T 2000 Primary Injection Test Set for Current Transformers up to 800 A
The T 2000 tests current transformers, covering the excitation curve, ratio and polarity, and winding resistance. The set suits substation maintenance and commissioning, where accurate measurement and a portable design are needed.
- High AC current
- up to 800 A
- With BU 2000 amplifier
- up to 4000 A
- High-voltage output
- 3000 V, 0.2 A, 600 VA; option 1200 V, 0.5 A, 600 VA
- Low AC voltage
- 250 V, 0.5 A, 125 VA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Beyond current transformers, the set checks voltage transformers for ratio, polarity and secondary burden, carries out primary injection for testing maximum current relays, measures earth resistance and soil resistivity, and determines line parameters such as impedance and coupling factor. A dynamic test of the on-load tap changer is provided for power transformers.
The high current AC output delivers up to 800 A, and with the external BU 2000 amplifier the current rises to 4000 A. The high-voltage output supplies up to 3000 V AC at 0.2 A, 600 VA continuously, and a 1200 V version is available as an option at 0.5 A and 600 VA. The low AC voltage output gives 250 V, 0.5 A and 125 VA. An optional high DC current module turns the set into a micro-ohmmeter with a current of 400 A DC at most.
Current and voltage measurement accuracy is ± 0.5 %, phase angle accuracy 1°, and frequency resolution 1 mHz. Ratio and resistance measurement error is 0.5 % typically and no more than 1 %, and resistance up to 250 Ohm can be measured. The timer covers ranges from 0 to 9.999 s up to 1000 to 9999 s, and the auxiliary binary output contact is rated 5 A, 250 V AC. Results appear on a 240x128 pixel FSTN display, memory holds up to 500 results and up to 10 settings, and the set communicates with a computer over RS232.
The set runs from a 230 V ± 10 % or 120 V ± 10 % supply at 50-60 Hz, with a maximum current of 16 A. It measures 455 × 325 × 290 mm and weighs 31 kg, while the T 2000E version, with more power for high current tests on a 1200 V generator, weighs 37 kg. The operating range is 0 to 50 °C, storage runs from -20 to 70 °C, humidity 5–95 % without condensation, and protection is IP 2X with IP 4X for the high-voltage output. Testing is done to the EN 60044-1 and EN 60044-2 series, EN 60076-1 and ANSI/IEEE C57.13.1, and the set meets CEI EN 61010-1 and EN 61326-1.
Technical specifications
| High AC current | up to 800 A |
|---|---|
| With BU 2000 amplifier | up to 4000 A |
| High-voltage output | 3000 V, 0.2 A, 600 VA; option 1200 V, 0.5 A, 600 VA |
| Low AC voltage | 250 V, 0.5 A, 125 VA |
| DC module (option) | 400 A DC maximum |
| Current and voltage accuracy | ± 0.5 % |
| Phase angle error | 1° |
| Ratio and resistance error | 0.5 % typical; 1 % max. |
| Measurable resistance | up to 250 Ohm |
| Memory | up to 500 results, up to 10 settings |
| Display | FSTN LCD, 240x128 pixels |
| Interface | RS232 |
| Power supply | 230 V ± 10 % or 120 V ± 10 %, 50-60 Hz |
| Dimensions | 455 × 325 × 290 mm |
| Weight | 31 kg (T 2000E 37 kg) |
| Operating temperature | 0 to 50 °C |
| Protection degree | IP 2X; 4X for the high-voltage output |
Part numbers
Show all part numbers (4)
PII20110, PII30110, PII40110, PII50110
Request a price and lead time
T 2000 Primary Injection Test Set for Current Transformers up to 800 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the maximum primary injection current?
The set alone delivers up to 800 A, and with the external BU 2000 amplifier it reaches 4000 A AC.
How does the T 2000E differ?
The T 2000E is built on a 1200 V generator with more power for high current output, and it weighs 37 kg.
Can the set measure the winding resistance of a current transformer?
Yes. Resistance up to 250 Ohm can be measured, with an error of 0.5 % typically and no more than 1 %.