International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Variable inductance resonant test systems, tank type, 22–150 kV

Variable inductance resonant test systems with the reactor in a steel tank, for factory and field testing of cables, capacitors and rotating machines. Standard units run from 22 kV at 288 kVA to 150 kV at 3000 kVA, and up to 12160 kVA at 75/50/25 kV, designed for a 50 or 60 Hz supply.

Output voltage
22 – 150 kV (with taps)
Power
125 – 12160 kVA
Frequency
50 or 60 Hz
Duty cycle
from 5 min on / 15 min off to continuous

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

These systems are mainly used for AC testing of power cables, capacitors and rotating machines, either in the factory or on site. They also suit other loads that are mostly capacitive with very small active losses, such as GIS, generator windings and dry testing of insulator strings. The system can be combined with partial discharge and loss tangent measurement.

Resonance occurs when the total inductive reactance equals the capacitive reactance. Here the frequency is fixed, so the circuit is tuned by changing the inductance of the reactor. At resonance reactive power circulates between the test object and the reactor, and the excitation winding supplies only the active losses in the windings and core. The ratio of reactive to active power sets the quality factor Q of the circuit.

The coils are oil-insulated and sit in an earthed steel dead tank, so the housing carries no potential. The system works in parallel and series resonance modes, and several output taps widen the tuning range. The bushing can stand vertically or at an angle, depending on the application.

Standard units cover 22 to 150 kV and 125 to 12160 kVA. The 22 kV / 288 kVA unit runs at half an hour on and four hours off, measures 970 × 1053 × 1053 mm and weighs 1134 kg. The 60 kV / 600 kVA unit is for continuous duty at 60 Hz, with dimensions of 2083 × 1727 × 2083 mm and a weight of 3720 kg. The 150/92/80/37 kV / 3000 kVA unit measures 3988 × 2159 × 2794 mm and weighs 11340 kg, and the largest standard unit, 75/50/25 kV at 12160 kVA, weighs 21319 kg. Duty cycles range from 5 minutes on and 15 minutes off up to continuous. Dimensions and weights are approximate and may change for custom versions.

Technical specifications

Output voltage22 – 150 kV (with taps)
Power125 – 12160 kVA
Frequency50 or 60 Hz
Duty cyclefrom 5 min on / 15 min off to continuous
Example, 22 kV / 288 kVA970 × 1053 × 1053 mm, 1134 kg
Example, 150/92/80/37 kV / 3000 kVA3988 × 2159 × 2794 mm, 11340 kg
Example, 75/50/25 kV / 12160 kVA3353 × 2997 × 3505 mm, 21319 kg
Resonance modesparallel and series
Constructionearthed steel tank, oil insulation
Bushingvertical or angled
Operation at another frequency50 to 60 Hz: tuning range reduced by 20%; 60 to 50 Hz: output voltage reduced by 20%
StandardsIEC 60060-1, IEEE 4

Request a price and lead time

Variable inductance resonant test systems, tank type, 22–150 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can a 50 Hz unit run on a 60 Hz supply?

Yes, but the tuning range is reduced by 20%. A 60 Hz unit run at 50 Hz gives an output voltage that is 20% lower.

Which units are rated for continuous duty?

Continuous duty is offered for the 40 kV / 1250 kVA unit at 50 Hz and the 60 kV / 600 kVA unit at 60 Hz. Other units run in cycles, from 5 minutes on and 15 minutes off up to 1 hour on and 1 hour off.

Can partial discharge measurement be added?

Yes, the system can be combined with partial discharge and loss tangent measuring equipment.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides