ARB 4-Wire Adjustable Ramp Buffer, Independently Adjustable Rise and Fall Rates

The ARB takes a current, voltage or contact closure input and ramps its output smoothly, at an adjustable rate up or down, to the value for the new input. It offers six ramp ranges from 100 milliseconds to 60 minutes.

Type
Adjustable ramp buffer, 4-wire
Input
Current, voltage or contact closure
Ramp ranges
100 milliseconds (fixed); 2-10 seconds; 10-50 seconds; 50-120 seconds; 2-10 minutes; 10-60 minutes
Adjustment
Increase and decrease times independent within the selected range

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The ARB accepts a current, voltage or contact closure input. When the input changes, it generates an analog output that ramps smoothly, at an individually adjustable rate up or down, to the value matching the new input. It suits any process that needs an adjustable rate-control signal.

Typical jobs are limiting or presetting the rate of valve actuation and smoothing signals that contain unwanted high-frequency components. The ARB output can feed integrators, alarms and digital displays, and can drive recorders and digital multiplexers.

There are six standard ramp ranges: 100 milliseconds (fixed), 2-10 seconds, 10-50 seconds, 50-120 seconds, 2-10 minutes and 10-60 minutes. Within the chosen range the increasing and decreasing ramp times are adjusted independently. A clock drives a staircase waveform of equal steps to produce a precise ramp. A contact closure input can start soak cycles or interface a relay with a modulating valve. An external clock generator (the STM module) extends ramp times up to 48 days.

Calibration capability is +/-1 part in 1000, ripple is below 0.2 % of maximum signal (10 mV peak-to-peak on a 5 V signal) and load effect is +/-0.01 % of span. Output is limited to 150 % of the maximum range value. Ambient range is 0 to 70 degrees C. Front-panel multiturn potentiometers adjust ZERO (+/-10 %), SPAN (+/-20 %) and the increase and decrease rates. The unit complies with ISA S50.1, Section 5.

The standard housing is a corrosion-resistant aluminium case approved by CSA, with a U-Back bracket that fits a 3 x 7-1/2 inch space. A plug-in housing serves high-density surface or card-rack mounting, and explosion-proof, oil-tight and watertight enclosures to NEMA standards are also offered. The -RF option adds a filter terminal assembly that keeps radio frequency interference out.

Technical specifications

TypeAdjustable ramp buffer, 4-wire
InputCurrent, voltage or contact closure
Ramp ranges100 milliseconds (fixed); 2-10 seconds; 10-50 seconds; 50-120 seconds; 2-10 minutes; 10-60 minutes
AdjustmentIncrease and decrease times independent within the selected range
External clock generatorRamp times up to 48 days
Calibration capability+/-1 part in 1000
RippleBelow 0.2 % of maximum signal, 10 mV peak-to-peak on 5 V
Load effect+/-0.01 % of span
Output limit150 % of maximum range value
Ambient range0 to 70 degrees C
AdjustmentsZERO +/-10 %, SPAN +/-20 %, increase and decrease rates
HousingCSA-approved aluminium case with U-Back bracket; plug-in; explosion-proof, oil-tight and watertight enclosures
ComplianceISA S50.1, Section 5

Part numbers

Show all part numbers (1)

ARB

How it compares with similar models

ParameterARB 4-Wire Adjustable Ramp Buffer, Independently Adjustable Rise and Fall RatesADB 4-Wire Analog Divider Module, Current or Voltage Output Proportional to the Quotient of Two InputsASM 4-Wire Adder Subtractor Module for Two to Four Analog InputsFCT [UB] 4-Wire Signal Converter and Isolator with Universal Power Input, Surface-Mount Housing
TypeAdjustable ramp buffer, 4-wireAnalog divider module, 4-wireAdder-subtractor module, 4-wireSignal converter and isolator, 4-wire
Calibration capability+/-1 part in 1000+/-0.25 % of span+/-0.5 % of span—
RippleBelow 0.2 % of maximum signal, 10 mV peak-to-peak on 5 VBelow 0.25 % of maximum signal, 10 mV peak-to-peak on 5 V10 mV peak-to-peak—
Ambient range0 to 70 degrees C-29 to +82 degrees C-29 to +82 degrees C-30 to +82 degrees C

Request a price and lead time

ARB 4-Wire Adjustable Ramp Buffer, Independently Adjustable Rise and Fall Rates. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What ramp ranges does the ARB offer?

100 milliseconds (fixed), 2-10 seconds, 10-50 seconds, 50-120 seconds, 2-10 minutes and 10-60 minutes.

Can rise and fall times differ?

Yes. The increasing and decreasing ramp times are adjusted independently within the selected range.

How long can a ramp last?

With an external clock generator, ramp times extend up to 48 days.