PIH Field-Mount Pressure-to-Current Transmitter, 0-15 psig to 4-20mA, NEMA 4X
The PIH converts a pneumatic signal into a proportional 4-20mA current for a data acquisition system, controller or recorder. It has an aluminium NEMA 4X/IP64 housing, a 600 ohm load capability at 24Vdc and ±0.2% of span accuracy.
- Type
- field-mount pressure-to-current (P/I) transmitter
- Input
- 0-15PSIG (also 3-15, 0-30, 3-27, 6-30 PSIG, .2-1BAR, .2-1KGCM2, 20-100KPA, 20-186KPA)
- Output
- 4-20mA
- Loop power
- 12-42Vdc
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The PIH is a field-mounted pressure-to-current transmitter for processes that need a rugged instrument to link a pneumatic device with a data acquisition/control system, controller, recorder or other electronic instrument. It accepts most pneumatic signals and accurately converts them to a proportional 4-20mA output. The typical model is PIH/0-15PSIG/4-20mA/12-42DC [WDNS]: 0-15psig input, 4-20mA output and a 12-42Vdc loop supply.
Inputs available are 0-15, 3-15, 0-30, 3-27 and 6-30 psig, 0.2-1 bar, 0.2-1 kgcm2, 20-100 kPa and 20-186 kPa. The -RO option gives a reverse output, so that the output current decreases as the input increases. The body is aluminium with a black PBT polyester cover, with NPT pneumatic ports and a ½-inch NPT female electrical entry port. The housing is watertight, dust-tight and resistant to corrosion and chemicals, in a NEMA 4X/IP64 field-mount enclosure. A metal cover weighs 808 grams and a polyester cover 623.5 grams. The metal casing gives strength without the added expense of an explosion-proof enclosure.
The PIH is immune to shock, vibration and mounting position. Running electrical wiring in place of fragile pneumatic tubing from remote pneumatic devices lowers installation costs. Calibration error is within ±0.2% of span including independent linearity as defined in SAMA PMC 20.1-1973, repeatability is within ±0.1% of input span and resolution is ±0.05%. Load capability is 600 ohms at a nominal 24Vdc. Input pressure of 150% of full scale causes no damage, and the output limit is 130% of output span. The ambient range is -1°C to +54°C with an effect of less than ±2.0% of full scale. Span adjusts to 100% of output span and zero adjusts 0 to ±10%. The unit is CE conformant under EMC Directive 2014/30/EU, EN 61326.
Technical specifications
| Type | field-mount pressure-to-current (P/I) transmitter |
|---|---|
| Input | 0-15PSIG (also 3-15, 0-30, 3-27, 6-30 PSIG, .2-1BAR, .2-1KGCM2, 20-100KPA, 20-186KPA) |
| Output | 4-20mA |
| Loop power | 12-42Vdc |
| Calibration capability | ±0.2% of span including linearity |
| Repeatability | ±0.1% of input span |
| Load capability | 600 ohms at nominal 24Vdc |
| Ambient range | -1°C to +54°C |
| Housing | aluminium body, PBT polyester cover, NEMA 4X/IP64 |
| Connections | NPT pneumatic, ½-inch NPT electrical |
| Weight | 808 grams (metal cover); 623.5 grams (polyester cover) |
| Options | -RO (reverse output) |
Part numbers
Show all part numbers (1)
PIH/0-15PSIG/4-20mA/12-42DC [WDNS]
How it compares with similar models
| Parameter | PIH Field-Mount Pressure-to-Current Transmitter, 0-15 psig to 4-20mA, NEMA 4X | PIT DIN-Rail Pressure-to-Current Transmitter, 3-15 psig to 4-20mA | PIX Explosion-Proof Pressure-to-Current Transmitter, 0.2-1 bar to 4-20mA, Field Mount | IPH2 NEMA 4X Current-to-Pressure (I/P) Transmitter, 4-20mA to 3-15 psig, Field Mount |
|---|---|---|---|---|
| Type | field-mount pressure-to-current (P/I) transmitter | pressure-to-current (P/I) transmitter, DIN version | explosion-proof field-mount pressure-to-current (P/I) transmitter | field-mount current-to-pressure (I/P) transmitter |
| Input | 0-15PSIG (also 3-15, 0-30, 3-27, 6-30 PSIG, .2-1BAR, .2-1KGCM2, 20-100KPA, 20-186KPA) | 3-15PSIG | 0.2-1 BAR (also 3-15 PSIG, 0.2-1 KGCM2, 6-30 PSIG) | 4-20mA (also 4-12mA, 12-20mA) |
| Output | 4-20mA | 4-20mA | 4-20mA | 3-15PSIG (also 6-30PSIG, 3-27PSIG, 0.2-1BAR, 20-100KPA) |
| Loop power | 12-42Vdc | 12-24Vdc (12-42DC listed for supply/loop power) | 12-42Vdc (also 12-24Vdc) | — |
| Housing | aluminium body, PBT polyester cover, NEMA 4X/IP64 | — | extruded aluminium, explosion-proof, NPT conduit entry | aluminium body and cover, NPT entry ports |
Request a price and lead time
PIH Field-Mount Pressure-to-Current Transmitter, 0-15 psig to 4-20mA, NEMA 4X. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which input ranges does the PIH have?
0-15, 3-15, 0-30, 3-27 and 6-30 psig, 0.2-1 bar, 0.2-1 kgcm2, 20-100 kPa and 20-186 kPa, with a 4-20mA output.
Is a reverse output available?
Yes, the -RO option makes the output decrease as the input increases.
What loop load is allowed?
600 ohms at a nominal 24Vdc, with a load effect of ±0.01% of span.