International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Smart Monitoring built-in insulation condition monitoring for HV bushings and current transformers

Insulation condition monitoring built into high-voltage bushings and current transformers with dry solid insulation. It runs online and flags a developing defect early, either through an LED pre-alarm or via a digital measurement terminal.

Type
Built-in insulation monitoring system
Mode
Online monitoring
Measuring principle
Capacitive divider C1/Cs
Interface
Visual (LED) or digital

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

A small low-voltage capacitor, Cs, sits inside the graded insulation core of the HV bushing alongside the main insulation C1. Together they form a capacitive voltage divider, and that divider is the heart of the system. Compared with current sensors wound on iron cores, it shields better against interference and gives better accuracy.

Because the C1 to Cs connection stays inside the core, it cannot work loose, and the last screen lead remains reliably earthed. Both capacitances share the same material and workmanship, so changes in temperature or frequency do not introduce large errors.

Users pick one of two interfaces. The visual option is an LED terminal on the current transformer: maintenance crews simply check whether the pre-alarm light is on, with no need to sift through large volumes of data. The digital option is a smart measurement terminal that passes readings to a monitoring system.

The dry, solid insulation slows the spread of a defect through the core to a crawl, so after the first warning there are weeks, often months, to investigate and repair. No emergency de-energisation is needed. The external acquisition device cannot harm the HV insulation even after a wiring short or open circuit, and it draws its power from the grid, so no separate supply has to be installed.

Online monitoring of this kind cuts the number and length of outages for off-line preventive testing and supports smart grid operation of substations.

Technical specifications

TypeBuilt-in insulation monitoring system
ModeOnline monitoring
Measuring principleCapacitive divider C1/Cs
InterfaceVisual (LED) or digital
AlarmLED pre-alarm
Power supplyFrom the grid, no external source
InsulationDry solid type
EquipmentHV bushings, current transformers

Request a price and lead time

Smart Monitoring built-in insulation condition monitoring for HV bushings and current transformers. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Does the monitoring device need its own power supply?

No, it is powered from the grid, so no external source or extra installation work is required.

What interface options are offered?

Two: an LED terminal on the current transformer giving a pre-alarm, or a smart digital measurement terminal.

Can a fault in the measuring circuit affect the HV insulation?

No, the external data acquisition device does not affect the HV insulation even in the event of a short circuit or open circuit.