TRF-250 three-phase transformer turns ratio tester, 250 V AC, with OLTC control
The TRF-250 measures turns ratio, magnetising current and winding polarity of three-phase transformers at voltages up to 250 V AC. It has a QWERTY keyboard, Bluetooth and USB interfaces, and a contact for on-load tap changer control.
- Type
- portable automatic three-phase turns ratio tester
- Test procedure
- ANSI/IEEE C57.12.90
- Ratio range
- 0.8 to 50000 : 1
- Test voltages
- 4 V AC at 1 A, 40 V AC at 200 mA, 100 V AC at 100 mA, 250 V AC at 50 mA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The TRF-250 is the fourth generation of turns ratio testers from this line. Compared with earlier models, it applies a higher test voltage of 250 V AC, adds a wireless Bluetooth link and includes a membrane QWERTY keyboard with 44 keys. The unit is portable, housed in a 45.7 × 12.7 × 30.5 cm case and weighing 9.1 kg, and it can work on its own or under PC control.
Turns ratio is determined according to the IEEE C57.12.90 method across 0.8 to 50000:1. Test voltages are 4 V at 1 A, 40 V at 200 mA, 100 V at 100 mA and 250 V at 50 mA. Accuracy is highest at 250 V, where the error is ±0.1% from 0.8 to 1999, ±0.15% from 2000 to 3999, ±0.8% from 4000 to 14999, and ±1.2% from 15000 to 50000. The instrument recognises 130 types of three-phase transformer by ANSI, IEC and Australian standards.
Alongside the ratio, it measures magnetising current from 0 to 2 A with ±0.1 mA plus 2% of reading, phase angle from 0 to 360° within ±0.2°, and winding polarity. The results appear on a backlit graphic LCD of 128 × 64 dots, which can be read in sunlight and in dim light. The OLTC control contact is rated at 240 V AC and 2 A, which allows the ratio to be taken at every tap changer position.
Internal memory holds 112 reports, each with up to 99 measurements, along with 128 test plans that can be sent to a PC. An external USB drive can record up to 999 reports. The PC link runs over Bluetooth or USB, and the analysis software is included in the kit. A 4.5 inch thermal printer is available as an option.
It runs from 100-240 V AC at 50/60 Hz. Operating temperature is -10 to 50 °C and storage is -30 to 70 °C. The enclosure carries IP32 protection and pollution degree 2, and it should be run with the lid open for ventilation. Safety compliance covers CAN/CSA C22.2 (number 1010.1-92) and UL 61010A-1. Before connecting cables, the instrument must be earthed to the substation earth grid, and the transformer must be disconnected and fully isolated. The kit contains single-phase and three-phase cable sets of 4.57 m each, a 7.62 m extension, an earth cable, a USB cable and a bag, while the printer and transport case are ordered separately.
Technical specifications
| Type | portable automatic three-phase turns ratio tester |
|---|---|
| Test procedure | ANSI/IEEE C57.12.90 |
| Ratio range | 0.8 to 50000 : 1 |
| Test voltages | 4 V AC at 1 A, 40 V AC at 200 mA, 100 V AC at 100 mA, 250 V AC at 50 mA |
| Accuracy at 250 V | 0.8 to 1999 ±0.1%; 2000 to 3999 ±0.15%; 4000 to 14999 ±0.8%; 15000 to 50000 ±1.2% |
| Magnetising current | 0 to 2 A, ±0.1 mA, ±2% of reading |
| Phase angle | 0 to 360°, ±0.2° |
| Display | backlit graphic LCD, 128 × 64 dots |
| Interfaces | Bluetooth, USB |
| Internal memory | 112 reports of up to 99 measurements each, 128 test plans |
| External memory | up to 999 reports on a USB drive |
| OLTC control contact | 240 V AC, 2 A |
| Printer | optional thermal printer, 4.5 inch |
| Supply | 100-240 V AC, 50/60 Hz |
| Operating temperature | -10 to 50 °C |
| Storage temperature | -30 to 70 °C |
| Safety | CAN/CSA C22.2 (number 1010.1-92) and UL 61010A-1 |
| Dimensions | 45.7 × 12.7 × 30.5 cm |
| Weight | 9.1 kg |
Part numbers
Show all part numbers (3)
9105-UC, 9105-PR, 9105-SC
Request a price and lead time
TRF-250 three-phase transformer turns ratio tester, 250 V AC, with OLTC control. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How does the TRF-250 differ from the TRF-100?
It applies a 250 V AC test voltage and adds a Bluetooth link, a QWERTY keyboard and an OLTC control contact rated at 240 V AC, 2 A.
Can the ratio be taken automatically at every tap position?
Yes, the OLTC control contact rated at 240 V AC, 2 A steps through the tap positions, and each result is recorded in a report of up to 99 measurements.
How many reports can the instrument store?
Internal memory holds 112 reports and 128 test plans, and an external USB drive holds up to 999 reports.