VBT-75 S2 Vacuum Interrupter Tester, 10-75 kV DC
The VBT-75 S2 is a portable microprocessor instrument that applies DC voltage from 10 to 75 kV stepped by 5 kV to test vacuum interrupters. A leakage current threshold of 100, 200 or 300 µA is set, and the result 'Pass' or 'Failure' appears on the LCD. It works in the substation and in the workshop.
- Output voltage
- 10 kV to 75 kV DC, stepped by 5 kV
- Voltage accuracy
- 1.5%
- Ripple
- no more than 3%
- Leakage threshold
- 100, 200 or 300 µA (programmable)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The second-generation instrument checks the dielectric strength of vacuum interrupters in medium voltage circuit breakers. Substation operations teams, repair bays and service crews use it either on the breaker in place or on a bench in the workshop. The breaker is taken out of service and fully isolated during the test, and only trained personnel should operate the instrument.
The operator sets the test voltage between 10 and 75 kV DC stepped by 5 kV, with a hold time from 5 seconds to 2 minutes. The voltage rises to the set level and is held for the entire test. If the leakage current stays below the 100, 200 or 300 µA threshold, the voltage is removed and the message 'Pass' appears on the screen. On flashover or breakdown of the interrupter, the voltage is cut off instantly, the message 'Failure' appears and the 'TEST FAIL' indicator lights. Output voltage accuracy is 1.5%, ripple is no more than 3%, and the internal high voltage discharges within 3 seconds.
A buzzer and an LED labelled 'HIGH VOLTAGE' signal the presence of high voltage. For operator safety the 'ARM' switch must be held during the test. Control is by a single turn-and-press knob, and the backlit LCD, 20 characters by 4 lines, can be read both in bright sunlight and in low light. Firmware is updated on site through the built-in USB flash drive port.
The unit runs from 90-240 Vac mains, drawing 2 A at 50/60 Hz. Operating temperature is from -10°C to +50°C and storage from -30°C to +70°C. Humidity is up to 90% at 40°C, non-condensing, and the safety specifications are fully met up to an altitude of 2000 m. The enclosure is rated IP32.
The 9134-UC kit includes a 3.05 m high voltage cable with a quick-release clamp, a return high voltage cable, an earth cable, a mains cord and a transport case. The 9134-SC case and replacement cables 8000-0016, 8000-0088 and 8000-0092 are ordered separately.
Technical specifications
| Output voltage | 10 kV to 75 kV DC, stepped by 5 kV |
|---|---|
| Voltage accuracy | 1.5% |
| Ripple | no more than 3% |
| Leakage threshold | 100, 200 or 300 µA (programmable) |
| Test duration | from 5 s to 2 min |
| Discharge time | no more than 3 s |
| Display | backlit LCD, 20 characters x 4 lines |
| Power supply | 2 A at 90-240 Vac, 50/60 Hz |
| Dimensions | 42.7 x 26.9 x 16.5 cm |
| Weight | 4.53 kg |
| Operating temperature | -10°C to +50°C |
| Storage temperature | -30°C to +70°C |
| Humidity | 90% RH at 40°C, non-condensing |
| Altitude | up to 2000 m |
| Enclosure rating | IP32 |
| Cables | high voltage 3.05 m, return 3.05 m, earth, mains |
Part numbers
Show all part numbers (5)
9134-UC, 9134-SC, 8000-0016, 8000-0088, 8000-0092
Request a price and lead time
VBT-75 S2 Vacuum Interrupter Tester, 10-75 kV DC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What voltage steps does the VBT-75 S2 use?
The test voltage is set from 10 to 75 kV DC stepped by 5 kV. The 1 kV step, keypad and test report printing are features of the VBT-75P S2 version.
How does the instrument detect a failed interrupter?
On flashover the voltage is cut off instantly, the display shows 'Failure' and the 'TEST FAIL' indicator lights. The leakage threshold is chosen as 100, 200 or 300 µA.
Can the firmware be updated on site?
Yes. Firmware is updated in place through the built-in USB flash drive port.