International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

DCC 2 / DCC-ML 2 surge arrester operation counters with leakage current measurement

DCC 2 / DCC-ML 2 operation counters for installation in the earthing circuit of surge arresters from any manufacturer. The DCC-ML 2 version has a leakage current scale of 0–50 mA, and no power supply is needed for the devices.

Counter
6-digit
Minimum operating current
100 A (8/20 µs)
Impulse current withstand
100 kA (4/10 µs)
Leakage current scale (DCC-ML 2)
0–50 mA (r.m.s.)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The counter has 6 digits, with a minimum operating current of 100 A at an 8/20 µs impulse. Impulse current withstand is 100 kA (4/10 µs). The DCC-ML 2 scale shows the r.m.s. value of the leakage current, which allows monitoring the arrester condition during inspection. Test spark gaps for discharge analysis are also offered.

Technical specifications

Counter6-digit
Minimum operating current100 A (8/20 µs)
Impulse current withstand100 kA (4/10 µs)
Leakage current scale (DCC-ML 2)0–50 mA (r.m.s.)
Power supplynot needed
Additionaltest spark gaps for discharge analysis

Request a price and lead time

DCC 2 / DCC-ML 2 surge arrester operation counters with leakage current measurement. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)9030 33 70 00
HS, 6 digits9030 33
CN (EU)9030 33 70
HTSUS (USA)9030 33 38 00
China customs tariff9030 33 90 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

Is the counter suitable for surge arresters from other manufacturers?

Yes, DCC 2 and DCC-ML 2 are installed in the earthing circuit of surge arresters from any manufacturer.

At what current does the counter operate?

The minimum operating current is 100 A (8/20 µs), and the impulse current withstand is 100 kA (4/10 µs).

Does the counter need a power supply?

No, no power supply is needed, and the DCC-ML 2 scale shows a leakage current of 0–50 mA.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides