International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

TTS Test Systems for Single-Phase Distribution Transformers, 125 kVA to 2500 kVA

The TTS systems supply voltage and current for tests on single-phase distribution transformers under IEC 60076 and ANSI / IEEE C57.12. Five models cover ratings from 125 kVA to 2500 kVA, from the TTS5M at the low end to the TTS50-1 at the top.

Models and ratings
TTS5M 125 to 375 kVA; TTS10M 250 to 750 kVA; TTS20-1 333 to 1000 kVA; TTS30-1 500 to 1500 kVA; TTS50-1 833 to 2500 kVA
Test standards
IEC 60076 and IEEE C57.12 with DOE efficiency rules
Basic tests
magnetising current, no-load losses, short-circuit voltage, load losses, temperature
Heat-run tests
TTS20-1, TTS30-1, TTS50-1

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The TTS systems are used to test single-phase distribution transformers. Typical jobs include confirming factory test results and design data before installation, checking a unit after repair or upgrade, and inspecting it after an event like a lightning strike. They also serve preventive and predictive maintenance programmes, and they show whether a transformer meets its purchase specification and will perform properly once installed.

The base tests follow ANSI / IEEE C57.12 and IEC 60076 and cover magnetising current, no-load losses, short-circuit voltage, load losses and temperature measurement. The TTS20-1, TTS30-1 and TTS50-1 models also carry out heat-run tests. Optional equipment adds applied-voltage tests from a cylindrical AC hipot, induced-voltage tests from a motor-generator with its controls and frequency meter on the panel, turns ratio measurement with the PATTR-03D and winding resistance measurement with the WRM-10N. The system is designed to meet DOE efficiency requirements.

The transformers that can be tested depend on their impedance. Optional high-voltage taps allow transformers with higher impedance or higher secondary voltage to be tested. The total harmonic distortion of the output voltage is less than 2%.

The TTS5M and TTS10M use manual output voltage control, a hold feature that freezes every meter reading, and three constant-power taps. Their frames have wheels for moving them about and hooks for storing cables. The TTS20-1, TTS30-1 and TTS50-1 add an HMI operator panel for programming automatic functions, with all readings shown on an LCD screen. Data acquisition and test reports run on a computer through the WIN TTS software. On these three models the voltage regulator is motorised with an adjustable ramp rate and automatic return to zero, the tap selector is also motorised, and the wattmeter and voltmeter select their ranges automatically.

Leads are 4.5 metres long, with separate leads for supply and measurement, and the set can be lifted by fork truck or overhead crane. All models include an automatic circuit breaker, high-voltage energise buttons with indicator lights, an external interlock, fast and slow overload protection, a start interlock that requires zero output and a foot switch. Measurements are four-wire, and the thermometer uses a 4.5 metre thermocouple. The equipment works from 10 to 40 °C with humidity below 95% and without condensation, at altitudes up to 1000 metres.

Technical specifications

Models and ratingsTTS5M 125 to 375 kVA; TTS10M 250 to 750 kVA; TTS20-1 333 to 1000 kVA; TTS30-1 500 to 1500 kVA; TTS50-1 833 to 2500 kVA
Test standardsIEC 60076 and IEEE C57.12 with DOE efficiency rules
Basic testsmagnetising current, no-load losses, short-circuit voltage, load losses, temperature
Heat-run testsTTS20-1, TTS30-1, TTS50-1
Control, TTS5M and TTS10Mmanual, three constant-power taps
Control, TTS20-1 to TTS50-1HMI panel, motorised regulator and tap selector, WIN TTS software
Total harmonic distortionbelow 2%
Output leads4.5 metres
Thermocouple4.5 metres
OptionsAC hipot, motor-generator, PATTR-03D, WRM-10N
Operating conditions10 to 40 °C, humidity below 95% non-condensing, altitude below 1000 m

Part numbers

Show all part numbers (7)

TTS5M, TTS10M, TTS20-1, TTS30-1, TTS50-1, PATTR-03D, WRM-10N

Request a price and lead time

TTS Test Systems for Single-Phase Distribution Transformers, 125 kVA to 2500 kVA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which model suits a 1000 kVA transformer?

1000 kVA falls within the TTS20-1 range of 333 to 1000 kVA and the TTS30-1 range of 500 to 1500 kVA, and the actual limit depends on the transformer impedance.

Can turns ratio and winding resistance be measured?

Yes, with the optional PATTR-03D for turns ratio and the WRM-10N for winding resistance.

Which models carry out heat-run tests?

Heat-run tests are available on the TTS20-1, TTS30-1 and TTS50-1 models.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides