International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

930 Electronic Pressure Monitor and Rapid Pressure Rise Relay for Transformers

The 930 monitor tracks pressure in the main tank of a transformer or in a tap changer compartment, responding to both sudden and gradual rises. It has a latching function, up to nine SPDT output relays and an analogue output for SCADA.

Type
electronic pressure monitor with rapid pressure rise relay
Pressure range
0–30 PSIG (0–2 bar)
Slow-rise set point
1–15 PSIG (0–1 bar)
Fast-rise set point
16-position rotary switch

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The 930 is installed on the compartment of an on-load tap changer or on the main tank of an oil or gas-filled transformer. The unit has two parts: a sensitive electronic pressure sensor fitted to the tank, and a control panel that is normally mounted in the transformer control cabinet. The sensor converts pressure into an electrical signal and passes it along a screened cable up to 750 ft (228.6 m) long. The monitor is powered from the mains.

The panel watches tank pressure and responds quickly to a sudden rise caused by an internal arc. That fast-rise signal can drive an alarm or trip the transformer automatically. A separate slow-rise channel operates at a set point adjustable between 1 and 15 PSIG (0 to 1 bar). The fast-rise characteristic is chosen with a 16-position rotary switch, so sensitivity can be matched to a specific tank. A selectable latching function holds the alarm condition until it is manually reset. Each sensor has two LEDs that show the source of an operation or the power status.

Two main versions are produced: one with a single sensor and board, and one with three sensors and three boards. The single-sensor model has 3 SPDT relays, either two for fast rise and one for slow rise, or one each for fast rise, slow rise and power status. The multi-sensor model has 9 SPDT relays, six for fast rise, two for slow rise and one for power status, plus signal logic that combines readings from several sensors and so reduces false trips. Contacts are rated at 10 A and 1/3 HP at 120 or 240 VAC.

The measuring range runs from 0 to 30 PSIG (2 bar), and the slow-rise channel has an accuracy of 2 % of range at 25 °C. A continuous 0–1 mA or 4–20 mA output follows the pressure in the tank and feeds remote indication or SCADA. The supply is preset to 120/240 VAC 50-60 Hz, 125/250 VDC or 36-72 VDC, while the universal version works from 85-265 VAC or 110-370 VDC.

The sensor connects to a 1/4″-18 NPT port, and the panel and board are fixed on studs. With transition flanges, the 930 fits the mounting positions of 900 and 910 series relays without reworking the tank. The sensor and cable operate between -40 and 85 °C, the control board between -30 and 72 °C, with humidity of 10 to 90 % non-condensing. The input is protected against impulse interference to 2500 V under ANSI/OEE C37.90, and the insulation withstands 1500 VAC for 60 seconds.

Technical specifications

Typeelectronic pressure monitor with rapid pressure rise relay
Pressure range0–30 PSIG (0–2 bar)
Slow-rise set point1–15 PSIG (0–1 bar)
Fast-rise set point16-position rotary switch
Slow-channel accuracy2 % of range at 25 °C
Relays1 sensor: 3 SPDT; 3 sensors: 9 SPDT
Contact rating10 A, 1/3 HP at 120/240 VAC
Analogue output0–1 mA or 4–20 mA
Supply120/240 VAC 50-60 Hz, 125/250 VDC, 36-72 VDC; universal 85-265 VAC or 110-370 VDC
Sensor connection1/4″-18 NPT
Cable lengthup to 750 ft (228.6 m)
Sensor and cable temperature-40 to 85 °C
Board temperature-30 to 72 °C
Humidity10–90 % non-condensing
Impulse protection2500 V, ANSI/OEE C37.90
Dielectric strength1500 VAC, 60 s
Shock10 g, 3 ms, three axes

Part numbers

Show all part numbers (6)

930-007-01, 930-007-02, 930-008-01, 930-008-02, 930-009-02, 930-010-01

Request a price and lead time

930 Electronic Pressure Monitor and Rapid Pressure Rise Relay for Transformers. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can the 930 replace an existing 900 or 910 series relay?

Yes. Transition flanges are available that fit the mounting positions of the 900 and 910 series relays, so the tank does not need reworking.

How does the 930 pass pressure to SCADA?

Through a continuous analogue signal of 0–1 mA or 4–20 mA that is proportional to the pressure in the tank.

How many relays does the multi-sensor model have?

Nine SPDT relays: six for fast pressure rise, two for slow pressure rise and one for power status.