TRM-40 winding resistance meter, 40 A DC, 1 µΩ to 500 Ω
The TRM-40 measures the DC resistance of transformer and rotating machine windings with currents from 1 to 40 A, over a range of 1 µΩ to 500 Ω. Two measuring channels, automatic discharge, demagnetisation after testing and an on-load tap changer test come as standard.
- Type
- portable winding resistance meter for transformers
- Resistance range
- 1 µΩ to 500 Ω
- Accuracy
- 1–19999 µΩ ±0.5%; 20–999 mΩ ±1%; 1–500 Ω ±1.5% (±1 count)
- Test current
- 1–40 A in 1 A steps
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Choose the TRM-40 when windings need a higher test current than the TRM-20 can supply, since it covers 1 to 40 A in 1 A steps. Its resistance range runs from 1 µΩ to 500 Ω, so it doubles as a micro-ohmmeter for the contacts of extra high voltage circuit breakers. Two input channels measure two windings at once, for instance primary and secondary.
A 60 V DC charging source brings the current to a steady level quickly on large transformers, and the voltage stays under 18 V during measurement. Automatic discharge removes stored energy from the winding after each test to protect personnel, and the demagnetisation function clears residual magnetism from the core without a manual step.
Accuracy is ±0.5% of reading plus one count from 1 to 19999 µΩ, ±1% from 20 to 999 mΩ, and ±1.5% from 1 to 500 Ω. The OLTC test mode records the dynamic characteristics of the tap changer as it switches.
Memory stores 256 static reports holding up to 111 measurements each and 120 dynamic reports, and up to 999 reports can be saved to an external USB drive. A built-in 2.5 inch thermal printer produces paper copies, and the backlit LCD remains visible in direct sunlight. PC links run over RS-232C, USB or Bluetooth.
The meter runs from 100-240 V AC at 50/60 Hz. Operating temperature is -10 to 50 °C, storage -30 to 70 °C, humidity up to 90% at 40 °C without condensation, and altitude up to 2000 m. The design complies with CAN/CSA C22.2 and UL 61010A-1. Before testing, the transformer must be disconnected and fully isolated, and leads must stay connected during measurement. The kit contains one current cable set, two potential cable sets of 15.24 m each, a 4.57 m OLTC control cable, an earth cable, a power cable, and RS-232C and USB cables of 1.83 m each. A transport case is optional.
Technical specifications
| Type | portable winding resistance meter for transformers |
|---|---|
| Resistance range | 1 µΩ to 500 Ω |
| Accuracy | 1–19999 µΩ ±0.5%; 20–999 mΩ ±1%; 1–500 Ω ±1.5% (±1 count) |
| Test current | 1–40 A in 1 A steps |
| Voltage | 60 V DC charging, up to 18 V DC during measurement |
| Channels | two static channels |
| Display | backlit LCD, 64 × 128 dots |
| Printer | built-in thermal printer, 2.5 inch |
| Internal memory | 256 static reports of up to 111 measurements, 120 dynamic |
| External memory | up to 999 reports on a USB drive |
| Interfaces | RS-232C, USB, Bluetooth |
| Supply | 100-240 V AC, 50/60 Hz |
| Operating temperature | -10 to 50 °C |
| Storage temperature | -30 to 70 °C |
| Humidity | up to 90% at 40 °C without condensation |
| Safety | CAN/CSA C22.2 and UL 61010A-1 |
| Dimensions | 53 × 43 × 24 cm |
| Weight | 15.4 kg |
Part numbers
Show all part numbers (9)
9061-UC, 8000-0005, 8000-0006, 8000-0015, 8000-0016, 8000-0071, 8000-0083, 8000-0087, 8000-0148
Request a price and lead time
TRM-40 winding resistance meter, 40 A DC, 1 µΩ to 500 Ω. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can two windings be measured at the same time?
Yes, the two input channels measure the resistance of two windings, such as primary and secondary, with a single current connection.
Can the TRM-40 check circuit breaker contacts?
Yes, the range from 1 µΩ allows it to be used as a micro-ohmmeter for the contacts of extra high voltage circuit breakers.
Is demagnetising needed after the measurement?
The instrument demagnetises the core automatically after the test, so no separate manual operation is required.