TEV Antenna capacitive partial discharge sensor for switchgear, 0.1 to 300 MHz
The TEV Antenna detects partial discharges through transient earth voltage on the earthed metal enclosure of switchgear. The passive sensor is clamped with magnets across an enclosure opening and is more sensitive than single-pole TEV sensors.
- Type
- passive TEV partial discharge sensor
- Principle of operation
- capacitive coupling to an earthed metal enclosure
- Frequency band
- 0.1 MHz to 300 MHz
- Connector
- BNC
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A TEV sensor, short for Transient Earth Voltage, is designed to find partial discharges in medium voltage switchgear. It works on the principle of direct capacitive coupling to the earthed metal enclosure, picking up the electrical signal that partial discharge activity creates across two metal surfaces on either side of an opening.
The sensor is laid across an opening in the metal enclosure so that both of its ends touch the metal surface directly. Magnets hold the contacts in place, so the two ends can be attached to almost any opening in a metal surface. The compact passive design suits direct mounting on medium voltage switchgear.
The two-ended construction gives it higher sensitivity than other single-pole TEV sensors. To raise sensitivity further, the supplier offers optional amplifiers and signal processing units. Power is supplied only to these optional devices, such as a frequency converter, because the sensor itself needs no power.
Used alone, the sensor covers a working band of 0.1 MHz to 300 MHz, and a frequency converter is recommended to extend its capabilities. The output uses a BNC connector, with the signal carried over an RF cable. It measures 130 × 70 × 25 mm, weighs 80 g without the RF cable, and tolerates relative humidity from 0 to 100% in its environment.
Applications include partial discharge measurement and inspection, testing of high voltage insulation systems, condition-based maintenance of rotating machines and diagnosis of electromagnetic interference. The sensor works with a partial discharge diagnostic system that records and analyses the signals it receives.
Technical specifications
| Type | passive TEV partial discharge sensor |
|---|---|
| Principle of operation | capacitive coupling to an earthed metal enclosure |
| Frequency band | 0.1 MHz to 300 MHz |
| Connector | BNC |
| Dimensions | 130 × 70 × 25 mm |
| Weight without cable | 80 g |
| Mounting | magnetic, to a metal switchgear enclosure |
| Relative humidity | 0 to 100% |
| Power | only for optional devices |
Request a price and lead time
TEV Antenna capacitive partial discharge sensor for switchgear, 0.1 to 300 MHz. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How is the TEV sensor mounted?
Across an opening in the metal switchgear enclosure, with both ends held on the metal by magnets.
Does the TEV sensor need a power supply?
No, the sensor is passive and power is supplied only to optional devices, such as a frequency converter.
What is the sensor's frequency range?
Its working band is 0.1 to 300 MHz, and its output connector is BNC.