TEM Antenna broadband partial discharge sensor, 100 MHz to 3 GHz
The TEM Antenna picks up electromagnetic emissions from partial discharges in equipment under monitoring, such as medium voltage switchgear or low and medium voltage induction motors fed by converters. The passive sensor is mounted directly on the equipment.
- Type
- passive partial discharge sensor
- Frequency band
- 100 MHz to 3 GHz
- Gain
- 1.8 to 4.25 dBi
- Typical VSWR
- 5:1
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Partial discharges within insulation are accompanied by electromagnetic radiation, which escapes through openings and radio-transparent areas of the enclosure. The TEM Antenna is placed beside such openings and passes its signal on to a partial discharge diagnostic system. It suits medium voltage switchgear, motors and almost any electrical equipment that has vents or radio-transparent surfaces.
The antenna is broadband with a flat amplitude-frequency response, so it works across a wide range of objects. Its working band of 100 MHz to 3 GHz covers the frequencies typical of partial discharge activity, and the design is tuned for maximum sensitivity and high gain. Gain runs from 1.8 to 4.25 dBi, the 3 dB beamwidth spans 100° to 210°, polarisation is linear and the typical VSWR is 5:1.
The sensor is passive and needs no power of its own, although optional devices such as a frequency converter are powered separately. It has a 50 Ω impedance and an N-type output connector. The compact housing measures 80 × 150 × 50 mm and weighs 250 g without the cable, and it tolerates relative humidity from 0 to 100%.
Objects suited to this sensor include generators, motors, variable frequency drives, PWM converter panels, switchgear, high voltage bushings, medium and high voltage power transformers, and measuring current and voltage transformers. The antenna is said to be compatible with the same diagnostic platform, and sensors of different types can be combined to suit a particular task.
Technical specifications
| Type | passive partial discharge sensor |
|---|---|
| Frequency band | 100 MHz to 3 GHz |
| Gain | 1.8 to 4.25 dBi |
| Typical VSWR | 5:1 |
| Beamwidth at 3 dB level | 100° to 210° |
| Polarisation | linear |
| Impedance | 50 Ω |
| Connector | N type |
| Dimensions | 80 × 150 × 50 mm |
| Weight without cable | 250 g |
| Power | only for optional devices |
| Installation | near openings in equipment enclosures |
| Relative humidity | 0 to 100% |
Request a price and lead time
TEM Antenna broadband partial discharge sensor, 100 MHz to 3 GHz. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Where is the TEM Antenna installed?
Close to openings or radio-transparent areas of the equipment enclosure, such as medium voltage switchgear or a motor.
Does the sensor need a power supply?
No, the sensor is passive and only optional devices, such as a frequency converter, need power.
Which connector and impedance does the antenna have?
It has an N type connector and a 50 Ω impedance.
Similar equipment from other manufacturers