International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

SGen-100A / SGen-1000A — air-cooled turbo generators 25–370 MVA

SGen-100A and SGen-1000A are series of air-cooled synchronous turbo generators of 25–370 MVA for steam and gas turbines. SGen-100A is made in two- and four-pole versions, and SGen-1000A is a two-pole machine of 180–370 MVA for large power stations. Efficiency reaches 98.9 %, and no hydrogen system is needed at the plant.

Apparent power
SGen-100A: 25–370 MVA; SGen-1000A: 180–370 MVA
Stator voltage
SGen-100A: 6.3–15.75 kV; SGen-1000A: 10.5–20 kV
Frequency
50 Hz (SGen5) / 60 Hz (SGen6)
Number of poles
2 (SGen-100A also 4-pole)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The SGen-100A series covers an apparent power of 25–370 MVA at a stator voltage of 6.3–15.75 kV. It is made two-pole and four-pole. SGen-1000A has only two poles, is rated for 180–370 MVA and 10.5–20 kV, and is aimed at large utility power stations. Both series are made for 50 Hz under the designation SGen5 and for 60 Hz under SGen6, with a rated power factor of 0.80 and 0.85 respectively.

Both series are optimized for industrial use and continuous operation in harsh conditions. Cooling is fully by air. Direct radial air flow cools the rotor winding, so the plant needs no hydrogen systems, gas handling or the related safety measures. The customer chooses the excitation, brushless or static.

The stator winding is insulated with the MICALASTIC® system using global vacuum pressure impregnation (GVPI) technology, thermal class F. Since 1988 more than 1700 stator windings of turbo generators with a total rating above 240 000 MVA have been made with this technology, and the reliability figure exceeds 99.9 %. Impregnation consolidates the winding tightly and still leaves it free for axial thermal expansion. Vibration sparking and slot discharges are eliminated, there is no need to rewedge the slots and tighten the end windings, and the stator core needs no maintenance. SGen-1000A is designed for 10 000 start-stop cycles over its service life.

The base version complies with IEC and IEEE/ANSI standards. The generators work in steam and combined-cycle power plants, CHP and industrial plants, as part of simple- and combined-cycle gas turbine plants in peak, intermediate and base load duty. In the oil and gas industry they are installed onshore and offshore, including in explosion-proof versions.

A separate area is the replacement of obsolete generators with water, hydrogen or air cooling within the existing foundation (Footprint™ replacement). The machine is also operated as a synchronous condenser to stabilize grid frequency and voltage.

Technical specifications

Apparent powerSGen-100A: 25–370 MVA; SGen-1000A: 180–370 MVA
Stator voltageSGen-100A: 6.3–15.75 kV; SGen-1000A: 10.5–20 kV
Frequency50 Hz (SGen5) / 60 Hz (SGen6)
Number of poles2 (SGen-100A also 4-pole)
Efficiencyup to 98.9 %
cos φ0.80 (50 Hz) / 0.85 (60 Hz)
Coolingair, direct radial cooling of the rotor winding
InsulationMICALASTIC® (GVPI), class F
Excitationbrushless or static
SGen-1000A service life10 000 start-stops
StandardsIEC, IEEE/ANSI

Request a price and lead time

SGen-100A / SGen-1000A — air-cooled turbo generators 25–370 MVA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8501 64 00 00
HS, 6 digits8501 64
CN (EU)8501 64 00
HTSUS (USA)8501 64 00 00
China customs tariff8501 64 10 00
8501 64 20 00
8501 64 30 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What rating and voltage do SGen-100A and SGen-1000A generators have?

SGen-100A covers 25–370 MVA at a stator voltage of 6.3–15.75 kV. SGen-1000A is rated for 180–370 MVA and 10.5–20 kV.

Is a hydrogen system needed for SGen-1000A generators?

No, cooling is fully by air, with direct radial cooling of the rotor winding. The plant does without a hydrogen system.

What standards does the base version meet and what is the insulation class?

The base version complies with IEC and IEEE/ANSI standards. The MICALASTIC® stator insulation is made with GVPI technology, class F.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides