International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

509 ITM Transformer Monitor with Direct Winding Temperature Measurement

An electronic monitor for medium and large oil-filled transformers and tap changers, measuring winding and oil temperature, controlling cooling, and logging parameters and events. Data is passed to the control system over DNP 3.0, Modbus RTU, IEC 61850 and IEC 60870.

Application
Oil-filled transformers, tap changers
Input modules
Up to 8, expandable to 16 inputs
Fibre optic inputs
Up to 16
Output relays
8 programmable Form C, 1 system status, 1 heater control

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The 509 ITM monitors oil-filled transformers and tap changers, both remotely and locally. It is fitted to vault transformers, large distribution units, medium and large power transformers, and sites where only temperature and pressure need watching. One enclosure combines measurement, alarms, cooling control and data logging, so separate temperature relays and loggers are not needed. The model codes are ITM509-100 for general transformer monitoring, ITM509-200 with extended cooling control, ITM509-300 with tap changer monitoring, and ITM509 DW with direct winding temperature measurement for the most critical transformers.

The base unit takes up to 8 input modules of configurable types, and expansion modules raise the total to 16 inputs. Up to 16 fibre optic inputs are provided for winding temperature sensors, and resistance thermometers of 10 Ω copper and 100 Ω platinum are supported over −40 to 120 °C. Input module error is ±0.5% of full scale, and pressure, oil level and flow sensors can also be connected.

The TransLife function calculates the wear rate of insulation, the loss of life, and the remaining life of each of the three windings separately. Critical Forecast estimates the time until a critical temperature is reached under current conditions, while Temperature Profiler keeps the temperature history. The monitor compares the measured and calculated winding temperatures in real time. Cooling control switches fan and pump groups in turn, pre-starts cooling when the load current exceeds a setpoint, and adjusts for seasonal air temperature.

Outputs are eight programmable Form C relays rated 10 A at 120/240 V AC and 10 A at 30 V DC, plus a system status relay and a heater control relay. The analogue output is 0–1 mA or 4–20 mA, selected in software. The log records up to 20 parameters at intervals from one minute to 24 hours. Shared non-volatile 32 MB flash memory holds 8 parameters at hourly intervals for more than 19 months, or 62500 time-stamped events.

Communication uses an RS-232 port on the front panel, an isolated four-wire RS-485 port, an ST optical port (820 nm, up to 1500 m), USB Type B for set-up and USB Type A for copying the log to a flash drive, with Ethernet as an option. Power is universal, 90–264 V AC at 47–63 Hz or 40–290 V DC, drawing under 35 W. Operating temperature runs from −40 to +72 °C. The unit meets IEC 61000-6-1 and IEC 61000-6-2 for EMC, IEEE C37.90.1 for surge withstand, and IEC 61010-1 for electrical safety.

Technical specifications

ApplicationOil-filled transformers, tap changers
Input modulesUp to 8, expandable to 16 inputs
Fibre optic inputsUp to 16
Output relays8 programmable Form C, 1 system status, 1 heater control
Contact rating10 A at 120/240 V AC, 10 A at 30 V DC
Analogue output0–1 mA (up to 450 Ω) or 4–20 mA (up to 10000 Ω)
Input module error±0.5% of full scale
Resistance thermometers10 Ω Cu, 100 Ω Pt, −40…120 °C
LogUp to 20 parameters, interval from 1 minute to 24 hours
Memory32 MB flash, up to 62500 events
ProtocolsDNP 3.0 level 1 slave, Modbus RTU, ASCII, IEC 61850, IEC 60870
InterfacesRS-232, RS-485, 820 nm ST optical up to 1500 m, USB A/B, Ethernet
Display2×16 character backlit LCD
Power supply90–264 V AC 47–63 Hz, 40–290 V DC
Power consumptionUnder 35 W
Dielectric strength2500 V AC, 60 s to earth
Operating temperature−40…+72 °C
Humidity5–90% non-condensing
StandardsIEEE C37.90.1, IEC 61000-6-1, IEC 61000-6-2, IEC 61010-1

Part numbers

Show all part numbers (7)

ITM509-100, ITM509-200, ITM509-300, ITM509 DW, ITM509-00060510, ITM509-00250659, ITM509-00252022

Request a price and lead time

509 ITM Transformer Monitor with Direct Winding Temperature Measurement. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is the difference between ITM509 DW and the ITM509-100, -200 and -300 versions?

The ITM509 DW uses fibre optic inputs for direct winding temperature measurement and compares it with the calculated value in real time. The -100, -200 and -300 versions are for general monitoring, cooling control and tap changer monitoring respectively.

Which protocols are available for SCADA integration?

DNP 3.0 level 1 slave, Modbus RTU, ASCII, IEC 61850 and IEC 60870, over RS-485, the optical port or Ethernet.

How much data does the log hold?

The 32 MB flash memory holds 8 parameters at hourly intervals for more than 19 months, or up to 62500 time-stamped events.

Similar equipment from other manufacturers