TRM-40 winding resistance meter, 40 A DC, 1 µΩ to 500 Ω

The TRM-40 measures the DC resistance of transformer and rotating machine windings with currents from 1 to 40 A, over a range of 1 µΩ to 500 Ω. Two measuring channels, automatic discharge, demagnetisation after testing and an on-load tap changer test come as standard.

Type
portable winding resistance meter for transformers
Resistance range
1 µΩ to 500 Ω
Accuracy
1–19999 µΩ ±0.5%; 20–999 mΩ ±1%; 1–500 Ω ±1.5% (±1 count)
Test current
1–40 A in 1 A steps

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Choose the TRM-40 when windings need a higher test current than the TRM-20 can supply, since it covers 1 to 40 A in 1 A steps. Its resistance range runs from 1 µΩ to 500 Ω, so it doubles as a micro-ohmmeter for the contacts of extra high voltage circuit breakers. Two input channels measure two windings at once, for instance primary and secondary.

A 60 V DC charging source brings the current to a steady level quickly on large transformers, and the voltage stays under 18 V during measurement. Automatic discharge removes stored energy from the winding after each test to protect personnel, and the demagnetisation function clears residual magnetism from the core without a manual step.

Accuracy is ±0.5% of reading plus one count from 1 to 19999 µΩ, ±1% from 20 to 999 mΩ, and ±1.5% from 1 to 500 Ω. The OLTC test mode records the dynamic characteristics of the tap changer as it switches.

Memory stores 256 static reports holding up to 111 measurements each and 120 dynamic reports, and up to 999 reports can be saved to an external USB drive. A built-in 2.5 inch thermal printer produces paper copies, and the backlit LCD remains visible in direct sunlight. PC links run over RS-232C, USB or Bluetooth.

The meter runs from 100-240 V AC at 50/60 Hz. Operating temperature is -10 to 50 °C, storage -30 to 70 °C, humidity up to 90% at 40 °C without condensation, and altitude up to 2000 m. The design complies with CAN/CSA C22.2 and UL 61010A-1. Before testing, the transformer must be disconnected and fully isolated, and leads must stay connected during measurement. The kit contains one current cable set, two potential cable sets of 15.24 m each, a 4.57 m OLTC control cable, an earth cable, a power cable, and RS-232C and USB cables of 1.83 m each. A transport case is optional.

Technical specifications

Typeportable winding resistance meter for transformers
Resistance range1 µΩ to 500 Ω
Accuracy1–19999 µΩ ±0.5%; 20–999 mΩ ±1%; 1–500 Ω ±1.5% (±1 count)
Test current1–40 A in 1 A steps
Voltage60 V DC charging, up to 18 V DC during measurement
Channelstwo static channels
Displaybacklit LCD, 64 × 128 dots
Printerbuilt-in thermal printer, 2.5 inch
Internal memory256 static reports of up to 111 measurements, 120 dynamic
External memoryup to 999 reports on a USB drive
InterfacesRS-232C, USB, Bluetooth
Supply100-240 V AC, 50/60 Hz
Operating temperature-10 to 50 °C
Storage temperature-30 to 70 °C
Humidityup to 90% at 40 °C without condensation
SafetyCAN/CSA C22.2 and UL 61010A-1
Dimensions53 × 43 × 24 cm
Weight15.4 kg

Part numbers

Show all part numbers (9)

9061-UC, 8000-0005, 8000-0006, 8000-0015, 8000-0016, 8000-0071, 8000-0083, 8000-0087, 8000-0148

Request a price and lead time

TRM-40 winding resistance meter, 40 A DC, 1 µΩ to 500 Ω. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Can two windings be measured at the same time?

Yes, the two input channels measure the resistance of two windings, such as primary and secondary, with a single current connection.

Can the TRM-40 check circuit breaker contacts?

Yes, the range from 1 µΩ allows it to be used as a micro-ohmmeter for the contacts of extra high voltage circuit breakers.

Is demagnetising needed after the measurement?

The instrument demagnetises the core automatically after the test, so no separate manual operation is required.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides