEC 60034-27-1, which covers discharge activity with a repetition rate above 10 per second. The bandwidth is 40 to 800 kHz, and the range runs from 10 pC to 200 nC.

The unit connects to a PC over USB, and a cable longer than about 5 m needs an optical USB extender. The tg δ meter is powered from USB, while the PD module needs an external 5 V DC supply. Calibration is built into the software, and reports are produced as HTML with export to spreadsheets. Its compact build and resistance to interference make it practical to upgrade older high voltage test stands.

Technical specifications

ModelsDeltaMaxx 15, DeltaMaxx 20, DeltaMaxx 30, DeltaMaxx 50
Test voltage15 kV, 20 kV, 30 kV, 50 kV
Test frequency10–100 Hz
Maximum current10 A standard, also 50 mA and 2 A (depends on shunts)
Reference and coupling capacitor1 nF for 15 and 20 kV, 0.7 nF for 30 kV, 0.5 nF for 50 kV
tg δ resolution10^-5
tg δ error(1–2)·10^-4
Capacitance error0.5% at 5 V input and 20 °C
ADC16-bit
PD bandwidth40–800 kHz, to IEC 60270
PD range10 pC – 200 nC (typical)
Maximum PD pulse rate40 thousand events per second
Power supplyFrom USB; PD module from external 5 V DC
PC requirementsDesktop or laptop, 512 MB RAM minimum
StandardsIEC 60034-27-3, IEEE 286, IEC 60034-27-1, IEC 60270, IEEE 1434
OptionsPD module with PDCAL 20 calibrator, laptop, optical USB extender

Part numbers

Show all part numbers (4)

DeltaMaxx 15, DeltaMaxx 20, DeltaMaxx 30, DeltaMaxx 50

Request a price and lead time

DeltaMaxx Analyser for tg δ, Capacitance and Partial Discharge, up to 50 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which standards does the instrument follow?

The tg δ and capacitance measurement follows IEC 60034-27-3 and IEEE 286, while partial discharge measurement follows IEC 60034-27-1, IEC 60270 and IEEE 1434.

Does the instrument need a separate power supply?

The tg δ meter is powered from USB, but the partial discharge module needs an external 5 V DC supply.

How do the 15, 20, 30 and 50 models differ?

They differ in rated test voltage and in the built-in capacitor value: 1 nF for 15 and 20 kV, 0.7 nF for 30 kV and 0.5 nF for 50 kV.