International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

NXAIR M / NXAIR C / NXAIR H — air-insulated switchgear 24–36 kV, up to 31.5 kA

NXAIR M, NXAIR C and NXAIR H are air-insulated switchgear for 24–36 kV networks with breaking currents up to 31.5 kA. Withdrawable vacuum circuit breakers, LSC 2B, internal arc IAC A FLR 1 s. For utility substations, industry, power plants and renewable energy.

NXAIR M
24 kV; 25 kA (3 s); peak 63/65 kA; busbars 2500 A; feeders 800–2500 A; width 800/1000 mm; height 2510 mm
NXAIR C
up to 24 kV; up to 25 kA; up to 2000 A; LSC2
NXAIR H
36 kV; 31.5 kA (3 s); peak 80/82 kA; busbars 2500 A; feeders 800–2500 A (up to 2900 A); width 1000 mm; height 2800 mm
Withstand voltage / impulse
50 (GOST 65) / 125 kV (24 kV); 70 / 170 kV (36 kV)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

NXAIR M, NXAIR C and NXAIR H are versions of the NXAIR family of air-insulated switchgear for 20–35 kV networks. Like the basic series, these are factory-built switchgear assemblies type tested to IEC 62271-200 with withdrawable vacuum circuit breakers, metallic partitions (class PM), category LSC 2B and internal arc classification IAC A FLR (1 s).

The internal arc stays within the compartment because the partitions are pressure resistant. All operations are performed with the high-voltage doors closed, and the position of the switching devices is shown by unambiguous indicators. The insulating medium is air, the materials are fully recyclable, and the service intervals are more than 10 years.

NXAIR M at 24 kV is rated for a breaking and short-time withstand current of 25 kA (3 s), a peak withstand current of 63/65 kA, a busbar current of 2500 A and feeder currents of 800, 1250, 2000 and 2500 A. The power-frequency withstand voltage is 50 kV (65 kV per GOST) and the lightning impulse withstand voltage is 125 kV. Panels 800 and 1000 mm wide have a height of 2510 mm and a depth of 1600 mm, and some characteristics exceed the IEC requirements. The switchgear is aimed at utilities, infrastructure and industry. For the automotive industry there is a separate version with a circuit breaker panel and HV HRC high-voltage fuses.

NXAIR C is a compact switchgear up to 24 kV, 25 kA and 2000 A with category LSC2. It is installed in primary distribution substations of utilities, industry and infrastructure, including traction power supply and mining and metallurgical plants.

NXAIR H at 36 kV is rated for 31.5 kA (3 s), a peak withstand current of 80/82 kA, a withstand voltage of 70 kV and a lightning impulse of 170 kV, a busbar current of 2500 A and feeder currents of 800–2500 A (up to 2900 A according to the manufacturer's catalog). A panel 1000 mm wide, 2800 mm high and 2670 mm deep allows wall-mounted and free-standing installation without limits up to the maximum short-circuit currents. All versions can be connected to the SICAM A8000 and Electrification X monitoring systems. Applications are 20–35 kV substations of distribution networks, industrial plants, power plants and renewable energy facilities.

Technical specifications

NXAIR M24 kV; 25 kA (3 s); peak 63/65 kA; busbars 2500 A; feeders 800–2500 A; width 800/1000 mm; height 2510 mm
NXAIR Cup to 24 kV; up to 25 kA; up to 2000 A; LSC2
NXAIR H36 kV; 31.5 kA (3 s); peak 80/82 kA; busbars 2500 A; feeders 800–2500 A (up to 2900 A); width 1000 mm; height 2800 mm
Withstand voltage / impulse50 (GOST 65) / 125 kV (24 kV); 70 / 170 kV (36 kV)
ClassificationLSC 2B, PM, IAC A FLR 1 s
StandardIEC 62271-200

Request a price and lead time

NXAIR M / NXAIR C / NXAIR H — air-insulated switchgear 24–36 kV, up to 31.5 kA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What are the voltages and short-circuit currents of the NXAIR M, C and H versions?

NXAIR M is rated for 24 kV and 25 kA (3 s), NXAIR C up to 24 kV and 25 kA, NXAIR H for 36 kV and 31.5 kA (3 s). Busbar current is up to 2500 A for M and H, and C feeders are up to 2000 A.

What are the panel dimensions of NXAIR H?

Width 1000 mm, height 2800 mm, depth 2670 mm. Wall-mounted and free-standing installation is permitted without limits up to the maximum short-circuit currents.

What is the NXAIR M version intended for?

For utility, infrastructure and industrial substations at 24 kV, and there is a separate version for the automotive industry. Panels 800 and 1000 mm wide have a height of 2510 mm.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00