T 3000 Primary Injection System for Substation Equipment up to 800 A
The T 3000 carries out primary tests during commissioning of substations. One unit tests current and voltage transformers, power transformers, protection relays, energy meters and converters.
- High AC current
- up to 800 A; 600 VA continuous, up to 2000 VA short-term
- With BU2000 amplifier
- up to 4000 A AC
- High-voltage output
- 3000 V, 0.2 A continuous; 2500 V, 0.6 A, 1 min
- High-voltage option
- 1200 V, 0.5 A, 600 VA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
For current transformers the set determines the ratio and polarity, the secondary burden, the excitation curve with its knee point, the winding resistance, and the withstand of the test voltage. Voltage transformers are checked for ratio, polarity and burden, and power transformers receive a dynamic check of the on-load tap changer. Separate modes test thermal relays, voltage and current relays, earth fault protection and auto-reclosing with up to 49 commands, and they also measure earth resistance and line impedance.
The high current AC output gives 600 VA continuously and up to 2000 VA for short periods, with a maximum current of 800 A. The external BU2000 amplifier, fitted with one, two or four transformers, raises the current to 2000, 3000 or 4000 A. The high-voltage output provides 3000 V at 0.2 A continuously and 2500 V at 0.6 A for one minute, and an optional 1200 V output is available for circuits with 5 A secondaries. The high DC current module gives 100 A continuously, 200 A for 4 minutes and 400 A for 15 s.
The auxiliary sources provide AC voltage of 65, 130 and 260 V and DC voltage of 130 or 240 V at 90 W. Frequency is adjustable from 40 to 500 Hz, and the phase angle from 0° to 360°. Accuracy of current and voltage measurement is ± 0.5 %, of ratio and resistance 0.5 % typically and 1 % maximum, and of the angle 1°. External inputs accept 20 mA or 10 A AC current and 10 V or 600 V voltage.
The display is a 240x128 pixel FSTN panel, memory stores up to 500 results, and the RS232 interface runs at 57600 baud. The unit operates from 230 V or 110 V ± 10 % at 50-60 Hz with a maximum current of 16 A. It measures 455 × 325 × 290 mm and weighs 34 kg, works from 0 to 50 °C, and has protection IP 2X with IP 4X for the high-voltage output. Testing is done to the EN 60044-1 and EN 60044-2 series, EN 60076-1 and ANSI/IEEE C57.13.1, and safety meets CEI EN 61010-1.
Technical specifications
| High AC current | up to 800 A; 600 VA continuous, up to 2000 VA short-term |
|---|---|
| With BU2000 amplifier | up to 4000 A AC |
| High-voltage output | 3000 V, 0.2 A continuous; 2500 V, 0.6 A, 1 min |
| High-voltage option | 1200 V, 0.5 A, 600 VA |
| DC module | 100 A continuous; 200 A for 4 min; 400 A for 15 s |
| Auxiliary AC voltage | 65, 130, 260 V |
| Auxiliary DC voltage | 130 or 240 V, 90 W |
| Frequency range | 40 to 500 Hz |
| Phase angle | 0° to 360° |
| Current and voltage error | ± 0.5 % |
| Ratio and resistance error | 0.5 % typical; 1 % max. |
| Memory | up to 500 results |
| Interface | RS232, 57600 baud |
| Power supply | 230 V or 110 V ± 10 %, 50-60 Hz; up to 16 A |
| Dimensions | 455 × 325 × 290 mm |
| Weight | 34 kg |
| Operating temperature | 0 to 50 °C |
| Protection degree | IP 2X; 4X for the high-voltage output |
Part numbers
Show all part numbers (6)
PII20102, PII30102, PII40102, PII50102, PII51102, PII52102
Request a price and lead time
T 3000 Primary Injection System for Substation Equipment up to 800 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How is a current above 800 A obtained?
Through the external BU2000 amplifier: up to 2000 A with one transformer, 3000 A with two and 4000 A with four.
What is the 1200 V option for?
The 1200 V output replaces the standard 3000 V output and is intended for current transformers with 5 A secondaries.
Can contact resistance be measured with a large DC current?
Yes. The DC module delivers 100 A continuously, 200 A for 4 minutes and 400 A for 15 s.