International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

130 and WT thermal plates simulating transformer winding temperature

Thermal plates 130 and WT simulate transformer winding temperature: a heater in the well is fed from a current transformer and adds a rise proportional to load to the oil temperature. Versions have 1 to 3 wells, and the 130 has one or two Pt100 sensors for remote indication and SCADA.

Purpose
winding temperature simulation, oil temperature measurement
Wells
1 (130); 1 to 3 (WT, 2WT, 3WT, 1WTL, 2WTL)
Resistance thermometer
1 or 2, Pt100; optionally Cu10
Current transformer (130)
1 A rated, 2 A maximum under overload

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Direct measurement of transformer winding temperature is usually not economical, so it is simulated indirectly. The sensor reads the temperature of the top oil layers, while a heater in the well, fed from a current transformer, adds a rise that follows the load. Thermal plates are used on new and in-service transformers, together with indicators, sensors and remote monitoring systems, including condition-based maintenance.

The 130 has a single well with a built-in heater and one or two resistance thermometers, either platinum Pt100 or, optionally, copper Cu10. The Pt100 signal is converted to a 4–20 mA output for transmission over long distances. The winding rise is set by jumpers on the resistor network near the current transformer input, from 0 to 38 °C at 30 °C oil temperature in 2 °C steps. The current transformer is rated 1 A, with a 2 A maximum under overload. The nickel-alloy heating grid and leads have a resistance of 0.164 Ω.

The WT plates have one to three wells for winding and oil thermometers. The WT, 2WT and 3WT carry heaters, while the 1WTL and 2WTL add a well without a heater for oil temperature. Simulation systems are built for current transformers of 1, 2 or 5 A. For currents up to 10 A an autotransformer, TRA-001, is used, and matching devices and trimming resistors cover other cases. In the multi-well plate the series 104 thermometer sensor goes into the heating coil, and the trimming resistor sits between the current transformer and the coil.

The housing is die-cast aluminium with ANSI #70 powder coating, optionally C5-High, and the sensors are brass. The plate is 102 mm across with one well and 165 mm with three, and the mounting hole is 51 mm and 102 mm respectively. The tank connection is G 1.00 inch per DIN 42554, the sensors are sealed with an O-ring and have a 7/8-14 UNF-2B thread, and the plate is mounted on the top or side of the tank.

The enclosure is rated IP54 to DIN 40050 (NEMA 3R), with screw terminals and a dielectric strength of 2000 V AC for one minute. The operating range is -40 to +70 °C ambient and -40 to +135 °C oil temperature, with humidity of 0 to 90% without condensation.

Technical specifications

Purposewinding temperature simulation, oil temperature measurement
Wells1 (130); 1 to 3 (WT, 2WT, 3WT, 1WTL, 2WTL)
Resistance thermometer1 or 2, Pt100; optionally Cu10
Current transformer (130)1 A rated, 2 A maximum under overload
Winding rise setting0 – 38 °C at 30 °C oil, 2 °C steps
Heaternickel alloy, 0.164 Ω
Plate diameter102 mm (1 well), 165 mm (3 wells)
Mounting hole51 mm (1 well), 102 mm (3 wells)
Tank connectionG 1.00 inch, DIN 42554
Sensor connectionO-ring seal, 7/8-14 UNF-2B
Mountingtop or side of tank
Housingdie-cast aluminium, ANSI #70 or C5-High
Protection ratingIP54 to DIN 40050 (NEMA 3R)
Dielectric strength2000 V AC, 1 min
Ambient temperature-40 … +70 °C
Oil temperature-40 … +135 °C
Humidity0 – 90%, non-condensing
Connectionscrew terminals

Part numbers

Show all part numbers (25)

130-003-01, 130-003-02, 130-003-01_CS-44603, 130-003-01_CS-33107, 130-003-02_CS-35712, 130-003-02_CS-51607, 130-003-01_CS-61649, 130-001-02_CS-55452, 130-001-05, 130-003-01_CS-45546, 130-003-02_CS-50808, 130-003-01_CS-46149, 130-003-01_CS-43398, 130-003-01_CS-41623, 130-001-02_CS-49841, 130-003-03_CS-33474, 130-001-04_CS-34227, 130-001-01, 130-001-01_CS-62780, 130-003-02_CS-33105, 130-001-02_CS-40492, 130-001-02_CS-45055, 130-001-04_CS-48347, 130-001-02, 130-001-02_CS-33129

Request a price and lead time

130 and WT thermal plates simulating transformer winding temperature. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How is the winding rise set on the 130 plate?

With jumpers on the resistor network near the current transformer input. The range is 0 to 38 °C at 30 °C oil, in 2 °C steps.

Can a 4–20 mA current signal be obtained?

Yes, the Pt100 signal from the 130 plate is converted to 4–20 mA by a separate converter for transmission over long distances.

What if the current transformer secondary is 10 A?

For currents up to 10 A an autotransformer, TRA-001, is used. Matching devices and trimming resistors cover other currents.