cgm.zero24 — SF6-free compact switchgear up to 24 kV / 630 A
The cgm.zero24 belongs to modular secondary distribution switchgear rated up to 24 kV and 630 A. It uses technical air insulation instead of SF6, with a short-circuit current of 20 kA. It is installed in transformer substations and is ready for automation.
- Voltage
- up to 24 kV
- Current
- up to 630 A
- Short-circuit current
- 20 kA
- Arc containment
- IAC AFL(R) 20 kA / 1 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The insulating medium is technical air with GWP = 1 at a pressure of up to 1.5 bar abs., and the unit contains no SF6. The design is modular, and the panels are assembled to suit the scheme of a particular substation. Arc containment corresponds to class IAC AFL(R) 20 kA / 1 s. Built to the IEC standard.
Technical specifications
| Voltage | up to 24 kV |
|---|---|
| Current | up to 630 A |
| Short-circuit current | 20 kA |
| Arc containment | IAC AFL(R) 20 kA / 1 s |
| Insulation | technical air, GWP = 1, pressure up to 1.5 bar abs. |
| Design | modular |
| Standard | IEC |
Request a price and lead time
cgm.zero24 — SF6-free compact switchgear up to 24 kV / 630 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8537 20 91 00 |
|---|---|
| HS, 6 digits | 8537 20 |
| CN (EU) | 8537 20 91 |
| HTSUS (USA) | 8537 20 00 20 |
| China customs tariff | 8537 20 90 00 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
What insulates the cgm.zero24?
Technical air with GWP = 1 at a pressure of up to 1.5 bar abs., instead of SF6.
What are the rated parameters of the switchgear?
Voltage up to 24 kV, current up to 630 A, short-circuit current 20 kA.
What is the internal arc withstand class?
IAC AFL(R) 20 kA / 1 s.