International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

IPX2 Explosion-Proof and Intrinsically-Safe Current-to-Pressure (I/P) Transmitter, Field Mount

The IPX2 converts a current signal into a pneumatic signal so a DCS, PLC or PC can control an actuator, valve or damper drive. It is 2-wire, loop-powered, in an extruded aluminium NEMA 4X/IP66 explosion-proof housing, with accuracy under ±0.25% of span.

Type
field-mount current-to-pressure (I/P) transmitter, 2-wire
Model
IPX2/4-12mA/3-15PSIG/20PSI [EXI]
Input
4-12mA
Output
3-15PSIG

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The IPX2 is a field-mounted current-to-pressure transmitter. It accepts a current signal from a DCS, PLC or PC-based control system and converts it to a proportional pneumatic signal, such as 3-15psig, 0.2-1bar or 20-100kPa, to control a pneumatic actuator, valve or damper drive. A typical model is IPX2/4-12mA/3-15PSIG/20PSI [EXI]: 4-12mA input, 3-15psig output, 20psi supply, with air as the supply and output medium.

The transmitter is 2-wire and loop-powered. The extruded aluminium housing is built for extended duty in harsh field environments: it is Type 3X/4X and IP66 rated, protects against water and dust, and resists corrosion and chemicals. The housing is explosion-proof, with a ½-inch NPT female threaded entry port for conduit. Certifications are intrinsically-safe, explosion-proof, flameproof and non-incendive (Div. 2, Zone 2). Versions on air and on natural gas (options -NG1 or -NG2, sweet gas with up to 20ppm H2S) are explosion-proof, and the natural gas versions meet the US EPA requirement for the oil and gas industry, with a maximum gas bleed rate below 6SCFH at a 3-15psi output and 17psi gas supply.

Inputs are 4-20mA or split range, with 22 direct and reverse output ranges, and reverse output is switch selectable on the IPX2. Accuracy is under ±0.25% of span including linearity, hysteresis and repeatability, with six-month stability. Air consumption is as low as 0.08SCFM and output reaches 300SCFH. Supply pressure changes between 20 and 35psig have a negligible effect on accuracy. Step response is under 0.25 seconds into a 100ml load (6 in3), air capacity is at least 5.0SCFM (20psig supply, 0psig output) and voltage drop is 5V at most.

The electronics module can be removed: if a liquid slug gets into the air or gas supply, taking the module out lets the accumulated liquid drain more effectively. A larger orifice with an easily replaceable internal filter protects against clogging by debris. An optional coalescing filter/regulator combines an air filter, a miniature supply line regulator and a gauge reading in both psig and bar. Special circuit and enclosure designs protect against radio frequency and electromagnetic interference.

Technical specifications

Typefield-mount current-to-pressure (I/P) transmitter, 2-wire
ModelIPX2/4-12mA/3-15PSIG/20PSI [EXI]
Input4-12mA
Output3-15PSIG
Supply pressure20PSI, air
Accuracy<±0.25% of span
Step response<0.25 seconds into 100ml (6 in3), 10% to 90% of span
Air capacity5.0SCFM minimum
Voltage drop5V maximum
Housingexplosion-proof aluminium, ½-inch NPT entry, NEMA 4X/IP66
Installationfield mount
Hazardous area certificationsIntrinsically-Safe, Explosion Proof, Flameproof, Non-Incendive/Div. 2, Zone 2
RoHScompliant

Part numbers

Show all part numbers (1)

IPX2/4-12mA/3-15PSIG/20PSI [EXI]

How it compares with similar models

ParameterIPX2 Explosion-Proof and Intrinsically-Safe Current-to-Pressure (I/P) Transmitter, Field MountIPH2 NEMA 4X Current-to-Pressure (I/P) Transmitter, 4-20mA to 3-15 psig, Field MountPIX Explosion-Proof Pressure-to-Current Transmitter, 0.2-1 bar to 4-20mA, Field MountEPX2 Explosion-Proof Voltage-to-Pressure (E/P) Transmitter, 1-5V to 3-15 psig, 3-Wire
Typefield-mount current-to-pressure (I/P) transmitter, 2-wirefield-mount current-to-pressure (I/P) transmitterexplosion-proof field-mount pressure-to-current (P/I) transmitterexplosion-proof voltage-to-pressure (E/P) transmitter, 3-wire
Input4-12mA4-20mA (also 4-12mA, 12-20mA)0.2-1 BAR (also 3-15 PSIG, 0.2-1 KGCM2, 6-30 PSIG)1-5 Volts
Output3-15PSIG3-15PSIG (also 6-30PSIG, 3-27PSIG, 0.2-1BAR, 20-100KPA)4-20mA3-15psig; 0-30psig; 6-30psig
Housingexplosion-proof aluminium, ½-inch NPT entry, NEMA 4X/IP66aluminium body and cover, NPT entry portsextruded aluminium, explosion-proof, NPT conduit entryextruded aluminium, explosion-proof, NEMA 4X
Hazardous area certificationsIntrinsically-Safe, Explosion Proof, Flameproof, Non-Incendive/Div. 2, Zone 2Intrinsically-Safe, Non-Incendive/Div. 2, Zone 2Explosion Proof, Non-Incendive/Div. 2, Zone 2—

Request a price and lead time

IPX2 Explosion-Proof and Intrinsically-Safe Current-to-Pressure (I/P) Transmitter, Field Mount. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can the IPX2 run on natural gas?

Yes, with the -NG1 or -NG2 option, on sweet gas with up to 20ppm H2S; maximum bleed rate is below 6SCFH at a 3-15psi output and 17psi gas supply.

What is the voltage drop across the unit?

5V maximum; the unit is 2-wire and loop-powered.

Can the output direction be reversed?

Yes, reverse output is switch selectable on the IPX2, which has 22 direct and reverse output ranges.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides