Rotoblok / Rotoblok SF / Air / VCB — air-insulated medium-voltage switchgear up to 25 kV

The Rotoblok series covers modular indoor MV switchgear with air insulation for voltages up to 24–25 kV, 50 Hz. It is used in industrial and distribution networks. Cells of all versions, Rotoblok SF, Air and VCB, are compatible with each other.

Rated voltage
up to 24–25 kV, 50 Hz
Rated current (VCB)
630 A
Short-time withstand current (VCB)
up to 16 kA (3 s) / 20 kA (1 s)
Internal arc withstand (VCB)
AFLR up to 16 kA (1 s)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The Rotoblok VCB version uses a three-function vacuum circuit breaker-disconnector-earthing switch. The rated current of the VCB is 630 A, the short-time withstand current is up to 16 kA for 3 s or 20 kA for 1 s. Internal arc withstand AFLR is up to 16 kA (1 s), the degree of protection is IP 43. The cells are two-compartment, in a galvanized metal enclosure, with a single busbar system.

Technical specifications

Rated voltageup to 24–25 kV, 50 Hz
Rated current (VCB)630 A
Short-time withstand current (VCB)up to 16 kA (3 s) / 20 kA (1 s)
Internal arc withstand (VCB)AFLR up to 16 kA (1 s)
Degree of protection (VCB)IP 43
Designtwo-compartment cells in a galvanized metal enclosure, single busbar system

Request a price and lead time

Rotoblok / Rotoblok SF / Air / VCB — air-insulated medium-voltage switchgear up to 25 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8537 20 91 00
HS, 6 digits8537 20
CN (EU)8537 20 91
HTSUS (USA)8537 20 00 40
China customs tariff8537 20 90 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What voltage is Rotoblok rated for?

The rated voltage is up to 24–25 kV at a frequency of 50 Hz.

Which circuit breaker is installed in Rotoblok VCB?

A three-function vacuum circuit breaker-disconnector-earthing switch. The rated current is 630 A, the short-time withstand current is up to 16 kA (3 s) or 20 kA (1 s).

Can cells of different versions be combined?

Yes, cells of all Rotoblok versions are compatible with each other. The design is two-compartment, in a galvanized enclosure, with a single busbar system.