TDR900 Portable Circuit Breaker Analyser, Four Breaks per Phase, Motion Measurement
TDR900 measures the timing and contact movement of high-voltage circuit breakers of any type. It checks control circuits, the movement of moving parts and operating time, and confirms the results of breaker maintenance.
- Number of phases
- 3
- Breaks per phase
- 4
- Travel channels
- 3
- Aux contact inputs
- 3
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The analyser issues open and close commands and records the timing of the main contacts, their travel, speed, closing moment and contact synchronism, along with the currents in the trip and close coils. It supports the operations O, C, O-0.3s-C, CO, O-CO, O-0.3s-CO, first trip and slow close. Contact timing of the shunt resistor contacts is measured separately, so synchronisation errors between main and resistor contacts appear in a single record.
The unit covers 3 phases with up to 4 breaks per phase, and it has three travel channels, three auxiliary contact inputs and three analogue inputs. For oil circuit breakers a configuration with 3 contacts is provided. Digital linear and rotary motion sensors measure travel from 0.0 to 1000.0 mm (0.0 to 40.0 inch) and from 0.0 to 2880.0°, with an error of ± 0.1 % of value, a resolution of 0.03 mm and 0.09°. Speed is measured up to 15 m/s and acceleration up to 1200 g for no more than 50 ms. Signals from the motion sensors give early diagnosis of mechanical faults in the operating mechanism.
The measuring inputs withstand ± 25 A and ± 300 V, with isolation to chassis of 1.0 kV. A recording with reduced resolution lasts up to 30 minutes. Accuracy is not affected by the electrostatic and electromagnetic interference typical of substations. Additional sensors, including those from third-party manufacturers, can be connected in the operating mechanism cabinet.
Control is from a computer, tablet or universal controller, and the included software produces reports in spreadsheet, text and PDF formats. The unit measures 60.9 × 39.4 × 21.6 cm and weighs 10 kg. It runs from a 100–240 V, 50/60 Hz supply, works from 0 to 50 °C, stores from -25 to +70 °C, and tolerates humidity up to 95 % without condensation.
Technical specifications
| Number of phases | 3 |
|---|---|
| Breaks per phase | 4 |
| Travel channels | 3 |
| Aux contact inputs | 3 |
| Analogue inputs | 3 |
| Linear travel | 0.0 to 1000.0 mm (0.0 to 40.0 inch) |
| Rotary travel | 0.0 to 2880.0° |
| Motion sensor accuracy | ± 0.1 % of value |
| Resolution | 0.03 mm; 0.09° |
| Velocity | up to 15 m/s |
| Acceleration | 1200 g, 50 ms maximum |
| Maximum input current | ± 25 A |
| Maximum input voltage | ± 300 V |
| Isolation to chassis | 1.0 kV |
| Recording time | up to 30 min at reduced resolution |
| Dimensions | 60.9 × 39.4 × 21.6 cm |
| Weight | 10 kg |
| Power supply | 100–240 V, 50/60 Hz |
| Operating temperature | 0 to 50 °C |
Part numbers
Show all part numbers (1)
TDR900
Request a price and lead time
TDR900 Portable Circuit Breaker Analyser, Four Breaks per Phase, Motion Measurement. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many breaks per phase can the TDR900 test?
Up to 4 breaks per phase, with three travel channels, three auxiliary contact inputs and three analogue inputs.
Which operating sequences are supported?
O, C, O-0.3s-C, CO, O-CO, O-0.3s-CO, first trip and slow close.
Can sensors from other manufacturers be connected?
Yes, additional sensors, including those from third-party manufacturers, can be connected in the operating mechanism cabinet.