TRF-250 A battery-powered three-phase transformer turns ratio tester, 250 V AC
The TRF-250 A is the battery version of the TRF-250, with a charge lasting about 3 hours of continuous use. It measures the turns ratio from 0.8 to 50000 at voltages up to 250 V AC, and includes a built-in printer, Bluetooth and USB.
- Type
- portable automatic three-phase turns ratio tester
- Test procedure
- ANSI/IEEE C57.12.90
- Ratio range
- 0.8 to 50000 : 1
- Test voltages
- 4 V AC at 120 mA, 40 V AC at 50 mA, 100 V AC at 20 mA, 250 V AC at 10 mA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The TRF-250 A is designed for measuring the turns ratio of three-phase transformers in places without a convenient mains supply. Compared with the base TRF-250, it runs on batteries: two lead-acid 12 V, 2 Ah batteries provide up to 3 hours of continuous operation. A built-in charger lets the instrument work while it is charging from a 100-240 V, 50/60 Hz mains supply. It works on its own or under PC control.
The ratio is determined by the IEEE C57.12.90 method across 0.8 to 50000:1. Test voltages are 4 V at 120 mA, 40 V at 50 mA, 100 V at 20 mA and 250 V at 10 mA. The instrument recognises 130 types of three-phase transformer by ANSI, IEC and Australian standards.
Along with the ratio, it measures magnetising current from 0 to 1 A with ±0.1 mA plus 2% of reading, phase angle from 0 to 360° within ±0.2°, and winding polarity. Results show on a backlit graphic LCD of 128 × 64 dots, readable in sunlight and in dim light, and data is entered from a 44-key membrane QWERTY keyboard. The OLTC control contact is rated at 240 V AC and 2 A.
A 4.5 inch thermal printer is fitted as standard on this model. Internal memory stores 112 reports, each holding up to 99 measurements, plus 128 test plans that can be sent to a PC. Reports can also be written to an external USB drive, up to 999 of them. The PC link runs over Bluetooth or USB, and the analysis software is included.
Operating temperature runs from -10 to 50 °C, and humidity can reach 90% at 40 °C without condensation, at altitudes up to 2000 m with full compliance with safety requirements. Safety compliance covers CAN/CSA C22.2 (number 1010.1-92) and UL 61010A-1. Dimensions are 45.7 × 12.7 × 30.5 cm and the weight is 9.1 kg. The kit includes single-phase and three-phase cable sets of 4.57 m each, a 7.62 m extension, an earth cable, a USB cable and a carrying bag, while a transport case and H and X cables of 9.14 m are optional extras.
Technical specifications
| Type | portable automatic three-phase turns ratio tester |
|---|---|
| Test procedure | ANSI/IEEE C57.12.90 |
| Ratio range | 0.8 to 50000 : 1 |
| Test voltages | 4 V AC at 120 mA, 40 V AC at 50 mA, 100 V AC at 20 mA, 250 V AC at 10 mA |
| Batteries | 2 lead-acid, 12 V, 2 Ah, up to 3 hours of operation |
| Mains supply | 100-240 V AC, 50/60 Hz |
| Magnetising current | 0 to 1 A, ±0.1 mA, ±2% of reading |
| Phase angle | 0 to 360°, ±0.2° |
| Display | backlit graphic LCD, 128 × 64 dots |
| Printer | built-in thermal printer, 4.5 inch |
| Interfaces | Bluetooth, USB |
| Internal memory | 112 reports of up to 99 measurements each, 128 test plans |
| External memory | up to 999 reports on a USB drive |
| OLTC control contact | 240 V AC, 2 A |
| Operating temperature | -10 to 50 °C |
| Humidity | 90% at 40 °C without condensation |
| Safety | CAN/CSA C22.2 (number 1010.1-92) and UL 61010A-1 |
| Dimensions | 45.7 × 12.7 × 30.5 cm |
| Weight | 9.1 kg |
Part numbers
Show all part numbers (2)
9106-UC, 9106-SC
Request a price and lead time
TRF-250 A battery-powered three-phase transformer turns ratio tester, 250 V AC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How long does the instrument run on battery?
Two 12 V, 2 Ah batteries give about 3 hours of continuous operation, and the instrument can be used while it charges from the mains.
Does the battery version have OLTC control?
Yes, the instrument has an OLTC control contact rated at 240 V AC and 2 A.
How does the TRF-250 A differ from the TRF-250?
It runs on batteries with a built-in charger and has a printer fitted as standard. Its test currents are lower, with 120 mA at 4 V as the highest.
Similar equipment from other manufacturers