IPX2 Explosion-Proof and Intrinsically-Safe Current-to-Pressure (I/P) Transmitter, Field Mount
The IPX2 converts a current signal into a pneumatic signal so a DCS, PLC or PC can control an actuator, valve or damper drive. It is 2-wire, loop-powered, in an extruded aluminium NEMA 4X/IP66 explosion-proof housing, with accuracy under ±0.25% of span.
- Type
- field-mount current-to-pressure (I/P) transmitter, 2-wire
- Model
- IPX2/4-12mA/3-15PSIG/20PSI [EXI]
- Input
- 4-12mA
- Output
- 3-15PSIG
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The IPX2 is a field-mounted current-to-pressure transmitter. It accepts a current signal from a DCS, PLC or PC-based control system and converts it to a proportional pneumatic signal, such as 3-15psig, 0.2-1bar or 20-100kPa, to control a pneumatic actuator, valve or damper drive. A typical model is IPX2/4-12mA/3-15PSIG/20PSI [EXI]: 4-12mA input, 3-15psig output, 20psi supply, with air as the supply and output medium.
The transmitter is 2-wire and loop-powered. The extruded aluminium housing is built for extended duty in harsh field environments: it is Type 3X/4X and IP66 rated, protects against water and dust, and resists corrosion and chemicals. The housing is explosion-proof, with a ½-inch NPT female threaded entry port for conduit. Certifications are intrinsically-safe, explosion-proof, flameproof and non-incendive (Div. 2, Zone 2). Versions on air and on natural gas (options -NG1 or -NG2, sweet gas with up to 20ppm H2S) are explosion-proof, and the natural gas versions meet the US EPA requirement for the oil and gas industry, with a maximum gas bleed rate below 6SCFH at a 3-15psi output and 17psi gas supply.
Inputs are 4-20mA or split range, with 22 direct and reverse output ranges, and reverse output is switch selectable on the IPX2. Accuracy is under ±0.25% of span including linearity, hysteresis and repeatability, with six-month stability. Air consumption is as low as 0.08SCFM and output reaches 300SCFH. Supply pressure changes between 20 and 35psig have a negligible effect on accuracy. Step response is under 0.25 seconds into a 100ml load (6 in3), air capacity is at least 5.0SCFM (20psig supply, 0psig output) and voltage drop is 5V at most.
The electronics module can be removed: if a liquid slug gets into the air or gas supply, taking the module out lets the accumulated liquid drain more effectively. A larger orifice with an easily replaceable internal filter protects against clogging by debris. An optional coalescing filter/regulator combines an air filter, a miniature supply line regulator and a gauge reading in both psig and bar. Special circuit and enclosure designs protect against radio frequency and electromagnetic interference.
Technical specifications
| Type | field-mount current-to-pressure (I/P) transmitter, 2-wire |
|---|---|
| Model | IPX2/4-12mA/3-15PSIG/20PSI [EXI] |
| Input | 4-12mA |
| Output | 3-15PSIG |
| Supply pressure | 20PSI, air |
| Accuracy | <±0.25% of span |
| Step response | <0.25 seconds into 100ml (6 in3), 10% to 90% of span |
| Air capacity | 5.0SCFM minimum |
| Voltage drop | 5V maximum |
| Housing | explosion-proof aluminium, ½-inch NPT entry, NEMA 4X/IP66 |
| Installation | field mount |
| Hazardous area certifications | Intrinsically-Safe, Explosion Proof, Flameproof, Non-Incendive/Div. 2, Zone 2 |
| RoHS | compliant |
Part numbers
Show all part numbers (1)
IPX2/4-12mA/3-15PSIG/20PSI [EXI]
How it compares with similar models
| Parameter | IPX2 Explosion-Proof and Intrinsically-Safe Current-to-Pressure (I/P) Transmitter, Field Mount | IPH2 NEMA 4X Current-to-Pressure (I/P) Transmitter, 4-20mA to 3-15 psig, Field Mount | PIX Explosion-Proof Pressure-to-Current Transmitter, 0.2-1 bar to 4-20mA, Field Mount | EPX2 Explosion-Proof Voltage-to-Pressure (E/P) Transmitter, 1-5V to 3-15 psig, 3-Wire |
|---|---|---|---|---|
| Type | field-mount current-to-pressure (I/P) transmitter, 2-wire | field-mount current-to-pressure (I/P) transmitter | explosion-proof field-mount pressure-to-current (P/I) transmitter | explosion-proof voltage-to-pressure (E/P) transmitter, 3-wire |
| Input | 4-12mA | 4-20mA (also 4-12mA, 12-20mA) | 0.2-1 BAR (also 3-15 PSIG, 0.2-1 KGCM2, 6-30 PSIG) | 1-5 Volts |
| Output | 3-15PSIG | 3-15PSIG (also 6-30PSIG, 3-27PSIG, 0.2-1BAR, 20-100KPA) | 4-20mA | 3-15psig; 0-30psig; 6-30psig |
| Housing | explosion-proof aluminium, ½-inch NPT entry, NEMA 4X/IP66 | aluminium body and cover, NPT entry ports | extruded aluminium, explosion-proof, NPT conduit entry | extruded aluminium, explosion-proof, NEMA 4X |
| Hazardous area certifications | Intrinsically-Safe, Explosion Proof, Flameproof, Non-Incendive/Div. 2, Zone 2 | Intrinsically-Safe, Non-Incendive/Div. 2, Zone 2 | Explosion Proof, Non-Incendive/Div. 2, Zone 2 | — |
Request a price and lead time
IPX2 Explosion-Proof and Intrinsically-Safe Current-to-Pressure (I/P) Transmitter, Field Mount. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the IPX2 run on natural gas?
Yes, with the -NG1 or -NG2 option, on sweet gas with up to 20ppm H2S; maximum bleed rate is below 6SCFH at a 3-15psi output and 17psi gas supply.
What is the voltage drop across the unit?
5V maximum; the unit is 2-wire and loop-powered.
Can the output direction be reversed?
Yes, reverse output is switch selectable on the IPX2, which has 22 direct and reverse output ranges.
Similar equipment from other manufacturers