EPX2 Explosion-Proof Voltage-to-Pressure (E/P) Transmitter, 1-5V to 3-15 psig, 3-Wire
The EPX2 converts a 1-5V voltage signal into a pneumatic signal so a DCS, PLC or PC can control valves, actuators and dampers. It has an explosion-proof aluminium NEMA 4X housing and accuracy under ±0.25% of span.
- Type
- explosion-proof voltage-to-pressure (E/P) transmitter, 3-wire
- Input
- 1-5 Volts
- Voltage input impedance
- 1 Mohm
- Output
- 3-15psig; 0-30psig; 6-30psig
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The EPX2 is a 3-wire (auxiliary-powered), low-voltage E/P transmitter. It accepts a 1-5V input signal from a DCS, PLC or PC-based control system and converts it to a pneumatic signal (3-15psig, 0.2-1Bar, 20-100kPa and others) for precise, proportional control of valves, actuators and other pneumatically controlled devices. Voltage input impedance is 1 megohm.
The extruded aluminium housing is explosion-proof and waterproof, rated NEMA 4X, and the unit is made for extended duty in harsh field environments such as remote natural gas well heads. An optional coalescing filter/regulator combines an air filter, a miniature supply line regulator and a gauge reading in both psi and bars. With the -NG1 or -NG2 option the EPX2 can use natural gas as its pneumatic supply (sweet gas with up to 20ppm of H2S), so it can be installed at remote compressor sites where running a clean air supply is impossible or too expensive.
There are 22 direct and reverse output ranges, including 3-15psig, 0-30psig and 6-30psig. Accuracy is under ±0.25% of span including linearity, hysteresis and repeatability, with six-month stability. Output reaches 5SCFM while consumption is as low as 0.08SCFM. The low power requirement of 3mA at 12Vdc allows a battery or solar panel supply, and the power supply range is 9-30Vdc. Supply pressure changes between 20 and 40psig have a negligible effect on accuracy. A larger orifice with an easily replaceable internal filter protects against clogging.
Step response is under 0.2 seconds into a 100ml load (6 in3) from 10% to 90% of span. Air capacity is at least 5.0SCFM and relief capacity at least 2.5SCFM. The air supply must be instrument air only, 20-40psig and 5psig above the maximum output. The ambient operating and storage range is -40°C to +85°C. Certification: CE conformant under EMC Directive 89/336/EEC, EN 61326.
Technical specifications
| Type | explosion-proof voltage-to-pressure (E/P) transmitter, 3-wire |
|---|---|
| Input | 1-5 Volts |
| Voltage input impedance | 1 Mohm |
| Output | 3-15psig; 0-30psig; 6-30psig |
| Power supply | 9-30Vdc |
| Accuracy | <±0.25% of span |
| Step response | <0.2 seconds into 100ml (6 in3), 10% to 90% of span |
| Air capacity | 5.0SCFM minimum |
| Relief capacity | 2.5SCFM minimum |
| Air supply | instrument air only, 20-40psig |
| Operating and storage range | -40°C to +85°C |
| Housing | extruded aluminium, explosion-proof, NEMA 4X |
Part numbers
Show all part numbers (1)
EPX2
How it compares with similar models
| Parameter | EPX2 Explosion-Proof Voltage-to-Pressure (E/P) Transmitter, 1-5V to 3-15 psig, 3-Wire | IPT2 Current-to-Pressure (I/P) Transmitter, 4-20mA to 3-15 psig, DIN Rail | IPX2 Explosion-Proof and Intrinsically-Safe Current-to-Pressure (I/P) Transmitter, Field Mount | SIX 1-5V/4-20mA 2-Wire Signal Isolator and Converter, 1500 Vrms Isolation |
|---|---|---|---|---|
| Type | explosion-proof voltage-to-pressure (E/P) transmitter, 3-wire | current-to-pressure (I/P) transmitter | field-mount current-to-pressure (I/P) transmitter, 2-wire | Signal isolator, converter and repeater, 2-wire |
| Input | 1-5 Volts | 4-20mA (also 4-12mA, 12-20mA) | 4-12mA | 1-5 V |
| Output | 3-15psig; 0-30psig; 6-30psig | 3-15psig (also 0.2-1 Bar, 20-100kPA) | 3-15PSIG | 4-20 mA |
| Accuracy | <±0.25% of span | <±0.25% of span | <±0.25% of span | +/-0.1 % of span |
| Step response | <0.2 seconds into 100ml (6 in3), 10% to 90% of span | <0.2 seconds into 100ml (6 in3), 10% to 90% of span | <0.25 seconds into 100ml (6 in3), 10% to 90% of span | — |
| Air capacity | 5.0SCFM minimum | minimum 2.0 SCFM | 5.0SCFM minimum | — |
Request a price and lead time
EPX2 Explosion-Proof Voltage-to-Pressure (E/P) Transmitter, 1-5V to 3-15 psig, 3-Wire. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What input does the EPX2 take?
A 1-5V signal with 1 megohm input impedance, and a 9-30Vdc supply.
Can the EPX2 run on natural gas?
Yes, with the -NG1 or -NG2 option, on gas as clean as instrument air with H2S not exceeding 20ppm.
Can it run from a battery or solar panel?
Yes, the 3mA at 12Vdc requirement allows a battery or solar panel supply.
Similar equipment from other manufacturers




![FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing](/media/no-photo-640.webp)