TRF-100 automatic three-phase transformer turns ratio tester, 100 V AC

The TRF-100 measures the turns ratio of power transformers, current transformers and voltage transformers across a range of 0.8 to 50000, using test voltages of 4, 40 and 100 V AC. This portable instrument serves substation work, with memory for 1000 full test reports and a USB interface.

Type
portable automatic three-phase turns ratio tester
Test procedure
ANSI/IEEE C57.12.90
Ratio range
0.8 to 50000 : 1
Test voltages
4 V AC at 1.0 A, 40 V AC at 0.6 A, 100 V AC at 0.1 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The TRF-100 is a portable, microprocessor-based instrument for checking transformers at substations, including power transformers and current and voltage transformers. It is the third generation of automatic three-phase turns ratio testers of this type. It is light and easy to carry, weighing 6.4 kg, and it measures 43.2 × 17.8 × 33.0 cm.

Results appear on a backlit LCD with 20 characters across four lines, which stays readable in bright sunlight and in dim light. An optional built-in thermal printer 4.5 inches wide can be fitted. The memory keeps 1000 full reports, covering nameplate voltages, ratios, magnetising current and phase angle, along with up to 128 test plans. Data goes to a PC over USB, and the analysis software is supplied with the instrument.

Turns ratio is determined by the IEEE C57.12.90 method, with the instrument measuring winding voltages on the transformer with no load. The circuit self-calibrates before each measurement, so neither adjustment nor temperature compensation is required. Accuracy is 0.1% or better; at 40 V and 100 V the error is ±0.05% across 0.8 to 1000, while from 20001 to 50000 it rises to ±0.5%.

Test voltages are 4 V at 1.0 A, 40 V at 0.6 A and 100 V at 0.1 A. Alongside the ratio, the instrument measures magnetising current from 0 to 2 A with an accuracy of ±1 mA plus 2% of reading, and phase angle from 0 to 360° within ±0.2°. It recognises 130 types of three-phase transformer according to ANSI, IEC and Australian standards.

It runs from 100-120 V or 200-240 V AC, switchable, at 50/60 Hz and 3 A. Operating temperature is -10 to 50 °C, storage -30 to 70 °C, and humidity up to 90% at 40 °C without condensation, at altitudes up to 2000 m with full safety compliance. The enclosure is tested to UL 61010A-1 and CSA-C22.2, with IEC 61010 (1995) also met. The kit includes single-phase and three-phase cable sets of 4.6 m each, a 7.6 m extension lead, a USB cable, power and earth cables and a carrying bag. A transport case, a remote on-load tap changer (OLTC) controller 9124-UC and H and X cables of 9.14 m are available as options.

Technical specifications

Typeportable automatic three-phase turns ratio tester
Test procedureANSI/IEEE C57.12.90
Ratio range0.8 to 50000 : 1
Test voltages4 V AC at 1.0 A, 40 V AC at 0.6 A, 100 V AC at 0.1 A
Ratio accuracy (40 and 100 V)0.8 to 1000 ±0.05%; 1001 to 4000 ±0.1%; 4001 to 15000 ±0.25%; 15001 to 20000 ±0.4%; 20001 to 50000 ±0.5%
Magnetising current0 to 2 A, ±1 mA, ±2% of reading
Phase angle0 to 360°, ±0.2°
Displaybacklit LCD, 20 characters × 4 lines
Printeroptional built-in thermal printer, 4.5 inch
InterfaceUSB
Memory1000 reports, 128 test plans
Supply100-120 V or 200-240 V AC, 50/60 Hz, 3 A
Operating temperature-10 to 50 °C
Storage temperature-30 to 70 °C
Humidity90% at 40 °C without condensation
SafetyUL 61010A-1 and CSA-C22.2, IEC 61010 (1995)
Dimensions43.2 × 17.8 × 33.0 cm
Weight6.4 kg

Part numbers

Show all part numbers (14)

9117-UC, 9117-PR, 9124-UC, 8000-0005, 8000-0009, 8000-0010, 8000-0011, 8000-0012, 8000-0013, 8000-0014, 8000-0186, 8000-0187, 8000-0188, 8000-0189

Request a price and lead time

TRF-100 automatic three-phase transformer turns ratio tester, 100 V AC. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which transformers can the instrument test?

Power transformers, both three-phase and single-phase, along with current and voltage transformers. It recognises 130 three-phase connection schemes according to ANSI, IEC and Australian standards.

Is temperature compensation or on-site calibration needed?

No, the measuring circuit self-calibrates before every measurement, so adjustment and temperature compensation are not required.

What should be ordered together with the main unit?

The main kit with cables has code 9117-UC, the built-in printer is 9117-PR and the remote OLTC controller is 9124-UC. H and X cables of 9.14 m are ordered separately.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides