038 Gas Accumulation Indicator for Conservator Transformers, 0 to 450 cm³ Scale
The 038 indicator mechanically measures the volume of gas that collects in a transformer with a conservator and gives a signal when the gas displaces more than 200 cm³ of oil. A built-in sampling port allows gas to be taken for laboratory analysis.
- Type
- Mechanical gas accumulation indicator
- Standard scale
- 0 to 450 cm³
- Alarm threshold
- More than 200 cm³ of displaced oil
- Switch
- SPDT, latched signal
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The indicator is fitted to power transformers with a conservator, including high-voltage units rated from 34 kV up to 345 kV or more, at utility and industrial sites. Gas forms inside a transformer during an internal arc or when insulation breaks down, so continuous measurement of the gas volume helps spot damage at an early stage and schedule maintenance according to the actual condition of the unit.
The dial shows the total volume of accumulated gases at all times. A SPDT switch inside the case operates when the gas displaces more than 200 cm³ of oil and switches on a latched alarm signal. The signal stays active until enough gas has been drawn from the collector. The standard scale runs from 0 to 450 cm³.
The 6 inch dial (152.5 mm) is tilted at 15 degrees, so the reading can be seen from ground level beside the base of the transformer. The scale can be customised for a specific application. The case and flange are aluminium with a thermosetting powder finish, the mounting parts, cup and rim are stainless steel, and the window is UV-stabilised polycarbonate. The case is either sealed or vented and meets IP54.
The switch carries 15 A at 125, 250 and 480 V AC on a resistive load, and 1/2 A at 125 V and 1/4 A at 250 V DC. Dielectric strength is 1500 V AC for one minute. The operating range is -40 °C to +80 °C with ambient humidity from 35% to 100%, and the unit weighs 5 kg. It connects to the tank through a 3/8 inch 18 NPT thread and is fixed by two 5/8 inch studs or bolts, 1.5 inch long, on 4.25 inch centres.
Cable entry type, cable type, colour and length are chosen to order. A VLV-602-2 sampling valve kit can be supplied to order; it is mounted at the side of the tank at ground level under a protective cover. A KIT-005-1 syringe kit draws a gas sample of a set volume.
Technical specifications
| Type | Mechanical gas accumulation indicator |
|---|---|
| Standard scale | 0 to 450 cm³ |
| Alarm threshold | More than 200 cm³ of displaced oil |
| Switch | SPDT, latched signal |
| AC switching | 15 A at 125, 250, 480 V, resistive load |
| DC switching | 1/2 A at 125 V; 1/4 A at 250 V, resistive load |
| Dielectric strength | 1500 V AC, 1 minute |
| Dial | 6 inch (152.5 mm), tilted 15 degrees |
| Case | Sealed or vented, IP54 |
| Tank connection | 3/8 inch 18 NPT |
| Mounting | 2 studs or bolts, 5/8 inch, on 4.25 inch centres |
| Operating temperature | -40 °C to +80 °C |
| Ambient humidity | 35% to 100% |
| Weight | 5 kg |
| Options | VLV-602-2, KIT-005-1 |
Part numbers
Show all part numbers (11)
038-001-02, 038-002-01, 038-002-02, 038-003-01, 038-003-03, 038-005-01, 038-005-02, 038-008-01, 038-009-01, 038-002-01-S, 038-009-01-S
Request a price and lead time
038 Gas Accumulation Indicator for Conservator Transformers, 0 to 450 cm³ Scale. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
When does the indicator signal contact operate?
The SPDT switch operates when the accumulated gas displaces more than 200 cm³ of oil, and the signal stays latched until gas has been drawn off.
How can a gas sample be taken at ground level?
A VLV-602-2 valve kit is mounted at the side of the tank at ground level and connected to the indicator by a tube.
Which transformers is the indicator intended for?
Power transformers with a conservator, including high-voltage units rated from 34 kV up to 345 kV or more.