TRM-403 three-phase winding resistance meter, 40 A DC, OLTC test
The TRM-403 measures the DC resistance of all three phases of a transformer without reconnecting cables, with currents from 1 to 40 A. It works out the resistance of delta-connected and star windings without an exposed neutral, checks the tap changer and demagnetises the core.
- Type
- portable three-phase winding resistance meter for transformers
- Resistance range
- 1 µΩ to 500 Ω
- Accuracy
- 1–19999 µΩ ±0.5%; 20–999 mΩ ±1%; 1–500 Ω ±1.5% (±1 count)
- Test current
- 1–40 A in 1 A steps
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The TRM-403 is intended for DC resistance measurement of windings in three-phase power transformers. Every test lead is attached to the transformer bushings once, and the instrument then tests each phase in turn without disconnecting anything. With a range from 1 µΩ to 500 Ω, it can also serve as a micro-ohmmeter, for example for the contacts of extra high voltage circuit breakers. Current is adjustable from 1 to 40 A in 1 A steps. For lower currents, the TRM-203 covers up to 25 A and up to 2000 Ω.
Four input channels and a 60 V DC charging source produce a fast and stable reading even on very large transformers, while the voltage stays under 18 V during measurement. For delta windings the instrument derives the resistance of each individual winding from phase readings, and it does the same for star windings without a brought-out neutral. If the winding temperature is entered, the resistance is recalculated to any chosen temperature for comparison with factory reports.
A logging mode collects data for up to 90 minutes at 10, 15, 20, 30 or 60 second intervals, and every record carries a timestamp. The make-before-break mode checks the sequence of tap changer or voltage regulator contacts and plots a dynamic resistance curve that reveals any contact break. Tap positions are changed from the instrument's front panel.
Accuracy is ±0.5% of reading plus one count from 1 to 19999 µΩ, ±1% from 20 to 999 mΩ and ±1.5% from 1 to 500 Ω. After testing, the core is demagnetised automatically. Data is entered on a membrane keyboard, and each report header records the company, substation, transformer details and operator. Memory holds 256 static reports of up to 111 measurements and 120 dynamic reports, and up to 999 reports can be written to a USB drive. A built-in 2.5 inch thermal printer is fitted, and communication with a PC runs over RS-232C, USB or Bluetooth.
The meter runs from 100-240 V AC at 50/60 Hz, with operating temperature from -10 to 50 °C and storage from -30 to 70 °C. It tolerates humidity up to 90% at 40 °C without condensation, and operates at altitudes up to 2000 m. The design complies with CAN/CSA C22.2 and UL 61010A-1. The kit includes four test leads of 15.24 m each, an OLTC control lead, earth, power and USB cables. Dimensions are 53 × 43 × 24 cm and the weight is 15.8 kg.
Technical specifications
| Type | portable three-phase winding resistance meter for transformers |
|---|---|
| Resistance range | 1 µΩ to 500 Ω |
| Accuracy | 1–19999 µΩ ±0.5%; 20–999 mΩ ±1%; 1–500 Ω ±1.5% (±1 count) |
| Test current | 1–40 A in 1 A steps |
| Voltage | 60 V DC charging, up to 18 V DC during measurement |
| Input channels | 4 |
| Modes | delta, star without neutral, OLTC test, demagnetisation, temperature conversion |
| Printer | built-in thermal printer, 2.5 inch |
| Internal memory | 256 static reports of up to 111 measurements, 120 dynamic |
| External memory | up to 999 reports on a USB drive |
| Interfaces | RS-232C, USB, Bluetooth |
| Supply | 100-240 V AC, 50/60 Hz |
| Operating temperature | -10 to 50 °C |
| Storage temperature | -30 to 70 °C |
| Humidity | up to 90% at 40 °C without condensation |
| Safety | CAN/CSA C22.2 and UL 61010A-1 |
| Dimensions | 53 × 43 × 24 cm |
| Weight | 15.8 kg |
Part numbers
Show all part numbers (9)
9006-UC, 8000-0005, 8000-0006, 8000-0015, 8000-0016, 8000-0077, 8000-0149, 8000-0150, 8000-0151
Request a price and lead time
TRM-403 three-phase winding resistance meter, 40 A DC, OLTC test. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Do the cables have to be reconnected between phases?
No, the cables are attached to all bushings once, and the instrument measures the resistance of each phase by itself.
What does the make-before-break mode show?
It plots the resistance of the tap changer or voltage regulator contacts as they switch, so a contact break is visible on the curve.
Can the instrument run long, unattended measurements?
Yes, the logging mode collects data for up to 90 minutes at 10, 15, 20, 30 or 60 second intervals, with each record time-stamped.