141, 146, 148, 35600 and 47500 pressure and vacuum switches for transformers and tap changers

Pressure and vacuum switches of the 141, 146, 148, 35600 and 47500 series for control, limit and alarm functions on power transformers and tap changers. The snap-action contact resets automatically when pressure returns to the set level. Models 141 and 148 can be fitted with a dial gauge.

Contact type
SPDT (141, 146, 148); SPST or SPDT (35600/47500)
Number of contacts
up to 2 (141, 148); 1 (146); 2 or 3 (35600/47500)
Contact rating, AC
15 A at 125, 250, 480 V AC (141, 148); 15 A at 115, 250 V AC (146); 5 A at 125 V, 3 A at 250 V (35600)
Contact rating, DC
1/2 A at 125 V, 1/4 A at 250 V (141, 146, 148); 0.8 A at 110 V, 0.6 A at 125 V, 0.4 A at 220 V (35600)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

These switches monitor pressure or vacuum in transformer tanks, tap changers and other electrical apparatus, and send signals for control, limiting and alarm. They are used in transformer protection schemes to detect abnormal pressure, and also in systems handling steam, air and non-flammable gases. Set points are fixed at the factory or adjusted on site.

The contact is snap-action and returns to its initial position automatically, so no manual reset is needed. Repeatability is ±5% or ±0.4 PSI (3 kPa) of the set point. The SPST and SPDT contacts carry UL and CSA approvals. The 35600 models respond in under 15 milliseconds when pressure changes at 20 to 50 MPa per second, which makes them suitable for catching fast pressure surges. Pressure and vacuum switches can be grouped on a common manifold under a protective cover.

The 141 has an SPDT contact rated 15 A at 125, 250 and 480 V AC, 1/2 A at 125 V DC and 1/4 A at 250 V DC, up to two contacts, and an operating range from -29 to +74 °C. The 146 has a single contact rated 15 A at 115 and 250 V AC. The 148 works from -40 to +82 °C and has IP11 (NEMA 2) protection as standard. The 35600 and 47500 models have two or three SPST or SPDT contacts rated 5 A at 125 V AC and 3 A at 250 V AC, and on DC 0.8 A at 110 V, 0.6 A at 125 V and 0.4 A at 220 V, with an operating range of -40 to +80 °C.

The optional dial is 3.5 inches (88.9 mm), with a -10 to +10 PSI scale and an accuracy of ±2% in the middle half of the scale and ±3% in the first and last quarters. The case is cold-rolled steel, with stainless steel as an option. The bezel and lens are one-piece moulded polycarbonate, and the diaphragm is nitrile or Viton. The 141-005 has a 5 PSI working pressure and a bleed valve on the case for a 1/4 inch hose. An optional enclosure gives protection up to IP55 (NEMA 4). Vibration at 60 Hz and its multiples does not affect operation.

The switch mounts vertically at the centre of the rear wall. The tank connection is 1/4-18 NPT, a 5/16 inch compression fitting, G3/8 or M26 x 1.5 mm. Electrical connection is by flexible leads as standard, or by quick-disconnect terminals, screw terminals or sealed connectors.

Technical specifications

Contact typeSPDT (141, 146, 148); SPST or SPDT (35600/47500)
Number of contactsup to 2 (141, 148); 1 (146); 2 or 3 (35600/47500)
Contact rating, AC15 A at 125, 250, 480 V AC (141, 148); 15 A at 115, 250 V AC (146); 5 A at 125 V, 3 A at 250 V (35600)
Contact rating, DC1/2 A at 125 V, 1/4 A at 250 V (141, 146, 148); 0.8 A at 110 V, 0.6 A at 125 V, 0.4 A at 220 V (35600)
Repeatability±5% or ±0.4 PSI (3 kPa)
Response time, 35600under 15 ms at 20–50 MPa/s
Dial3.5 inches (88.9 mm), -10 to +10 PSI
Dial accuracy±2% in middle half, ±3% in first and last quarters of scale
Operating temperature-29 to +74 °C (141, 146); -40 to +82 °C (148); -40 to +80 °C (35600)
Tank connection1/4-18 NPT, 5/16 inch compression, G3/8, M26 x 1.5 mm
Casecold-rolled steel or stainless steel
Diaphragmnitrile, Viton
ProtectionIP11 (NEMA 2), optionally IP55 (NEMA 4)
Mountingvertical, centre of rear wall

Part numbers

Show all part numbers (25)

141-001-01_CS-3752, 141-005-01_CS-45881, 141-1_PT1, 141-1_PT1_CS-51200, 141-007-01, 141-005-02_CS-47508, 141-1_PT1_CS-49465, 141-001-01_CS-51784, 141-002-01_CS-43767, 141-003-01, 141-005-02_CS-61894, 141-001-01_CS-40254, 141-005-01_CS-59980, 141-001-01_CS-40871, 141-001-01_CS-51156, 141-005-01_CS-50688, 141-001-01_CS-53463, 141-002-01, 141-005-01_CS-41261, 141-1_PT1_CS-43521, 141-005-01_CS-51480, 141-001-01_CS-30697, 141-001-01_CS-47285, 141-003-01_CS-61371, 141-003-01_CS-48231

Request a price and lead time

141, 146, 148, 35600 and 47500 pressure and vacuum switches for transformers and tap changers. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which switch suits detecting a fast pressure surge?

The 35600 models respond in under 15 ms when pressure changes at 20 to 50 MPa per second. The 141 and 148 switches cover pressure and vacuum control with a repeatability of ±5%.

Does the switch need a manual reset after operating?

No. The snap-action contact returns automatically when pressure comes back to the set level.

What tank connections are available?

A 1/4-18 NPT thread, a 5/16 inch compression fitting, G3/8 or M26 x 1.5 mm for the 35600 and 47500 models.