UHF Horn Antenna for Partial Discharge Measurement in GIS, GIL and Transformers, 500 MHz to 3 GHz

This UHF horn antenna picks up electromagnetic emissions from partial discharge in gas-insulated switchgear (GIS and GIL) and in medium and high voltage power transformers. The broadband antenna has a flat response from 500 MHz to 3 GHz and works as a passive sensor.

Frequency band
500 MHz to 3 GHz
Antenna factor
50 to 30 dB/m
Typical VSWR
5:1
3 dB beam width
60° to 140°

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The antenna is used to detect and monitor partial discharge in high voltage equipment. Its operating band is chosen to match partial discharge activity, and the design is tuned for maximum sensitivity and high gain. The flat frequency response makes the antenna suitable for many tasks. It can be fitted to almost any electrical equipment that has openings or surfaces transparent to electromagnetic radiation, so one model can be used on different types of equipment.

The antenna is compact, rugged and passive, so it needs no power supply and no maintenance, which suits direct mounting on GIS, GIL and medium and high voltage transformers. Dimensions are 70 mm x 100 mm x 50 mm and the weight is 260 g. It has a Type N connector and a 50 ohm impedance. Polarisation is linear, the 3 dB beam width runs from 60° to 140°, the antenna factor is 50 to 30 dB/m, and the typical VSWR is 5:1.

On GIS and GIL the antenna is placed above a spacer that is transparent to electromagnetic radiation. On a power transformer it is mounted close to a bushing. In both cases the antenna connects to the partial discharge measuring system through a frequency converter, and placement should follow the manufacturer's mounting scheme. Position it next to unshielded openings in the enclosure. Permissible relative humidity during operation is 0-100%.

The antenna belongs to a range of sensors compatible with the manufacturer's diagnostic platform, and different sensor types can be combined for a given application. The manufacturer cites maintenance-free operation, high sensitivity, ease of use and safety among the advantages.

Technical specifications

Frequency band500 MHz to 3 GHz
Antenna factor50 to 30 dB/m
Typical VSWR5:1
3 dB beam width60° to 140°
Polarisationlinear
Impedance50 ohm
Dimensions70 mm x 100 mm x 50 mm
Weight260 g
ConnectorType N
Sensor typepassive
Mountingclose to unshielded openings in the enclosure
Relative humidity0-100%

Request a price and lead time

UHF Horn Antenna for Partial Discharge Measurement in GIS, GIL and Transformers, 500 MHz to 3 GHz. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Where is the antenna fitted on GIS and transformers?

On GIS and GIL it is placed above a spacer that is transparent to electromagnetic radiation, and on a transformer it is fitted near a bushing.

Does the antenna need a power supply?

No. It is passive and needs no maintenance. It connects to the measuring system through a frequency converter.

What connector and impedance does it have?

It has a Type N connector and 50 ohm impedance, with a frequency band of 500 MHz to 3 GHz.

Similar equipment from other manufacturers