International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

STS 5000 Multifunction Test System, 800 A AC and 400 A DC Outputs

The STS 5000 carries out primary tests on current transformers, voltage transformers, power transformers and earthing devices during substation commissioning. Its high-current outputs of 800 A AC and 400 A DC also allow micro-ohm contact resistance and circuit breaker timing measurements.

Test objects
current transformers, voltage transformers, power transformers, earthing devices, circuit breakers
High-current AC output (230 V)
800 A / 4800 VA / 25 s; 400 A / 2560 VA / 500 s; 200 A / 1300 VA / over 2 hours
High-current DC output
400 A / 2600 W / 140 s; 200 A / 1300 W / over 2 hours
Primary injection with BUX 5000
5000 A or 7000 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The STS 5000 is a multifunction system for commissioning and maintaining substations. It tests current transformers, voltage transformers, power transformers and earthing devices, and runs the work from test plans. The PADS software conducts the tests as planned, evaluates the results and produces the test report.

The system has high-current outputs for both AC and DC, and it accepts the BUX 5000, BUX 3000 and BUX 2000 boosters. On a 230 V supply, the AC output delivers 800 A at 4800 VA for 25 s, 400 A at 2560 VA for 500 s, and 200 A at 1300 VA for more than two hours. The DC output gives 400 A at 2600 W for 140 s and 200 A at 1300 W for more than two hours. With the BUX 5000 the primary injection current rises to 5000 A or 7000 A.

For current transformers the system measures the turns ratio in voltage mode, polarity, secondary burden, ALF and ISF, the excitation curve and the knee voltage, along with winding resistance and burden, and it runs voltage withstand tests. It also checks Rogowski coils, low-power transformers and transformers with IEC 61850-9 output. For power transformers it covers turns ratio, vector group, winding resistance, OLTC dynamic resistance, excitation and no-load current, short-circuit impedance and leakage reactance.

The main generator also provides a high-voltage AC output up to 2000 V AC for voltage withstand tests, low-voltage outputs of 6 A or 3 A AC at 70 V or 140 V, and 6 A DC at 65 V DC, with a frequency range of 15 to 500 Hz at 10 mHz resolution. Ratio measurement accuracy is within 0.15% of reading, and the phase angle error is below 0.1°.

The TD 5000 module adds tan delta and capacitance measurement at voltages up to 12 kV. The STCS and STCS PLUS automate switching for transformer tests, and the STDE demagnetises the core.

Control is local from a 640 by 480 TFT display or remotely by computer over USB or Ethernet, and the IEC 61850-9-2 protocol is supported. The unit runs from 100 to 230 V with a tolerance of ±15%, 48 to 62 Hz, draws up to 16 A, and its maximum power is 3.6 kW. It measures 450 × 400 × 230 mm and weighs 29 kg. It works at -10 to 55 °C, with humidity of 5 to 95% without condensation, and carries IP 2X protection with IP 4X on the high-voltage output.

Technical specifications

Test objectscurrent transformers, voltage transformers, power transformers, earthing devices, circuit breakers
High-current AC output (230 V)800 A / 4800 VA / 25 s; 400 A / 2560 VA / 500 s; 200 A / 1300 VA / over 2 hours
High-current DC output400 A / 2600 W / 140 s; 200 A / 1300 W / over 2 hours
Primary injection with BUX 50005000 A or 7000 A
High-voltage AC output2000 V AC
Low-current AC output6 A or 3 A AC, 70 V or 140 V AC, 360 VA
Low-current DC output6 A DC, 65 V DC, 360 W
Output frequency15 to 500 Hz, 10 mHz resolution
Tan delta with TD 5000maximum 12 kV
Ratio measurement accuracybelow 0.15% of reading, below 0.15% of range
Phase angle errorbelow 0.1°
DisplayTFT, 640 x 480, 132 x 99 mm
InterfacesUSB, Ethernet, IEC 61850-9-2
Mains supply100 to 230 V ±15%, 48 to 62 Hz, up to 16 A, 3.6 kW
Dimensions450 x 400 x 230 mm
Weight29 kg
Operating temperature-10 to 55 °C
Protection classIP 2X, IP 4X for the high-voltage output

Request a price and lead time

STS 5000 Multifunction Test System, 800 A AC and 400 A DC Outputs. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is the maximum primary injection current?

The built-in outputs reach 800 A AC, and with the BUX 5000 booster the figures rise to 5000 A or 7000 A.

How long can the AC output deliver 800 A?

On a 230 V supply it gives 800 A at 4800 VA for 25 s, while 200 A at 1300 VA can be held for more than two hours.

Can tan delta and capacitance be measured?

Yes, with the TD 5000 module at voltages up to 12 kV.