VRTS8CC variable frequency resonant test systems for GIS, 200–1000 kV

Transportable variable frequency resonant test systems of the VRTS8CC series for on-site AC testing of gas-insulated switchgear (GIS) and gas-insulated lines (GIL). Models cover 200 to 1000 kV with currents of 3.0, 4.5 or 7 A, and the output voltage is pure sinusoidal.

Maximum test voltage
200 – 1000 kV
Current
3.0 / 4.5 / 7 A
Frequency range
[45]..60 – 300 Hz
Modules in series
1 – 4

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

These resonant AC test systems suit any job where the load is mainly capacitive with low losses, such as power cables, gas-insulated switchgear, capacitors, generator windings and dry testing of insulators. The VRTS8CC series is built first of all for testing GIS and GIL installations, though cables, transformers, generators and motors can be tested on the same kit. The units are light for their class and easy to move, and stationary versions are offered for factories and laboratories.

Resonance is reached by tuning the frequency. The high-voltage reactor has a fixed inductance, so the frequency is adjusted until the reactor's inductive reactance matches the capacitive reactance of the test object. From then on the mains supplies only the active losses, so the input power equals the output power divided by the quality factor Q of the circuit. During GIS testing Q is set mostly by reactor losses and often exceeds 100 at full load. The energy released in a breakdown is far lower than from transformer sources, whose short-circuit current is usually about 10 times rated.

The reactors are FRP cylinders with oil-insulated coils, and their radially laminated cores are wrapped in copper windings. The cylinders are stacked and connected in series in a cascade to reach high voltages, and they run in series resonance. The power-to-mass ratio of the high-voltage section is up to four times better than in fixed-frequency systems. There are no moving internal parts, so maintenance is minimal, and the symmetrical three-phase input reduces the cost of hiring a generator. The operator HMI panel shows voltage and current.

Systems of 200 and 250 kV use one module, 400 and 500 kV use two, 600 and 750 kV use three, and 800 and 1000 kV use four. The 3.0 A models run at 1/2 hour on and 6 hours off with an 807 kg module. The 4.5 A S variant runs at 1 hour on and 23 hours off with a 795 kg module, the 4.5 A L variant at 1 hour on and 4 hours off with a 1450 kg module, and the 7 A model at 1 hour on and 4 hours off with a 2495 kg module. The HV section height runs from 2.1 m in VRTS8CC200-900-S to 9.8 m in VRTS8CC1000-7000-4L. The bracketed 45 Hz figure in the frequency range marks reduced-voltage operation.

The systems meet the requirements of IEEE STD 400, IEEE STD 4-2010, IEC 62271-203 and IEC 60517, and they work within the recommended IEC frequency band of 45 to 300 Hz.

Technical specifications

Maximum test voltage200 – 1000 kV
Current3.0 / 4.5 / 7 A
Frequency range[45]..60 – 300 Hz
Modules in series1 – 4
Duty cycle1/2 h on / 6 h off, 1 h on / 4 h off, 1 h on / 23 h off
HV module weight795 / 807 / 1450 / 2495 kg
HV section height2.1 – 9.8 m
Load capacitance (VRTS8CC200-900-S)2.3 – 59 nF [106]
Load capacitance (VRTS8CC1000-3000-4)0.3 – 8 nF [14]
Output voltagepure sinusoidal
Power supplysymmetrical three-phase
ReactorFRP cylinder, oil insulation, series resonance
StandardsIEEE STD 400, IEEE STD 4-2010, IEC 62271-203, IEC 60517

Part numbers

Show all part numbers (16)

VRTS8CC1000-7000-4L, VRTS8CC1000-3000-4, VRTS8CC800-3600-4L, VRTS8CC800-3600-4S, VRTS8CC750-5250-3L, VRTS8CC750-2250-3, VRTS8CC600-2700-3L, VRTS8CC600-2700-3S, VRTS8CC500-3500-2L, VRTS8CC500-1500-2, VRTS8CC400-1800-2L, VRTS8CC400-1800-2S, VRTS8CC250-1750-L, VRTS8CC250-750, VRTS8CC200-900-L, VRTS8CC200-900-S

Request a price and lead time

VRTS8CC variable frequency resonant test systems for GIS, 200–1000 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which load capacitance can the VRTS8CC system test?

It depends on the model. The VRTS8CC200-900-S works at 200 kV with 2.3 to 59 nF, while the VRTS8CC1000-7000-4L works at 1000 kV with 0.75 to 18 nF. At reduced voltage the range is wider, reaching [106] nF for the 200 kV models.

What supply does the site need?

The system runs from a symmetrical three-phase mains supply. The mains power equals the output power divided by Q, which during GIS testing often exceeds 100.

How is 1000 kV reached?

By connecting four cylinder reactors in series in a cascade. The HV section of the VRTS8CC1000-3000-4 is 8.9 m high.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides