International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

909 Seal-In Relay for Transformer Pressure Surge Protection

The 909 series relay accepts a brief or chattering contact closure and holds the signal, so it can drive alarms and tripping. It is used alongside the 900 and 910 series rapid pressure rise relays on oil and gas-filled transformers.

Type
seal-in signal relay
Number of relays
2
Output
1 Form A and 1 Form C
Operating time
under 20 ms

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The 909 sits in the monitoring and control cabinet of a transformer, where the pressure sensor output arrives as a pulse. A rapid pressure rise relay from the 900 series for oil-filled units, or the 910 series for gas-filled units, gives a short pulse when an internal arc occurs. The 909 captures that pulse and holds it until the breaker trips the transformer and the operator resets the circuit. The same applies to chattering contacts, which are hard to route to alarms and other peripheral devices.

The housing contains two independent relays, with outputs of 1 Form A and 1 Form C and an operating time under 20 ms. Self-holding is provided by the relay contact itself, and the trip circuit contacts are protected by a surge suppressor. Electronics sit on a printed circuit board inside a type 304 stainless steel enclosure. A red LED shows that the trip relay has operated, while a yellow LED signals a short in the sensor circuit or faulty wiring. A manual reset button restores the initial state.

A jumper header sets the relay for the supply voltage and type of current, and the wiring diagrams and jumper positions are printed on the enclosure. The 909-300-01 runs on 24, 48 or 125 VDC, or 120 VAC, while the 909-300-02 runs on 48, 125 or 250 VDC, or 120 or 240 VAC. Both models carry UL recognition to UL508, and the 909-300-02 is also listed under UL 1604, Class I, Division II for hazardous locations.

Trip and alarm contacts are rated at 1/4 HP at 125/250 VAC, 8 A at 250 VAC and 8 A at 30 VDC on a resistive load. Insulation withstands 2500 VAC for one minute. Connections use screw terminal blocks rated at 20 A and 600 V under UL. The relay mounts on a surface inside the cabinet. Mounting dimensions and wiring are compatible with existing installations of similar devices, so an old relay can be replaced without modifying the cabinet. Operating temperature runs from -45 to 40 °C, ambient air from -45 to 70 °C, with humidity up to 95 % non-condensing. It withstands 60 to 120 Hz vibration at 0.004″ amplitude and 10 g shocks along three axes.

Technical specifications

Typeseal-in signal relay
Number of relays2
Output1 Form A and 1 Form C
Operating timeunder 20 ms
Supply 909-300-0124, 48 or 125 VDC, or 120 VAC
Supply 909-300-0248, 125 or 250 VDC, or 120 or 240 VAC
Trip and alarm contacts1/4 HP at 125/250 VAC; 8 A at 250 VAC; 8 A at 30 VDC (resistive)
Dielectric strength2500 VAC, 1 min
Connectionscrew terminal block, UL 20 A at 600 V
Mountingsurface mounted inside the cabinet
Enclosurestainless steel type 304
Operating temperature-45 to 40 °C
Ambient air temperature-45 to 70 °C
Humidity95 % non-condensing
Vibration60–120 Hz, 0.004″ on three axes
Shock10 g on three axes
CertificationUL508; UL 1604, Class I, Division II (909-300-02)

Part numbers

Show all part numbers (2)

909-300-01, 909-300-02

Request a price and lead time

909 Seal-In Relay for Transformer Pressure Surge Protection. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which sensors does the 909 relay work with?

Most often the 900 and 910 series rapid pressure rise relays on oil-filled and gas-filled transformers, and any pulsed or chattering contacts.

Which model should I choose for a 250 VDC supply?

The 909-300-02, which runs on 48, 125 or 250 VDC or 120 or 240 VAC and carries the UL 1604 listing, Class I, Division II.

How does the relay show a fault in the sensor circuit?

A yellow LED signals a short in the sensor circuit or faulty wiring, while a red LED shows that the trip relay has operated.