ADB 4-Wire Analog Divider Module, Current or Voltage Output Proportional to the Quotient of Two Inputs
The ADB divides one process input, in percent, by another and, with optional -KO scaling, delivers the quotient as a current or voltage. Calibration capability is +/-0.25 % of span, ripple is 10 mV peak-to-peak at most, and housings range from STD to EX.
- Type
- Analog divider module, 4-wire
- Current input
- 1-5 mA into 200 ohms; 4-20 mA into 50 ohms; 10-50 mA into 20 ohms
- Voltage input
- 0-5 V, 1-5 V standard, 0.5 megohm; others optional
- Current output
- 1-5 mA into 0-4800 ohms; 4-20 mA into 0-1200 ohms; 10-50 mA into 0-480 ohms
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ADB divides one process input, expressed as a percentage, by a second. With optional scaling (-KO) it produces a current or voltage output that represents the quotient as a percentage. It is particularly useful in calculations needed to obtain volumetric flow.
A typical task is differential-pressure flow measurement compensated for absolute static pressure and temperature. The ADB then works with a multiplier module and a square root extracting module, and the normalised flow can be totalised by a linear integrating totaliser at the end of the chain.
Current inputs are 1-5 mA into 200 ohms, 4-20 mA into 50 ohms and 10-50 mA into 20 ohms. Voltage inputs are 0-5 V and 1-5 V as standard at 0.5 megohm; other voltages are optional. Current outputs are 1-5 mA into 0-4800 ohms, 4-20 mA into 0-1200 ohms and 10-50 mA into 0-480 ohms, and the voltage output is 1-5 Vdc into 20K ohms minimum. Output is limited to 150 % of the maximum range value.
Calibration capability is +/-0.25 % of span, ripple is below 0.25 % of maximum signal (10 mV peak-to-peak on a 5 V signal), load effect is +/-0.01 % of span and frequency response is 50 Hz at the 3 dB point. Ambient range is -29 to +82 degrees C. Front-panel multiturn potentiometers set SPAN, ZERO and the A and B input zero. Power input is 24 Vdc, 45 Vdc, or 117, 220 or 240 Vac at 50/60 Hz, +/-10 %, 5 watts nominal. Weight is approximately 908 g.
Options: -TX two-wire transmitter excitation of 30 Vdc at 25 mA; -KO, -KA and -KB internal K factors set at the factory; -RF RFI/EMI protection. Housings: STD, AB, CP, D2, EX explosion-proof enclosure, WT (NEMA 4), OT (NEMA 12), PC, PM and GP (NEMA 1). The module complies with ISA S50.1, Section 5 and is CSA certified.
Technical specifications
| Type | Analog divider module, 4-wire |
|---|---|
| Current input | 1-5 mA into 200 ohms; 4-20 mA into 50 ohms; 10-50 mA into 20 ohms |
| Voltage input | 0-5 V, 1-5 V standard, 0.5 megohm; others optional |
| Current output | 1-5 mA into 0-4800 ohms; 4-20 mA into 0-1200 ohms; 10-50 mA into 0-480 ohms |
| Voltage output | 1-5 Vdc into 20K ohms minimum |
| Calibration capability | +/-0.25 % of span |
| Ripple | Below 0.25 % of maximum signal, 10 mV peak-to-peak on 5 V |
| Frequency response | 50 Hz at 3 dB point |
| Ambient range | -29 to +82 degrees C |
| Power | 24 Vdc, 45 Vdc, 117 Vac, 220 Vac, 240 Vac, 50/60 Hz, +/-10 %; 5 watts |
| Options | -TX, -KO, -KA, -KB, -RF |
| Housings | STD, AB, CP, D2, EX, WT, OT, PC, PM, GP |
| Weight | Approximately 908 g |
| Compliance | ISA S50.1, Section 5; CSA |
Part numbers
Show all part numbers (1)
ADB
How it compares with similar models
| Parameter | ADB 4-Wire Analog Divider Module, Current or Voltage Output Proportional to the Quotient of Two Inputs | ASM 4-Wire Adder Subtractor Module for Two to Four Analog Inputs | ACT 4-Wire AC Current and Voltage Transmitter with Input-Output Isolation | ACX 2-Wire AC Current Isolator and Transmitter, 4-20 mA Output, 12-42 V DC Loop Power |
|---|---|---|---|---|
| Type | Analog divider module, 4-wire | Adder-subtractor module, 4-wire | AC current and voltage transmitter, 4-wire | AC current and voltage isolator and transmitter, 2-wire |
| Current input | 1-5 mA into 200 ohms; 4-20 mA into 50 ohms; 10-50 mA into 20 ohms | 1-5 mA into 1000 ohms; 4-20 mA into 250 ohms; 10-50 mA into 100 ohms | 0-1, 0-2, 0-3, 0-4 or 0-5 A AC, 0.1 ohm impedance | 0-1, 0-2, 0-3, 0-4 or 0-5 A AC, 0.1 ohm impedance |
| Voltage input | 0-5 V, 1-5 V standard, 0.5 megohm; others optional | 0-5 V, 1-5 V, 250,000 ohms minimum | Up to 0-150 VAC, 1000 ohms per volt | 0-0.5, 0-1.5, 0-5, 0-10, 0-25, 0-50, 0-120 or 0-150 VAC, 100 ohms per volt |
| Current output | 1-5 mA into 0-4800 ohms; 4-20 mA into 0-1200 ohms; 10-50 mA into 0-480 ohms | 1-5 mA into 0-4800 ohms; 4-20 mA into 0-1200 ohms; 10-50 mA into 0-480 ohms | 1-5 mA into 0-4800 ohms; 4-20 mA into 0-1200 ohms | — |
| Calibration capability | +/-0.25 % of span | +/-0.5 % of span | +/-0.5 % of span | +/-0.2 % of span; +/-0.5 % at 0-10 Vac and lower |
| Ripple | Below 0.25 % of maximum signal, 10 mV peak-to-peak on 5 V | 10 mV peak-to-peak | Below 10 mV peak-to-peak | 10 mV peak-to-peak maximum |
Request a price and lead time
ADB 4-Wire Analog Divider Module, Current or Voltage Output Proportional to the Quotient of Two Inputs. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What does the ADB calculate?
The quotient of one input divided by another, in percent, delivered as a current or voltage output.
Where is the ADB used in flow measurement?
In volumetric flow computation with static pressure and temperature compensation, working with multiplier and square root extracting modules.
What does the -TX option provide?
Two-wire transmitter excitation of 30 Vdc at 25 mA, enough to power one 4-20 mA field transmitter.