SGT/XSGT 4-Wire Strain Gage Transmitter, 4-20mA Output
The SGT converts a strain gage input into 4-20mA or another standard process current or voltage output. It has an adjustable excitation source, 10 megohm input impedance and complete isolation of input, output and power.
- Type
- strain gage transmitter, 4-wire
- Input
- strain gage
- Standard outputs
- 1-5 mA, 4-20 mA, 10-50 mA or voltage
- Isolation
- complete: input, output, power input
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A strain gage input goes in, and a 4-20mA signal or any other standard process current or voltage signal comes out. Typical applications are pressure transducers, load cells and stress-strain measurements. Output noise or ripple is under 10 millivolts peak to peak, which suits computer interface applications.
Input, output and power input are completely isolated from one another, so the SGT can be applied to virtually any input source, grounded or ungrounded, without interface problems. The adjustable, regulated excitation source for the gage is built in. High input impedance of 10 megohms is standard and simplifies interfacing. Common mode rejection is 120 dB (1,000,000:1), which minimises errors caused by signal noise.
Standard output ranges are 1-5 mA, 4-20 mA, 10-50 mA or voltage. Temperature stability is ±0.005%/°F over a range of -20°F to +180°F. An optional push-button calibration feature increments the strain gage signal by a fixed amount equal to a known output, giving a quick system check.
For multichannel applications the SGT is available as a compact plug-in card module for the standard 11-position relay rack, or for a 5-15 position card rack for surface mounting. An explosion-proof housing (EX) is also available.
Technical specifications
| Type | strain gage transmitter, 4-wire |
|---|---|
| Input | strain gage |
| Standard outputs | 1-5 mA, 4-20 mA, 10-50 mA or voltage |
| Isolation | complete: input, output, power input |
| Input impedance | 10 megohms |
| Common mode rejection | 120 dB (1,000,000:1) |
| Output ripple | less than 10 mV peak-to-peak |
| Temperature stability | ±0.005%/°F over -20°F to +180°F |
| Multichannel | plug-in card: 11-position relay rack or 5-15 position card rack |
| Housing | standard, plug-in, explosion-proof (EX) |
How it compares with similar models
| Parameter | SGT/XSGT 4-Wire Strain Gage Transmitter, 4-20mA Output | FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing | SPA2 programmable temperature transmitter and alarm trip, RTD, T/C, mV, ohms, 2 relays, analogue output | SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation |
|---|---|---|---|---|
| Type | strain gage transmitter, 4-wire | Signal converter and isolator, 4-wire | Programmable temperature transmitter and alarm trip | Signal isolator, converter and repeater, 2-wire |
| Input | strain gage | 0-20 mA, 4-20 mA (50 ohms); 0-50 mA, 10-50 mA (20 ohms); 0-1 V, 0-5 V, 1-5 V (1 megohm); 0-10 V (2 megohms) | RTD (23 types), T/C (9 types), mV, ohms, potentiometer | 1-5 V |
| Isolation | complete: input, output, power input | 1000 Vrms between input, output and power | Fully isolated | 1500 Vrms input to output; 500 Vrms with -RF option |
| Housing | standard, plug-in, explosion-proof (EX) | UB with U-back bracket for surface mounting | DIN-style, 35mm (EN50022) Top Hat DIN rail | DIN-style housing, 32 mm G-type (EN50035) and 35 mm Top Hat (EN50022) rail |
Request a price and lead time
SGT/XSGT 4-Wire Strain Gage Transmitter, 4-20mA Output. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What does the SGT measure?
A strain gage signal, for example from pressure transducers, load cells and stress-strain measurements, with a 4-20mA or other standard output.
Does the SGT provide gage excitation?
Yes, adjustable, regulated gage excitation is built in.
Which outputs are available?
Standard ranges are 1-5 mA, 4-20 mA, 10-50 mA or voltage.
Similar equipment from other manufacturers
![FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing](/media/no-photo-640.webp)