International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

T 3000 Primary Injection System for Substation Equipment up to 800 A

The T 3000 carries out primary tests during commissioning of substations. One unit tests current and voltage transformers, power transformers, protection relays, energy meters and converters.

High AC current
up to 800 A; 600 VA continuous, up to 2000 VA short-term
With BU2000 amplifier
up to 4000 A AC
High-voltage output
3000 V, 0.2 A continuous; 2500 V, 0.6 A, 1 min
High-voltage option
1200 V, 0.5 A, 600 VA

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

For current transformers the set determines the ratio and polarity, the secondary burden, the excitation curve with its knee point, the winding resistance, and the withstand of the test voltage. Voltage transformers are checked for ratio, polarity and burden, and power transformers receive a dynamic check of the on-load tap changer. Separate modes test thermal relays, voltage and current relays, earth fault protection and auto-reclosing with up to 49 commands, and they also measure earth resistance and line impedance.

The high current AC output gives 600 VA continuously and up to 2000 VA for short periods, with a maximum current of 800 A. The external BU2000 amplifier, fitted with one, two or four transformers, raises the current to 2000, 3000 or 4000 A. The high-voltage output provides 3000 V at 0.2 A continuously and 2500 V at 0.6 A for one minute, and an optional 1200 V output is available for circuits with 5 A secondaries. The high DC current module gives 100 A continuously, 200 A for 4 minutes and 400 A for 15 s.

The auxiliary sources provide AC voltage of 65, 130 and 260 V and DC voltage of 130 or 240 V at 90 W. Frequency is adjustable from 40 to 500 Hz, and the phase angle from 0° to 360°. Accuracy of current and voltage measurement is ± 0.5 %, of ratio and resistance 0.5 % typically and 1 % maximum, and of the angle 1°. External inputs accept 20 mA or 10 A AC current and 10 V or 600 V voltage.

The display is a 240x128 pixel FSTN panel, memory stores up to 500 results, and the RS232 interface runs at 57600 baud. The unit operates from 230 V or 110 V ± 10 % at 50-60 Hz with a maximum current of 16 A. It measures 455 × 325 × 290 mm and weighs 34 kg, works from 0 to 50 °C, and has protection IP 2X with IP 4X for the high-voltage output. Testing is done to the EN 60044-1 and EN 60044-2 series, EN 60076-1 and ANSI/IEEE C57.13.1, and safety meets CEI EN 61010-1.

Technical specifications

High AC currentup to 800 A; 600 VA continuous, up to 2000 VA short-term
With BU2000 amplifierup to 4000 A AC
High-voltage output3000 V, 0.2 A continuous; 2500 V, 0.6 A, 1 min
High-voltage option1200 V, 0.5 A, 600 VA
DC module100 A continuous; 200 A for 4 min; 400 A for 15 s
Auxiliary AC voltage65, 130, 260 V
Auxiliary DC voltage130 or 240 V, 90 W
Frequency range40 to 500 Hz
Phase angle0° to 360°
Current and voltage error± 0.5 %
Ratio and resistance error0.5 % typical; 1 % max.
Memoryup to 500 results
InterfaceRS232, 57600 baud
Power supply230 V or 110 V ± 10 %, 50-60 Hz; up to 16 A
Dimensions455 × 325 × 290 mm
Weight34 kg
Operating temperature0 to 50 °C
Protection degreeIP 2X; 4X for the high-voltage output

Part numbers

Show all part numbers (6)

PII20102, PII30102, PII40102, PII50102, PII51102, PII52102

Request a price and lead time

T 3000 Primary Injection System for Substation Equipment up to 800 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How is a current above 800 A obtained?

Through the external BU2000 amplifier: up to 2000 A with one transformer, 3000 A with two and 4000 A with four.

What is the 1200 V option for?

The 1200 V output replaces the standard 3000 V output and is intended for current transformers with 5 A secondaries.

Can contact resistance be measured with a large DC current?

Yes. The DC module delivers 100 A continuously, 200 A for 4 minutes and 400 A for 15 s.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides