505 ITM Intelligent Transformer Monitor with Winding Thermal Model
An electronic monitor for remote and local supervision of an oil-filled transformer and its tap changer. It calculates winding temperature with a thermal model, controls cooling groups, raises alarms and reports to SCADA over DNP 3.0 and Modbus RTU.
- Application
- oil-filled transformers, tap changers, cooling control
- Input modules
- up to 4: 2 fixed, 2 configurable
- Input types
- 100 ohm Pt RTD, 10 ohm Cu RTD, heated thermowell, current transformers 5/10/20 A, 0 to 1 mA, 4 to 20 mA, potentiometer, dry and powered contacts
- RTD range
- -40 to 120 °C
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 505 ITM combines measurement, alarms and cooling control for an oil-filled transformer, together with monitoring of the tap changer, in one device, so separate units are not needed. Setup and data review use the ITM manager software. The TransLife function reports key condition figures for the transformer: the rate of life loss, the life consumed and the remaining life. Critical Forecast estimates the time to a critical temperature under present conditions, and Temperature Profiler keeps a history of temperatures.
Winding temperature is calculated with a thermal model from a clamp-on current transformer signal, and a more accurate calculation allows the transformer to carry a heavier load safely. Cooling control includes automatic rotation of fan and pump groups, pre-cooling ahead of overloads, adaptive set points that follow the trend in air temperature, and seasonal schedules. A low temperature lockout keeps oil pumps switched off in cold conditions, which helps prevent static electrification and arcing.
The monitor accepts up to four input modules, two fixed and two configurable. Available inputs are 100 ohm platinum and 10 ohm copper resistance thermometers covering -40 to 120 °C, a heated thermowell, clamp-on current transformers of 5, 10 and 20 A, voltage inputs of 0 to 140 V and 0 to 360 V, 0 to 1 mA and 4 to 20 mA current signals, 5K to 15K potentiometers, and dry and powered contacts. Input accuracy is ±0.5 % of full scale. Matrix relays act on set points, combinations of set points and differential calculations, which reduces nuisance trips.
Outputs are Form C relays rated 10 A at 120/240 V AC and 10 A at 30 V DC, plus 0 to 1 mA or 4 to 20 mA analogue outputs for SCADA. Communication is by RS-485 or RS-232 using DNP 3.0 level 3 slave, Modbus RTU and ASCII, and wired and wireless versions are available. The front panel carries a 2 by 16 character backlit LCD. Dielectric strength is 2500 V AC for 60 seconds to earth.
The monitor is supplied for panel mounting in a control cabinet, in a NEMA 4X fibreglass enclosure, in a stainless steel panel version or in a 19 inch rack. A heater is optional, for 120 or 240 V AC. Operating temperature is -40 to +72 °C, storage -50 to +85 °C, and humidity 5 to 90 % non-condensing. It withstands 10 g shock and vibration at 60/120 Hz at 0.004 inch and at 10/150 Hz at 1 g. It conforms to IEEE C37.90.1, IEC 61000-6-1, IEC 61000-6-2 and IEC 61010-1.
Technical specifications
| Application | oil-filled transformers, tap changers, cooling control |
|---|---|
| Input modules | up to 4: 2 fixed, 2 configurable |
| Input types | 100 ohm Pt RTD, 10 ohm Cu RTD, heated thermowell, current transformers 5/10/20 A, 0 to 1 mA, 4 to 20 mA, potentiometer, dry and powered contacts |
| RTD range | -40 to 120 °C |
| Current transformer range | 0 to 5, 10, 20 A |
| AC voltage | 0 to 140 and 0 to 360 V |
| Potentiometer | 5K to 15K |
| Input accuracy | ±0.5 % of full scale |
| Outputs | Form C, 10 A at 120/240 V AC, 10 A at 30 V DC |
| Analogue outputs | 0 to 1 mA or 4 to 20 mA |
| Protocols | DNP 3.0 level 3 slave, Modbus RTU, ASCII |
| Interfaces | RS-485, RS-232, wireless |
| Display | 2 by 16 character backlit LCD |
| Power consumption | below 15 W DC, below 30 W AC |
| Dielectric strength | 2500 V AC, 60 s to earth |
| Enclosure | NEMA 4X fibreglass, stainless steel panel, 19 inch rack |
| Operating temperature | -40 to +72 °C |
| Humidity | 5 to 90 % non-condensing |
| Standards | IEEE C37.90.1, IEC 61000-6-1, IEC 61000-6-2, IEC 61010-1 |
Part numbers
Show all part numbers (5)
ITM505-00146057, ITM505-00393286, ITM505-00049409, ITM505-00271801, ITM505-00416056
Request a price and lead time
505 ITM Intelligent Transformer Monitor with Winding Thermal Model. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many inputs does the 505 ITM have?
Up to four input modules, two fixed and two configurable. They can take RTDs, current transformers, voltage, current signals or contacts.
How is winding temperature determined?
It is calculated with a thermal model of the winding, using a signal from a clamp-on current transformer rated 5, 10 or 20 A.
Which protocols does the monitor support?
DNP 3.0 level 3 slave, Modbus RTU and ASCII over RS-485 or RS-232, as well as 0 to 1 mA or 4 to 20 mA analogue outputs.