International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

HS-X, cubicle GIS 24/36 kV for primary substations

HS-X at 24/36 kV is a cubicle gas-insulated switchgear (C-GIS) for indoor installation. It is installed at 36 kV primary substations, at large industrial consumers, in power plant switchgear and at renewable energy facilities, including offshore wind farms. Rated currents are 630, 1250, 2000 and 2500 A.

Rated voltage
24 / 36 kV
Rated current
630, 1250, 2000, 2500 A
Short-time withstand current
25 / 31.5 / 40 kA, 3 s
Insulation level
125 / 170 kV (lightning impulse), 50 / 70 kV (1 min)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The switchgear is made with a single and a double busbar system. Both versions protect personnel during an internal arc fault, with classification AFLR 31.5 kA / 1 s or 40 kA / 1 s according to IEC 62271-200. The vacuum circuit breakers have a motor-spring mechanism.

The plug-in busbars have solid insulation. Therefore no gas work is done on site during installation and extension of the switchgear. The gas compartments are filled to rated pressure at the factory and divided by installation unit, so installation is faster and simpler. Each installation unit is tested at the factory, which shortens the time to put the substation into operation and preserves the quality of the equipment during transport.

The rated voltage is 24 or 36 kV, the frequency 50/60 Hz. The power frequency withstand voltage is 50 / 70 kV for 1 minute, and the lightning impulse withstand voltage 125 / 170 kV. The short-time withstand current is 25, 31.5 or 40 kA for 3 s. SF6 is at a low gauge pressure of 0.03 MPa, and the alarm operates when it falls to 0.02 MPa. The low gauge pressure reduces the mechanical load on the walls of the gas compartments.

An outgoing 24 kV 1250 A cell has typical dimensions of 600×1900×2300 mm, another version 800×1900×2910 mm. The depth of 1900 mm is the same for both versions, so cells of different width and height stand in one row. Cells 600 mm wide make it possible to place a switchboard with many connections in a small switchgear room. For incomers and bus sections at higher currents, suitable cells from the same range are chosen.

Like the smaller HS-X model for 12/24 kV, the switchgear draws on the manufacturer's experience in cubicle GIS and vacuum switching. The design is compact and needs minimal maintenance throughout its service life. For offshore wind farms, where access to equipment is limited, minimal maintenance is of practical importance. The cubicle GIS HS-X for 24/36 kV complements the smaller model for 12/24 kV, so switchboards of different voltage classes of one series can be supplied to one site.

Technical specifications

Rated voltage24 / 36 kV
Rated current630, 1250, 2000, 2500 A
Short-time withstand current25 / 31.5 / 40 kA, 3 s
Insulation level125 / 170 kV (lightning impulse), 50 / 70 kV (1 min)
Insulating mediumSF6, 0.03 MPa gauge (alarm 0.02 MPa)
Internal arcAFLR 31.5 kA / 1 s; AFLR 40 kA / 1 s
Breaker drivemotor-spring
Dimensions (24 kV, 1250 A, outgoing)600×1900×2300 / 800×1900×2910 mm
StandardIEC 62271-200
Busbarssingle and double system

Request a price and lead time

HS-X, cubicle GIS 24/36 kV for primary substations. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8537 20 91 00
HS, 6 digits8537 20
CN (EU)8537 20 91
HTSUS (USA)8537 20 00 00
China customs tariff8537 20 90 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What rated currents does HS-X 24/36 kV have?

630, 1250, 2000 and 2500 A. The short-time withstand current is 25, 31.5 or 40 kA for 3 s.

What internal arc withstand does the GIS have?

Classification AFLR 31.5 kA / 1 s or 40 kA / 1 s according to IEC 62271-200 for single and double busbar versions.

Is gas work needed during installation?

No, the plug-in busbars have solid insulation. The gas compartments are filled at the factory to a gauge pressure of 0.03 MPa.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides