PIT DIN-Rail Pressure-to-Current Transmitter, 3-15 psig to 4-20mA

The PIT converts a 3-15 psig pneumatic signal into a proportional 4-20mA current for a data acquisition system, controller or recorder. It is solid state with no moving parts, accurate to ±0.2% of span, and mounts on a DIN rail.

Type
pressure-to-current (P/I) transmitter, DIN version
Model
PIT/3-15PSIG/4-20mA/12-24DC/-FA1 [DIN]
Input
3-15PSIG
Output
4-20mA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The PIT takes a pneumatic signal (3-15 psig, 0.2-1 bar, 3-27 psig and others) and accurately converts it to a proportional 4-20mA output; the family also offers 10-50mA. It is the economical way to link a pneumatic device to a data acquisition control system, controller, recorder or other electronic instrument. A typical model is PIT/3-15PSIG/4-20mA/12-24DC/-FA1 [DIN]: 3-15psig input, 4-20mA output, 12-24Vdc supply, with the -FA1 option giving a front electrical connection and a bottom pneumatic connection.

The unit is 100% solid state, so there are no moving parts to wear out or adjust. It is immune to shock, vibration and position: accuracy of ±0.2% of span holds even in unstable environments, and it can be mounted in any position without loss of performance. The self-sealing pneumatic connection lets the PIT be taken out of service without disconnecting the pneumatic line and with no air loss. The standard pneumatic connection is 1/8-inch NPT female, and 1/8-inch NPT male is optional.

Error does not exceed ±0.2% of span including independent linearity as defined in SAMA Standard PMC 20.1-1973. Repeatability is within ±0.1% of input span and resolution is ±0.05% of input span. Load capability is 600 ohms at a nominal 24Vdc, with a load effect of ±0.01% of span. With field strengths of 10 V/m at 20-500MHz, RFI/EMI effect is less than ±0.1% span change. The input is instrument air only; 150% of full scale input pressure causes no damage, the output limit is 130% of output span and output ripple is negligible. The ambient range is -1.1°C to +54°C, with an effect of less than ±2.0% of full scale.

Span is fully adjustable to 100% of output span and zero adjusts 0 to ±10% of span, using multiturn adjustments with no interaction. Weight is 340 grams. Approvals for the [DIN] version: FM Non-Incendive, Class I, Division 2, Groups A, B, C, D; CSA general (ordinary) locations; and CE conformant under EMC Directive 2014/30/EU, EN61326.

Technical specifications

Typepressure-to-current (P/I) transmitter, DIN version
ModelPIT/3-15PSIG/4-20mA/12-24DC/-FA1 [DIN]
Input3-15PSIG
Output4-20mA
Loop power12-24Vdc (12-42DC listed for supply/loop power)
Calibration capabilityerror not to exceed ±0.2% of span
Repeatability±0.1% of input span
Load capability600 ohms at nominal 24Vdc
Ambient range-1.1°C to +54°C
Pneumatic connection1/8-inch NPT female (male optional)
Weight340 grams
InstallationDIN rail or rack mount
Hazardous area certificationsNon-Incendive/Div. 2, Zone 2

Part numbers

Show all part numbers (1)

PIT/3-15PSIG/4-20mA/12-24DC/-FA1 [DIN]

How it compares with similar models

ParameterPIT DIN-Rail Pressure-to-Current Transmitter, 3-15 psig to 4-20mAPIH Field-Mount Pressure-to-Current Transmitter, 0-15 psig to 4-20mA, NEMA 4XIPT2 Current-to-Pressure (I/P) Transmitter, 4-20mA to 3-15 psig, DIN RailPIX Explosion-Proof Pressure-to-Current Transmitter, 0.2-1 bar to 4-20mA, Field Mount
Typepressure-to-current (P/I) transmitter, DIN versionfield-mount pressure-to-current (P/I) transmittercurrent-to-pressure (I/P) transmitterexplosion-proof field-mount pressure-to-current (P/I) transmitter
Input3-15PSIG0-15PSIG (also 3-15, 0-30, 3-27, 6-30 PSIG, .2-1BAR, .2-1KGCM2, 20-100KPA, 20-186KPA)4-20mA (also 4-12mA, 12-20mA)0.2-1 BAR (also 3-15 PSIG, 0.2-1 KGCM2, 6-30 PSIG)
Output4-20mA4-20mA3-15psig (also 0.2-1 Bar, 20-100kPA)4-20mA
Loop power12-24Vdc (12-42DC listed for supply/loop power)12-42Vdc—12-42Vdc (also 12-24Vdc)
Hazardous area certificationsNon-Incendive/Div. 2, Zone 2—Non-Incendive/Div. 2, Zone 2Explosion Proof, Non-Incendive/Div. 2, Zone 2

Request a price and lead time

PIT DIN-Rail Pressure-to-Current Transmitter, 3-15 psig to 4-20mA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What are the PIT input and output signals?

Pneumatic input (3-15 psig, 0.2-1 bar, 3-27 psig and others) and 4-20mA output, with 10-50mA also offered across the family.

Can the PIT be removed without disconnecting the air line?

Yes, the self-sealing pneumatic connection allows removal with no line disconnection and no air loss.

What load can the loop carry?

600 ohms at a nominal 24Vdc, with a load effect of ±0.01% of span from zero to maximum load.