900/910 RPRR Pressure Rise Relay for Transformer Tank Protection
The 900/910 RPRR relay detects a fast rise in pressure inside a transformer tank by its rate of change, not its absolute value. When the event is dangerous, its contact changes state and sends an alarm or trip signal to limit the risk of tank damage.
- Type
- Mechanical pressure rise relay
- Version
- 900 for oil space; 910 for gas space
- Contact
- SPDT, snap action
- AC switching
- 15 A at 125, 250, 480 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The relay is used in protection systems for oil-filled and gas-filled transformers and other electrical equipment, guarding against tank rupture during internal faults. The 900 version is calibrated for the oil space of a transformer, while the 910 version is for the gas or air space. Units are fitted at utility and industrial sites, in repair workshops and at factories that build transformers.
The sensing element is a bellows. The device compares how quickly the pressure rises with the limits set by the transformer maker and operates only when the rise becomes hazardous. Ordinary pressure changes from temperature swings or vibration do not trigger it. The bellows withstands pressures from -14.7 PSIG to 20 PSIG, and the operating characteristics of the 900 and 910 series are set by separate response curves.
The output contact is a snap-action SPDT microswitch. On AC it switches 15 A at 125, 250 and 480 V, and on DC it switches 1/2 A at 125 V and 1/4 A at 250 V for resistive loads. To hold a short signal, the relay is usually wired together with a 909 latching relay, which has two output relays, LED indication and can be set for AC or DC voltage.
The housing and cover are die-cast aluminium, the O-ring seal is Viton and the standard finish is ANSI #70 powder coat, with C5-High available on request. The enclosure is rated IP65 and the ambient operating temperature runs from -40 °C to 82 °C. The unit can be mounted vertically or horizontally, in the gas or oil space, either on a flange with four slots, each 1/2 inch in diameter and equally spaced on a 4 inch bolt circle, or on a 2 1/2 inch 8 NPT tapered pipe male thread with a 3 inch hex wrench flat. The electrical connection is an ANSI connector, a military-style connector, a proprietary connector or a terminal box for direct cable wiring.
Every relay is calibrated at the factory, its contacts and operating time are checked, and each unit receives a serial number with the calibration records kept on file. A field test set with a GO/NO-GO test is available for on-site checks, and the FIX-601 bench reproduces the calibration tests in the factory.
Technical specifications
| Type | Mechanical pressure rise relay |
|---|---|
| Version | 900 for oil space; 910 for gas space |
| Contact | SPDT, snap action |
| AC switching | 15 A at 125, 250, 480 V |
| DC switching | 1/2 A at 125 V; 1/4 A at 250 V, resistive load |
| Minimum bellows pressure | -14.7 PSIG |
| Maximum bellows pressure | 20 PSIG |
| Ingress protection | IP65 |
| Housing and cover | Die-cast aluminium |
| Seal | Viton |
| Finish | ANSI #70 powder coat; C5-High on request |
| Flange mounting | 4 slots of 1/2 inch on a 4 inch bolt circle |
| Thread mounting | 2 1/2 inch 8 NPT, 3 inch hex wrench flat |
| Mounting position | Vertical or horizontal |
| Ambient temperature | -40 °C to 82 °C |
| Electrical connection | ANSI connector, military-style, proprietary connector; terminal box |
Part numbers
Show all part numbers (11)
RPRR112C1, RPRR21341, RPRR11351, RPRR222A1, RPRR21391, RPRR21141, 900-010-02, 900-0156-00, 910-015-34, 910-015-05, 910-010-03
Request a price and lead time
900/910 RPRR Pressure Rise Relay for Transformer Tank Protection. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can slow temperature changes operate the relay?
No, the relay responds to the speed of the pressure rise, so slow changes caused by temperature swings and vibration do not operate it.
Which version suits a gas cushion in a transformer?
The 910 version is for the gas space and the 900 version is for the oil space, and each has its own response curve.
How can a short contact pulse be held for the protection system?
The relay is wired to a 909 latching relay, which stores the operation and has two output relays.