130 and WT thermal plates simulating transformer winding temperature
Thermal plates 130 and WT simulate transformer winding temperature: a heater in the well is fed from a current transformer and adds a rise proportional to load to the oil temperature. Versions have 1 to 3 wells, and the 130 has one or two Pt100 sensors for remote indication and SCADA.
- Purpose
- winding temperature simulation, oil temperature measurement
- Wells
- 1 (130); 1 to 3 (WT, 2WT, 3WT, 1WTL, 2WTL)
- Resistance thermometer
- 1 or 2, Pt100; optionally Cu10
- Current transformer (130)
- 1 A rated, 2 A maximum under overload
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Direct measurement of transformer winding temperature is usually not economical, so it is simulated indirectly. The sensor reads the temperature of the top oil layers, while a heater in the well, fed from a current transformer, adds a rise that follows the load. Thermal plates are used on new and in-service transformers, together with indicators, sensors and remote monitoring systems, including condition-based maintenance.
The 130 has a single well with a built-in heater and one or two resistance thermometers, either platinum Pt100 or, optionally, copper Cu10. The Pt100 signal is converted to a 4–20 mA output for transmission over long distances. The winding rise is set by jumpers on the resistor network near the current transformer input, from 0 to 38 °C at 30 °C oil temperature in 2 °C steps. The current transformer is rated 1 A, with a 2 A maximum under overload. The nickel-alloy heating grid and leads have a resistance of 0.164 Ω.
The WT plates have one to three wells for winding and oil thermometers. The WT, 2WT and 3WT carry heaters, while the 1WTL and 2WTL add a well without a heater for oil temperature. Simulation systems are built for current transformers of 1, 2 or 5 A. For currents up to 10 A an autotransformer, TRA-001, is used, and matching devices and trimming resistors cover other cases. In the multi-well plate the series 104 thermometer sensor goes into the heating coil, and the trimming resistor sits between the current transformer and the coil.
The housing is die-cast aluminium with ANSI #70 powder coating, optionally C5-High, and the sensors are brass. The plate is 102 mm across with one well and 165 mm with three, and the mounting hole is 51 mm and 102 mm respectively. The tank connection is G 1.00 inch per DIN 42554, the sensors are sealed with an O-ring and have a 7/8-14 UNF-2B thread, and the plate is mounted on the top or side of the tank.
The enclosure is rated IP54 to DIN 40050 (NEMA 3R), with screw terminals and a dielectric strength of 2000 V AC for one minute. The operating range is -40 to +70 °C ambient and -40 to +135 °C oil temperature, with humidity of 0 to 90% without condensation.
Technical specifications
| Purpose | winding temperature simulation, oil temperature measurement |
|---|---|
| Wells | 1 (130); 1 to 3 (WT, 2WT, 3WT, 1WTL, 2WTL) |
| Resistance thermometer | 1 or 2, Pt100; optionally Cu10 |
| Current transformer (130) | 1 A rated, 2 A maximum under overload |
| Winding rise setting | 0 – 38 °C at 30 °C oil, 2 °C steps |
| Heater | nickel alloy, 0.164 Ω |
| Plate diameter | 102 mm (1 well), 165 mm (3 wells) |
| Mounting hole | 51 mm (1 well), 102 mm (3 wells) |
| Tank connection | G 1.00 inch, DIN 42554 |
| Sensor connection | O-ring seal, 7/8-14 UNF-2B |
| Mounting | top or side of tank |
| Housing | die-cast aluminium, ANSI #70 or C5-High |
| Protection rating | IP54 to DIN 40050 (NEMA 3R) |
| Dielectric strength | 2000 V AC, 1 min |
| Ambient temperature | -40 … +70 °C |
| Oil temperature | -40 … +135 °C |
| Humidity | 0 – 90%, non-condensing |
| Connection | screw terminals |
Part numbers
Show all part numbers (25)
130-003-01, 130-003-02, 130-003-01_CS-44603, 130-003-01_CS-33107, 130-003-02_CS-35712, 130-003-02_CS-51607, 130-003-01_CS-61649, 130-001-02_CS-55452, 130-001-05, 130-003-01_CS-45546, 130-003-02_CS-50808, 130-003-01_CS-46149, 130-003-01_CS-43398, 130-003-01_CS-41623, 130-001-02_CS-49841, 130-003-03_CS-33474, 130-001-04_CS-34227, 130-001-01, 130-001-01_CS-62780, 130-003-02_CS-33105, 130-001-02_CS-40492, 130-001-02_CS-45055, 130-001-04_CS-48347, 130-001-02, 130-001-02_CS-33129
Request a price and lead time
130 and WT thermal plates simulating transformer winding temperature. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How is the winding rise set on the 130 plate?
With jumpers on the resistor network near the current transformer input. The range is 0 to 38 °C at 30 °C oil, in 2 °C steps.
Can a 4–20 mA current signal be obtained?
Yes, the Pt100 signal from the 130 plate is converted to 4–20 mA by a separate converter for transmission over long distances.
What if the current transformer secondary is 10 A?
For currents up to 10 A an autotransformer, TRA-001, is used. Matching devices and trimming resistors cover other currents.