International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

CABINEL modular and compact SF6-insulated secondary distribution switchgear 12–36 kV

CABINEL is a family of metal-enclosed secondary distribution units with SF6 gas insulation for 12, 24 and 36 kV and currents up to 630 A. They are intended for indoor installation in ring and radial medium voltage networks. More than 90 % of the components are made and assembled at the manufacturer's plant in Toledo.

Rated voltage
12, 24, 36 kV
Rated current
400/630 A
ISF load break switch
20 kA, 50 kA making, M2, E3; 125/145 kV (24 kV), 170–175/195 kV (36 kV)
Vacuum circuit breaker
125/170 kV impulse, 50/70 kV, 20 kA 3 s, 50 kA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

CABINEL units are approved by the largest national and foreign utilities. They are installed indoors in all types of medium voltage distribution networks, ring and radial, fed from one or several points. More than 90 % of the components are made and assembled at the manufacturer's plant in Toledo.

There are two systems. In the modular system one function corresponds to one module, the modules are connected in parallel and the combination is selected for the customer. They are available extensible on one or both sides, or non-extensible. Connections are made with double 630 A connectors, and the free sides of the end units are closed with end caps. The compact system combines several functions in one enclosure with the same characteristics and costs less than the equivalent modular one. The functions are distributed as follows. CML1/CML2 are line units, CMPF1/CMPF2 fuse protection, CMPAS circuit breaker protection with a disconnector, CMR riser units, CMM metering units.

Rated voltages are 12, 24 and 36 kV, currents up to 630 A. The ISF switch-disconnector is rated 400/630 A, with a short-time withstand current of 20 kA, a peak current of 50 kA, a making capacity of 50 kA, mechanical class M2 and electrical class E3. Insulation for 24 kV is 125/145 kV impulse and 50/60 kV power frequency, for 36 kV it is 170–175/195 kV and 70/80 kV. The vacuum circuit breaker withstands 20 kA for 3 s and makes 50 kA. The SF6 filling pressure is 0.03 MPa for 24 kV and 0.05 MPa for 36 kV. The enclosure protection degree is IP2X, impact resistance IK08, and the SF6 tank has IP67.

The units are tested for internal arc withstand and can operate for 24 hours fully submerged, so they are used in underground substations at risk of flooding. Control is local and remote, with integration into communication and SCADA systems. The equipment includes a pressure gauge, a voltage indication system, interlocks and fuse operation signalling. Standards are IEC 62271-200, -103, -105, -102, -100, IEC 60282-1, IEC 60376, EN 50181, IEC 60529. Applications: transformer substations, sectionalizing points, data centres, charging stations and renewable energy sites.

Technical specifications

Rated voltage12, 24, 36 kV
Rated current400/630 A
ISF load break switch20 kA, 50 kA making, M2, E3; 125/145 kV (24 kV), 170–175/195 kV (36 kV)
Vacuum circuit breaker125/170 kV impulse, 50/70 kV, 20 kA 3 s, 50 kA
SF6 pressure0.03 MPa (24 kV), 0.05 MPa (36 kV)
Protection degreeIP2X, IK08; tank IP67
FunctionsCML1/CML2 (line), CMPF1/CMPF2 (fuse protection), CMPAS (circuit breaker), CMR, CMM (metering)
Flooding24 h operation under water
StandardsIEC 62271-200, -103, -105, -102, -100, IEC 60282-1, IEC 60376, EN 50181

Request a price and lead time

CABINEL modular and compact SF6-insulated secondary distribution switchgear 12–36 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What voltage and current classes do CABINEL units have?

Rated voltages are 12, 24 and 36 kV, currents 400/630 A. The ISF switch-disconnector withstands 20 kA and makes 50 kA.

How do the modular and compact systems differ?

In the modular system one function corresponds to one module, and the units are connected in parallel. The compact system combines several functions in one enclosure with the same characteristics and costs less than the equivalent modular one.

What SF6 pressure and protection degree do the units have?

The filling pressure is 0.03 MPa for 24 kV and 0.05 MPa for 36 kV. The enclosure has IP2X and IK08, the SF6 tank has IP67, and the units operate for 24 hours under water.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides