ARB 4-Wire Adjustable Ramp Buffer, Independently Adjustable Rise and Fall Rates
The ARB takes a current, voltage or contact closure input and ramps its output smoothly, at an adjustable rate up or down, to the value for the new input. It offers six ramp ranges from 100 milliseconds to 60 minutes.
- Type
- Adjustable ramp buffer, 4-wire
- Input
- Current, voltage or contact closure
- Ramp ranges
- 100 milliseconds (fixed); 2-10 seconds; 10-50 seconds; 50-120 seconds; 2-10 minutes; 10-60 minutes
- Adjustment
- Increase and decrease times independent within the selected range
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ARB accepts a current, voltage or contact closure input. When the input changes, it generates an analog output that ramps smoothly, at an individually adjustable rate up or down, to the value matching the new input. It suits any process that needs an adjustable rate-control signal.
Typical jobs are limiting or presetting the rate of valve actuation and smoothing signals that contain unwanted high-frequency components. The ARB output can feed integrators, alarms and digital displays, and can drive recorders and digital multiplexers.
There are six standard ramp ranges: 100 milliseconds (fixed), 2-10 seconds, 10-50 seconds, 50-120 seconds, 2-10 minutes and 10-60 minutes. Within the chosen range the increasing and decreasing ramp times are adjusted independently. A clock drives a staircase waveform of equal steps to produce a precise ramp. A contact closure input can start soak cycles or interface a relay with a modulating valve. An external clock generator (the STM module) extends ramp times up to 48 days.
Calibration capability is +/-1 part in 1000, ripple is below 0.2 % of maximum signal (10 mV peak-to-peak on a 5 V signal) and load effect is +/-0.01 % of span. Output is limited to 150 % of the maximum range value. Ambient range is 0 to 70 degrees C. Front-panel multiturn potentiometers adjust ZERO (+/-10 %), SPAN (+/-20 %) and the increase and decrease rates. The unit complies with ISA S50.1, Section 5.
The standard housing is a corrosion-resistant aluminium case approved by CSA, with a U-Back bracket that fits a 3 x 7-1/2 inch space. A plug-in housing serves high-density surface or card-rack mounting, and explosion-proof, oil-tight and watertight enclosures to NEMA standards are also offered. The -RF option adds a filter terminal assembly that keeps radio frequency interference out.
Technical specifications
| Type | Adjustable ramp buffer, 4-wire |
|---|---|
| Input | Current, voltage or contact closure |
| Ramp ranges | 100 milliseconds (fixed); 2-10 seconds; 10-50 seconds; 50-120 seconds; 2-10 minutes; 10-60 minutes |
| Adjustment | Increase and decrease times independent within the selected range |
| External clock generator | Ramp times up to 48 days |
| Calibration capability | +/-1 part in 1000 |
| Ripple | Below 0.2 % of maximum signal, 10 mV peak-to-peak on 5 V |
| Load effect | +/-0.01 % of span |
| Output limit | 150 % of maximum range value |
| Ambient range | 0 to 70 degrees C |
| Adjustments | ZERO +/-10 %, SPAN +/-20 %, increase and decrease rates |
| Housing | CSA-approved aluminium case with U-Back bracket; plug-in; explosion-proof, oil-tight and watertight enclosures |
| Compliance | ISA S50.1, Section 5 |
Part numbers
Show all part numbers (1)
ARB
How it compares with similar models
| Parameter | ARB 4-Wire Adjustable Ramp Buffer, Independently Adjustable Rise and Fall Rates | ADB 4-Wire Analog Divider Module, Current or Voltage Output Proportional to the Quotient of Two Inputs | ASM 4-Wire Adder Subtractor Module for Two to Four Analog Inputs | FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing |
|---|---|---|---|---|
| Type | Adjustable ramp buffer, 4-wire | Analog divider module, 4-wire | Adder-subtractor module, 4-wire | Signal converter and isolator, 4-wire |
| Calibration capability | +/-1 part in 1000 | +/-0.25 % of span | +/-0.5 % of span | — |
| Ripple | Below 0.2 % of maximum signal, 10 mV peak-to-peak on 5 V | Below 0.25 % of maximum signal, 10 mV peak-to-peak on 5 V | 10 mV peak-to-peak | — |
| Ambient range | 0 to 70 degrees C | -29 to +82 degrees C | -29 to +82 degrees C | -30 to +82 degrees C |
Request a price and lead time
ARB 4-Wire Adjustable Ramp Buffer, Independently Adjustable Rise and Fall Rates. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What ramp ranges does the ARB offer?
100 milliseconds (fixed), 2-10 seconds, 10-50 seconds, 50-120 seconds, 2-10 minutes and 10-60 minutes.
Can rise and fall times differ?
Yes. The increasing and decreasing ramp times are adjusted independently within the selected range.
How long can a ramp last?
With an external clock generator, ramp times extend up to 48 days.
Similar equipment from other manufacturers


![FCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing](/media/no-photo-640.webp)